correct report

profileMashael Abdulaziz
report.docx

Abstract

The purpose of this experiment was to operate a packed column and measure the experimental pressure drop values for four different regimes: dry, 40% irrigated, 60% irrigated, and wet. The trials were carried out exactly in that order. Each main trial consisted of 5 sub-trials. The operators only changed the velocity of air for each sub-trial. The other parameters were set before. Another purpose of this lab was to obtain more data that are required to calculate the theoretical pressure drop via mathematical correlations.

The experimental results were then compared with theoretical. The results followed the expected general trend: the velocity of air was directly proportional to the pressure drop. It is evident from Reynolds number that all conditions were operated at intermediate flow regime that share properties of both laminar and turbulent flows.

The results for experimental pressure drop are: 618-961.4 Pa over the range of velocity 1.89-2.43m/s for dry condition; 971.2-1805.04 Pa over 1.77-2.21 m/s for 40% irrigated; 1108.53-2315.16 Pa over 1.73-2.18 m/s for 60% irrigated; and 725.9-1088.9 Pa over 2.24-3.44 m/s for wet condition.

Dry regime has the lowest pressure drop in this experiment, while 60% irrigate has the highest. The pressure drops of other trials increase in this order: wet, and 40% irrigated. Irrigated regimes have higher pressure drop because the stream of air meets the counter-current stream of water. During wet regime the air only meets resistance from the water at the surface of packing.

The resistance from water is important in this experiment. More resistance results in more pressure building up inside the column. This explains why one condition has higher pressure drop than the other.

The wet column has higher pressure drop then dry column and lesser than both irrigated column as it was been predicted. Also, it was conducted at 60% irrigated column for comparative purpose. Lower viscosity and density of the air were supposed to result in lower pressure. However, the result was complete opposite. This could be happened due to various sources of error, mainly due to oscillating level in manometers. Besides, the change in temperature was not large enough to see the significant change.

Table of Contents

Table of Contents 3

1 Nomenclature 5

2 Introduction 7

3 Results and Discussion 14

3.1 General Trends 14

3.2 Dry Conditions 15

3.3 Irrigated, 40% 17

3.4 Irrigated, 60% 19

3.5 Wet Conditions 21

4 Sources of Error 23

5 Conclusions 23

6 Acknowledgements 24

7 Works Cited 25

List of Figures

Figure 1: PFD of the Packed Column 1 3

Figure 2: Comparison Chart 1 4

Figure 3: Pressure Drop (Reduced to Friction Factor) versus Reynolds Number Plot 1 5

Figure 4: Pressure Drop vs. Fluid Velocity for Dry Column 1 6

Figure 5: Pressure Drop vs. Fluid Velocity for Irrigated 40% Column 1 8

Figure 5: Pressure Drop vs. Fluid Velocity for Irrigated 60 % Column ……………......... 20

Figure 5: Pressure Drop vs. Fluid Velocity for Wet Column ……………………… ……2 2

List of Tables

Table 1: Dry Column 1 6

Table 2: Irrigated Column at 40% Maximum Flow of Water 1 8

Table 3 : Irrigated Column at 60% Flow of Water 1 9

Table 4 : Wet Column 2 2

Nomenclature

X Particle Diameter (ft)

ε Bed Voidage

U Gas Velocity (ft/s)

H Bed Height (ft)

µ Fluid Viscosity (Pa.s)

ρ Fluid Density (lb/ft3)

ΔP Pressure drop (inches H2O)

U Superficial air velocity (ft/s)

ρg Density of air (lb/ft3)

C2 Packing coefficient

Q air flow rate (m3/s)

C Coefficient of discharge for orifice

ΔPt  total pressure drop, inches H2O per foot of packing

ΔPL  pressure drop due to liquid presence

ΔPd dry pressure drop

gas loading factor

it’s a picking factor

dry picking factor 1/ft

superficial F-factor for gas

G gas mass velocity lb/hr..

gas loading factor lb/hr..

