Hazard Identification & Compliance
Assessment
459 Little Collins Street, Melbourne
August 2013 (Revised February 2014)
Auditor - Savills (VIC) Pty Ltd
Building Representative – Bruce Hosking
Number of Pages - 43
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 2 of 43
Disclaimer
This report was prepared for Savills for the purpose set out herein. Responsibility is
disclaimed for any loss or damage (including but not limited to damage resulting from
the use by Uniting Church (NSW) Trust Association Ltd of this report) suffered by any
other person for any reason whatsoever including but not limited to negligence on the
part of Savills (VIC) Pty Limited. This report is confidential to Uniting Church (NSW) Trust
Association Ltd and Savills (VIC) Pty Limited does not intend that any other person
accept or rely upon it.
This report is based on our inspections and the information provided. Whilst this report is
accurate to the best of our knowledge and belief, Savills (VIC) Pty Limited cannot
guarantee the completeness or accuracy of any descriptions or conclusions based on
the supplied information.
The recommendations contained in this report are advisory only. No representation or
opinion is given to the effect that all applicable statutory rules and regulations and
directions have been given or will be complied with or that there are no other hazards
in existence.
Audited By: M. Puglielli Date: 20th August 2013 (Revised Feb 2014)
Position: Divisional Director
Before printing, think about the environment
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 3 of 43
Executive Summary
Savills Facilities Management was engaged to perform a hazard identification and
compliance assessment (HICA) of 459 Little Collins Street, Melbourne. The key
objectives of this project were to identify the outstanding occupational health, safety,
environmental (OHS&E) and associated business risks to Uniting Church (NSW) Trust
Association Ltd and (where applicable) develop practical and cost-effective measures to mitigate these risks.
The project involved a comprehensive inspection of the premises, along with a review
of relevant documentation and discussions with key on-site and contractor personnel.
A detailed checklist was utilised during the site visit, with this checklist incorporating a list
of current legislation, standards and codes of practice for a range of OHS&E hazards,
such as:
• Legionella
• Asbestos / Hazardous Materials
• Dangerous Goods / Hazardous Substances
• Hazardous Waste
• Disability Access
• Radio Frequency Radiation
• Fire
• Confined Spaces
• Plant Equipment
• Working at Height
• Emergency Management
• Workplace Environment
• Traffic Hazards
• Environmental Hazards
• Electrical Hazards
In addition, hazards affecting public liability (e.g. slips, trips and falls) and contractor
management were assessed against best-practice measures.
A total of 29 control measures have been recommended as part of the HICA project,
with prompt action duly required to address risks associated with falls from height and
hazardous chemicals in particular.
If required, Savills FM can coordinate the rectification measures nominated in this report
to further assist Uniting Church (NSW) Trust Association Ltd effectively discharge its legal
and moral obligations in the management of 459 Little Collins Street, Melbourne.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 4 of 43
Table of Contents
SECTION PAGE NO.
Introduction 5
Methodology 5
Site Description 6
Legionella 7
Asbestos / Hazardous Materials 9
Dangerous Goods / Hazardous Substances 12
Hazardous Waste 15
Public Liability 16
Disability Access 17
Radio Frequency Radiation 19
Fire 20
Confined Spaces 23
Plant Equipment 25
Working at Height 28
Contractors 30
Emergency Management 31
Workplace Environment 32
Traffic Hazards 33
Environmental Hazards 34
Electrical Hazards 36
Photos 38
Risk Assessment 40
Appendix A – Implementation Plan for Control Measures 50
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 5 of 43
Introduction
Savills Facilities Management was engaged to perform a hazard identification and
compliance assessment (HICA) of 459 Little Collins Street, Melbourne. The key
objectives of this project were to identify the outstanding occupational health, safety,
environmental (OHS&E) and associated business risks to Uniting Church (NSW) Trust
Association Ltd and (where applicable) develop practical and cost-effective measures to mitigate these risks.
Methodology
The general scope of works included the following:
A visit to site to inspect the premises.
A review of available documentation.
Follow-up discussions with key on-site and contractor personnel, where required.
Provision of a comprehensive report, summarising the findings / observations,
along with recommended control measures.