L liquid mass velocity lb/hr..

liquid loading factor lb/hr..

Introduction

The packed bed separation process have been widely used in a chemical engineering. Absorption is one of several separation vassals. How it works? The mechanism of this column is to increase the contact area between the gas and the liquid by filled the tower beds. Moreover, this beds might be reactant with the flow or it does not react on the other hand to control the process inside the vassals. (Chao, 1981 )

There are several parameter that can be managed to have the final product such as temperature, the type of the beds, flow rate of the liquid and the gas, and the pressure drop inside the column. A real application in the industrial can emphasis this kind of process. Analysing a Gasoline and pure Naphtha by using a packed bed column is one of this technology used in the oil refinery. (A. Di Corcia, 1978) Optimise this on the packed column in the B-24 by using a several correlation method help the team to study the pressure drop inside the column and how can the other parameters be affected.

There are two parameters of packed beds that should be maximized and balanced: open area and wetted surface area. Firstly, open area is the average percentage of the cross-sectional area of the tower that is not blocked by packing. In other words, it is space available for the flow of liquid and vapour.

Secondly, Wetted surface area is taken by the surface of the packing. This area is available for liquid-vapour contact. In addition, large open area allows great capacity of the tower. On the other hand, large wetted surface area of the packing makes separation more efficient. These features should be balanced in packed column. For example, an empty column has great capacity, but is very inefficient. On the other hand, a column filled completely with sand will be highly efficient, but very low on capacity. (Lieberman, 2008) In any type of packed tower, the liquid drips through the packing and forms a thin film on the surface of the packing. The vapour starts percolates through the packing, and exchanges heat or molecules with the thin film of liquid (Lieberman, 2008)

The main purpose of packing is to increase the contacting surface area to volume ratio. Various shapes of packing result in different voidage and surface area. The reaction or separation proceeds faster when more surface area is exposed. Packed columns are generally used in industry for catalytic reactions, distillation, absorption, drying, and other separation processes.

In this experiment, the lab team operated packed column to obtain experimental values for pressure drop under three different conditions. Several mathematical models will be also applied to calculated theoretical pressure drop. For comparative purposes, the experimental and theoretical data will be plotted on a same graph for each condition

2. Theory

Three mathematical models were tested in this experiment. Equation 1 is Ergun equation for flow through a randomly packed bed of particles. The advantage of using Ergun equation is the fact that it combines laminar and turbulent components of the pressure gradient. Under laminar conditions, the second term becomes negligible. Under turbulent conditions, on the other hand, the second term dominates (Rhodes, 2008).

1

Where: X = Particle Diameter (ft)

ε = Bed Voidage

U = Gas Velocity (ft/s)

H = Bed Height (ft)

µ = Fluid Viscosity (Pa.s)

ρ = Fluid Density (lb/ft3)

2

Leva developed two more correlations. Equation 3 represents Leva equation for wetted column (Perry & Chilton, 1973).

3

Where: ΔP = Pressure drop (inches H2O)

U = Superficial air velocity (ft/s)

ρg = Density of air (lb/ft3)

C2 = Packing coefficient

For irrigated conditions the Leva Equation takes this form:

4

There is no Leva equation available for the dry column.

There were no apparatus available in this lab to measure the flow rate of air directly. Instead, the flow rate can be estimated from the pressure drop of air across the orifice according to equation 5 (Perry & Chilton, 1973).

5

Where: Q = air flow rate (m3/s)

C = Coefficient of discharge for orifice

Ao = orifice area (m2)

Do = orifice diameter (m)

DS = air supply pipe diameter (m)

g = gravitational acceleration (m/s2)

ΔP = Orifice Pressure drop (Pa)

ρ = air density (kg/m3)

In these correlations the pressure drop is directly proportional to the superficial velocity;

Vs=V* 6

This equation will give the team the option to predict the superficial velocity (Rhodes, 2008)

7

This correlation will be used to determine the pressure drop experimentally (M, 2006)

Where: ρ = Fluid Density (lb/ft3)

P = Pressure drop (inches H2O)

h= the height differences in the manometers (inch)

The following correlations will measure the pressure drop for the dry column and the irrigated column and it’s called Robbin’s (Perry & Chilton, 1973).

8

ΔPt = total pressure drop, inches H2O per foot of packing 9

ΔPL =pressure drop due to liquid presence = 10

ΔPd= dry pressure drop = 11

= gas loading factor=986 12

=liquid loading factor= if greater than 200 13

The term it’s a picking factor. If less than

= 14

=dry picking factor 1/ft

=superficial F-factor for gas,, ft./s

G=gas mass velocity lb/hr..

=gas loading factor lb/hr..

L=liquid mass velocity lb/hr..

=liquid loading factor lb/hr..

Test Methods

The purpose of this experiment is to measure the pressure drop over the packed column under different fluid flow conditions and then compare experimental results with mathematical models. The optimum operating conditions were then determined from the results.

The apparatus for this experiment consists of a packed column filled with ¾ inch Raschig Rings, various meters and gauges, an air blower. The setup is shown on Figure 1.

The blower supplies air to the column at constant flow rate. Valve V-1 opens a side withdraw that removes some of the air, thus decreasing the flow rate. The flow rate of air to the column is at its maximum when the valve is completely closed. Gauges T-1 and T-2 measure the temperature of air before and after the orifices respectively.

The air passes through the column and exits from the top. Gauge T-4 measures the temperature of exit air. Water supply enters the column from the top. F-1 measures the flow rate of water in percents of maximum flow, which is 1.96 USGPM. The temperature of water supply is measured by T-5.

The water flows through the packing and leaves column from the bottom. Thermometer T-3 measures the temperature of exit water stream. There are also three manometers available in this experiment. P-1 measures the pressure of air from the blower and it has Mercury. P-2 takes readings across the orifice and it has an oil gage. The pressure drop over the column is measured by P-3 and it contain water with a green indicator to make the riding more easily.

The lab team carried out this experiment under four different conditions: dry column, two different irrigated conditions, and wet. Each condition consisted of 5-sub-trials. The sub-trials vary by the flow rate of air. The other factors remained constant, such as temperature of air supply and flow rate of water.

The experiment started with a dry column. For the second main trial the water supply was switched on at 40% of maximum flow. The column became irrigated due to constant supply of water. For the next trial the flow rate of water was increased up to 60%. The water supply was then shut down for the last trial, and the air went through the wet column. Each trial had air supply.

The team leader controlled the flow rates and recorded the readings from pressure gauges. Adam took readings from the top of the column. Joshua recorded temperature readings from the gauges located at the bottom of the column.

Figure 1: PFD of the Packed Column

Results and Discussion

General Trends

The experimental results are shown on Figure 2.

Figure 2: Comparison Chart

The pressure drop tends to increase as the superficial velocity of air increases. This was expected from the mathematical correlations and is common to all four conditions observed in this experiment.

The range of Reynolds numbers is 239-318. The flow regime was intermediate for the entire experiment, because Reynolds numbers are greater than 10 (laminar regime) and less than 2000 (turbulent regime).

The experimental graphs of pressure drop versus superficial velocity of air are curves. This proves that flow regime is indeed intermediate. Laminar flow supposed to have a straight line with a negative slope, while turbulent flow results in horizontal line as shown on figure 3.

Figure 3: Pressure Drop (Reduced to Friction Factor) versus Reynolds Number Plot

Dry Conditions

The results for dry trial are presented in Table 1. Ergun equation is working only for Dry regimes; hence it is missing from this section. The graph of pressure drop versus superficial fluid velocity is shown on Figure 4. The experimental pressure drop values are smaller than the ones predicted by Ergun equation. Such difference may result from errors. The sources of errors will be discussed later on.