The project included identification / evaluation of the potential health risks associated
with the system in accordance with the general principles of AS/NZS ISO 31000: 2009
Risk management - Principles and guidelines.
A detailed checklist was utilised during the site visit, with this checklist incorporating a
list of current legislation, standards, codes of practice or measures deemed ‘best
practice’ for a range of OHS&E hazards, such as:
• Legionella
• Asbestos / Hazardous Materials
• Dangerous Goods / Hazardous Substances
• Hazardous Waste
• Disability Access
• Radio Frequency Radiation
• Fire
• Confined Spaces
• Plant Equipment
• Working at Height
• Emergency Management
• Workplace Environment
• Traffic Hazards
• Environmental Hazards
• Electrical Hazards
In addition, hazards affecting public liability (e.g. slips, trips and falls) and contractor
management were assessed against best-practice measures.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 6 of 43
Site Description
459 Little Collins Street is a 16-level office tower with a basement car park that was
originally constructed in 1969 and has since undergone numerous upgrades. It is
classified as C grade building with a net lettable area of approximately 9,962 square
metres and a recent 2-Star NABERS Energy Rating. The building is supported on
reinforced concrete caissons, with plasterboard internal walls and ceilings. The
external façade of the building is rendered pre-fabricated concrete panels, with
glazed panels fitted to the front and the rear façades. The building is currently owned
by Uniting Church (NSW) Trust Association Ltd and managed by Savills (VIC) Pty Ltd.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 7 of 43
1. Legionella
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
1.1 At-risk employees are provided with information,
instruction and training regarding the associated
hazards and control processes.
Model Work Health and Safety Act 2010, Section 19 &
20
C No employees (other than the Facility
Manager) are required to access the
cooling tower area, with the FM and all
contractors required to have received
associated training as part of Savills’
policies/procedures.
1.2 The cooling towers are registered in accordance
with applicable government requirements.
C The Main A/C Cooling Tower System
(CTS 899) and the Tenant A/C Cooling
Tower System (CTS 7016) are registered
with the Department of Health until
16/06/2014.
1.3 A risk assessment/management process has been
prepared, reviewed, and/or audited in accordance
with applicable government requirements.
C The Risk Management Plans (RMPs) are
reviewed and audited on an annual
basis.
The RMPs were last reviewed by Savills
on 30/10/2012. The RMPs were last
audited by ECC on 09/07/2012 for the
period 02/06/11 to 1/06/12 inclusive and
all audit requirements were deemed to
have been met.
1.4 The cooling water systems are equipped with a
certified process designed to control microbial
growth in accordance with applicable government
requirements.
C The maintenance/testing program for
each system is conducted in
accordance with the Risk Category ‘A’
ratings.
1.5 The cooling towers are inspected in accordance
with applicable government requirements.
C The cooling tower systems are inspected
weekly and serviced fortnightly by Hydo-
Chem in accordance with the Risk
Category ‘A’ ratings.
1.6 The cooling towers are cleaned /disinfected in
accordance with applicable government
requirements.
C The cooling towers are disinfected and
cleaned by Hydro-Chem on a quarterly
basis.
1.7 Maintenance/testing records, RMP are maintained in
accordance with applicable government
requirements.
C Copies of maintenance/testing reports
are kept on-site, along with the current
registration, RMP Reviews and RMP Audit
certificates.
1.8 Heterotrophic Colony Count and Legionella analysis
is performed in accordance with applicable
government requirements.
C HCC and Legionella analysis is
conducted on a monthly basis and
results distributed electronically to all
stakeholders as soon as the results are
available.
1.9 Remedial actions in response to adverse bacterial
results are undertaken in accordance with
applicable government requirements.
N/A There have been no adverse bacterial
results recorded during the period of
review.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 8 of 43
Legionella (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
1.10 Relevant authorities have been formally advised of
adverse bacterial results in accordance with
applicable government requirements.
N/A There have been no adverse bacterial
results recorded during the period of
review requiring external notification.
1.11 Dosing / bleed-off devices are fitted to the cooling
tower systems in accordance with applicable
government requirements.
AS/NZS 3666.2 s.2.5.2
C The cooling tower systems are fitted with
monitoring/control equipment that
enables automatic bleed-off and
addition of dual biocides and corrosion
inhibitor.