Table 1: Dry Column

Superficial Velocity, m/s

Experimental Pressure Drop, Pa

Ergun Equation, Pa

%Diff

1.89

618.03

651.35

0.051

2.04

706.32

754.74

0.064

2.14

765.18

834.24

0.082

2.25

824.04

917.71

0.102

2.34

882.9

997.18

0.114

2.44

961.38

1076.65

0.107

Table 1 above presents the numerical results obtained for the dry regime. By analyzing the dry regime, it can be noticed that the pressure drop, obtained experimentally, across the packed column increases with increasing air velocity during different conditions.

Figure 4: Pressure Drop vs. Fluid Velocity for Dry Column

As shown above, represents the results obtained for the dry regime. The reason for the difference between the Erqun pressure drop and the experimental one, that Erqun is theoretical and used at steady state conditions, hence there will be error and difference between them. From the above figure we notice that the experimental and theoretical pressure drop increase with increasing the airflow.

Irrigated, 40%

Table 2 and Figure 5 show the results for irrigated condition at 40% of maximum flow rate. Both Robbin and Leva equations does not fit experimental values equally. On the other hand, leva equation will be more accurate with the experimentally date by comparing the distance between the graphs.

Moreover, by comparing Robbins data dose not consistent with the experimental data. The sources of error will be discussed later on. In comparison with dry column irrigated condition results in higher pressure drop at corresponding flow rates. This happens because the stream of air meets more resistance from the counter-current flow of water. This results in more pressure building up inside the column.

Figure 5and 6 along with tables 2and 3, show the results for the 40% and 60% irrigated bed. The experimental pressure drop was increasing as the flows of water and air were gradually increasing. For 60% irrigated flow, the pressure drop increased significantly compare to the pressure drop of 40% irrigated flow.

Table 2: Irrigated Column at 40% Maximum Flow of Water

Superficial Velocity, m/s

Experimental delta Pa

Robbins (Pa)

% Diff

Leva(pa)

%Diff

1.77

971.19

24953.02

0.96107927

826.1488

0.15

1.93

1167.39

49016.05

0.97618351

1029.97757

0.11

2.02

1334.16

69831.19

0.9808945

1156.03252

0.13

2.11

1589.22

98645.22

0.98388954

1294.83166

0.18

2.22

1805.04

145697.82

0.98761107

1473.13452

0.18

Figure 5: Pressure Drop vs. Fluid Velocity for Irrigated 40% Column

Irrigated, 60%

This trial has potential for flooding. When the velocity of air is low enough, the water does not meet enough resistance and can freely flow through the packed bed. However, when both water and air streams run at high velocities, the resistance may become great enough to stop water from flowing downwards. Now that water is stuck in the middle of the column by air resistance, it can only move upwards until the column is overflown. The flooding occurred when the velocity of air was 2.19 m/s.,only five data points were obtained.

Due to a higher resistance caused by higher flow rate of water the pressure drop is expected to be greater than in the previous trial. In fact, as shown on Figure 2, this trial has the largest pressure drop in the entire experiment.

The experimental results fit Ergun equation better than Leva. At higher velocity the difference suddenly rises up, resulting in a much greater error. The main source of error in this trial is flooding.

Table 3: Irrigated Column at 60% Flow of Water

Superficial Velocity, m/s

Experimental Pressure Drop, Pa

Leva Equation, Pa

Diff%

Robbin (pa)

Diff%

1.73

1108.53

998.1

0.292

21139.14

0.947

1.89

1393.02

1080.7

0.299

41565.51

0.966

2.00

1638.27

1261.3

0.308

65495.85

0.974

2.07

1903.14

1333.0

0.349

85866.22

0.977

2.19

2315.16

1428.4

0.386

130824.89

0.982

Figure 6: Pressure Drop vs. Fluid Velocity for 60% Irrigated Flow

As you can see the percentage difference for the results in the tables is much higher than we would like. This is a clear indication that the Robin equation is not an optimal method of calculating the pressure drop through packed beds while irrigated.

I would guess this is due to the fact that the robin equation does not account for the added flow of water through the column. This is evident due to the much smaller pressure drops across the column resulting from the robin calculation relative to the actual experimental data.

Comparing the results obtained in this section of the experiment with the results for the dry run it is clear that the irrigation largely increases the pressure drop through the column. This makes sense as the water would increase resistance to the air flow upward through the bed. Error in experimentation could have occurred due to fluctuating water flows as it was difficult to keep the rotameter at a constant level. Calculation error could have occurred due to large amounts of unit conversions.

Wet Conditions

In this trial the air stream experienced much less resistance, since there was no counter-current stream of water in the column. That is the reason pressure drop is lower than in irrigated trials. However, a significant amount of the water remained on Raschig rings because combined together they create large surface area. This resulted in notable increase in pressure drop, comparing to dry column. Leva correlation works better for this trial resulting in less error.

Moreover From the presented figure below for air flowing through wet packing, the experimental pressure drop in the packed column are lower compared to the theoretical pressure drop obtained from Leva equation. However, the two methods of calculation proved the same point which is: as the flow of the air increases, the pressure drop in the packed column increases because of the high friction between air, the pack and column walls which poses a significant impact on the pressure in the column

Table 4: Wet Column

Superficial Velocity, m/s

Experimental Pressure Drop, Pa

Leva Equation, Pa

%Diff

2.25

725.94

811.34

0.10

2.58

833.85

1068.85

0.21

2.89

912.33

1344

0.32

3.17

1010.43

1615.62

0.37

3.44

1088.91

1901.35

0.42

Figure 7: Pressure Drop vs. Fluid Velocity for Wet Column

4 Sources of Error

The main source of error is unstable reading from the manometers. The fluid level in manometers oscillated with an amplitude of 5-10 mm. This indicates that the flow rate of air was not constant. The amplitude was larger at higher velocities of supplied air. That’s the main reason all graphs have more error at the right side.

Irrigated conditions have more error, because there were two streams. The flow rate of water varied even more than the flow rate of air. The flooding at the end of 60% irrigated run added even more error to the trial.

Some errors may result from correlations. For example, Ergun equation does not account for friction forces. This may explain that experimental results are generally lower than theoretical. On the other hand, using Robbin equation on the irrigated column is not a good idea because the high difference in the pressure drop comparing with the theoretical result moreover Robbin equation dose have a lot of terms involved in it so that one of the major sources of error Also the unit conversion is kind of tricky to get it in SI unit

5 Conclusions

· The pressure drop is directly proportional to the superficial fluid velocity for packed columns.

· The packed column in this experiment operated under intermediate flow regime.

· Dry column has the lowest pressure drop.

· Irrigated column at 60% of maximum flow rate has the highest pressure drop.

· The pressure drop of other trials increases in this order: wet 40% irrigated

· Overall, Ergun equation works better than Leva and Robbin equations, because it accounts for both laminar and turbulent regimes.

· Leva works better for wet condition, because it was specifically designed for that.

· Both equations yield rather equal error under irrigated conditions. Leva seems to work slightly better than Robbin , however, more trials are required to identify which equation is more suited for irrigated conditions.

1. Acknowledgements

I would like to acknowledge the efforts of my teammates Adam and Joshua in helping me to conduct this experiment and prepare this formal report. I would also like to thank theTA Andrew and Mr. Jamie for their help in pre-lab and supervision of this experiment

Works Cited A. Di Corcia, R. S. (1978). Gas Chromatographic analysis of gasoline and pure naphtha using packed column. Chao, j. T. (1981 ). Analysis of packed bed process . Lieberman, N. P. (2008). A Working Guide to Process Equipment. New York: R. R. Donnelley & Sons Company. M, Y. A. (2006). Fluid mechanics fundamentals and applications. Perry, R. H., & Chilton, C. H. (1973). Perry's Chemical Engineers' Handbook. New York: McGraw-Hill. Rhodes, M. (2008). Introduction to Particle Technology, second edition. Australia: John Wiley & Sons,Ltd.

Appendix A

Appendix B

Appendix C

Dry 1.891987421407068 2.037301686117801 2.1423853287384413 2.247441316287428 2.3431195459666698 651.34954954016825 754.7359145115048 834.24206648207246 917.70631491625238 997.18181887082471 Wet 2.247441316287428 2.5795607297579863 2.8925903323832713 3.1714449808656635 3.44047831698238 811.33565846222609 1068.8465413654544 1343.9951559743836 1615.6162242421726 1901.3474778745215 Irrigated 40% 1.7721172834288601 1.932185876293975 2.0210679478380094 2.1114094524353004 2.2179331480446343 24953.023370066734 49016.046224068334 69831.192083280897 98645.224580308641 145697.82415837058 Irrgated 60% 1.73454162396 48723 1.891987421407068 2.0047027558463251 2.0746864866879973 2.18802706295754 21139.138197940934 41565.510284641503 65495.846664083278 85866.223184380608 130824.89427363624

Dry Column

Erqun Pa 1.891987421407068 2.037301686117801 2.1423853287384413 2.247441316287428 2.3431195459666698 2.4350412610931946 651.34954954016825 754.7359145115048 834.24206648207246 917.70631491625238 997.18181887082471 1076.6450820318435 Expermintal delta Pa 1.891987421407068 2.037301686117801 2.1423853287384413 2.247441316287428 2.3431195459666698 2.4350412610931946 618.03000000000009 706.32 765.18000000000018 824.03999999999985 882.90000000000043 961.38

Velocity m/s

Pressure Drop Pa

Irrigated Packing- Low flow rate (40%)

Expermintal delta Pa 971.19000000000017 1167.3900000000003 1334.16 1589.2200000000003 1805.0400000000002 Theroitical Delta P 24953.023370066734 49016.046224068334 69831.192083280897 98645.224580308641 145697.82415837058 Leva 826.14880000000005 1029.9775728695231 1156.032523423645 1294.8316646467076 1473.1345157671649

Velocity m/s

Pressure Drop Pa

Irrigated Packing- high flow rate (60%)

Expermintal delta Pa 1108.5299999999997 1393.0199999999998 1638.2699999999998 1903.1399999999999 2315.1600000000003 Theroitical Delta P 21139.138197940934 41565.510284641503 65495.846664083278 85866.223184380608 130824.89427363624 Leva 784.30049732537975 976.27815522913727 1132.1028832161344 1237.1251908933236 1421.4802891647198

Velocity m/s

Pressure Drop Pa

Wet Column

Expermintal delta Pa 2.247441316287428 2.5795607297579863 2.8925903323832713 3.1714449808656635 3.44047831698238 725.93999999999994 833.85 912.32999999999981 1010.4299999999997 1088.9100000000001 Theroitical Delta P(Leva) 2.247441316287428 2.5795607297579863 2.8925903323832713 3.1714449808656635 3.44047831698238 811.33565846222609 1068.8465413654544 1343.9951559743836 1615.6162242421726 1901.3474778745215

Velocity m/s

Pressure Drop Pa

10

Tubrulent

Laminar

+

=

D

-

H

P

2

2

t

g

U

C

P

r

=

D

2

2

3

10

t

g

U

C

U

C

P

t

r

=

D

r

P

g

D

D

CA

Q

S

D

÷

÷

ø

ö

ç

ç

è

æ

-

=

2

1

4

0

0

T-1

Bolwer

V-1

P-1

P-2

T-2

Packed Column

T-5

Water supply

F-1

P-3

T-4

Drain Water

T-3

Drin Air

Exhaust

Air

P-12

3

2

3

2

2

)

1

(

75

.

1

)

1

(

150

e

e

r

e

e

m

-

+

-

=

D

-

x

U

x

U

H

P

f