1.12 Safe / ready access is provided to enable inspection,
cleaning and maintenance of the cooling towers in
accordance with applicable government
requirements.
AS/NZS 3666.2 s. 2.2.3
SC Safe/ready access to the cooling towers
CTS 899 & 7016 are provided for
inspection and maintenance activities.
Although, some improvements are
required to the safe access to cooling
tower 7016.
1.13 Drift eliminators (with a drift loss rating of <0.002% of
the circulation rate) are fitted across the entire air
stream.
AS/NZS 3666.1 s.4.15 & s4
C
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 9 of 43
2. Asbestos / Hazardous Materials
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
2.1 At-risk employees are provided with information,
instruction and training regarding the associated
hazards and control processes.
Model Work Health and Safety Act 2010, Section 19 &
20
C No employees are required to access
areas where asbestos-containing
materials are located, with all building
contractors required to have received
associated training as part of Savills’
policies/procedures.
2.2 Exposure to airborne asbestos in the workplace is
either eliminated or (practicably) minimised (e.g. via
enclosing or sealing asbestos).
Model Work Health & Safety Regs 2010 r. 7.3.2
C The vinyl tiles on the tenanted floors are
unlikely to be disturbed, due to the
protection afforded by a covering of
carpet. The asbestos in the ductwork
joint mastic has not been sealed, due to
issues of access. The nature of these
asbestos-containing materials is such
that it does not pose a high risk of
exposure, given that Savills Contractor
Induction Guidelines forms the basis for
controlling works that may potentially
disturb or damage these materials.
2.3 Asbestos at the workplace has been identified (or a
presumption of its presence made) by a competent
person.
Model Work Health & Safety Regs 2010 r. 7.3.4
C An Asbestos Register was undertaken as
part of an Asbestos Management Plan
by Noel Arnold & Associates in August
2009.
2.4 The presence and location of asbestos has been
clearly indicated, preferably via labelling.
Model Work Health & Safety Regs 2010 r. 7.3.6
PC Where practicable, the majority of
asbestos-containing materials (i.e.
encapsulated fire doors, plant room
walls) has been appropriately labelled.
There are, however, other materials
identified in the Asbestos Register are
concealed in the ceiling space
2.5 An Asbestos Register (that details the location,
source, type, friability and condition of identified
asbestos, along with activities likely to damage /
disturb the asbestos and inaccessible areas likely to
contain asbestos) has been developed.
Model Work Health & Safety Regs 2010 r. 7.3.7
Code of Practice How to Manage and Control
Asbestos in the Workplace
C An Asbestos Register was undertaken as
part of an Asbestos Management Plan
by Noel Arnold & Associates in August
2009.
2.6 An Asbestos Register has been reviewed and (if
necessary) adjusted if the risk assessment or a control
measure is reviewed; or if further asbestos is identified
at the workplace.
Model Work Health & Safety Regs 2010 r. 7.3.8
C The last Asbestos survey was carried out
on the August 2009 by Noel Arnold and
Associates. An update is due August
2014.
Ensure the Asbestos Register is updated
to reflect the recent asbestos removal.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 10 of
43
Asbestos / Hazardous Materials (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
2.7 An Asbestos Register has been maintained and
made available to building occupants, contractors
and/or health & safety reps.
Model Work Health & Safety Regs 2010 r. 7.3.9
C The Asbestos Register is kept on site in
the Facility Manager’s Office and made
available to building occupants and
contractors as required.
2.8 An Asbestos Management Plan has been developed
and maintained on site.
Model Work Health & Safety Regs 2010 r. 7.3.11
Code of Practice How to Manage and Control
Asbestos in the Workplace
C An Asbestos Management Plan was
prepared by Noel Arnold & Associates in
August 2009. Ensure the Asbestos
Management plan is reviewed to reflect
the recent asbestos removal.
2.9 An Asbestos Management Plan has been reviewed
and revised at least once every 5 years or if there is a
review of the asbestos register, risk assessment or a
control measure.
Model Work Health & Safety Regs 2010 r. 7.3.12
C The Asbestos Register and Asbestos
Management Plan is due for review by
August 2014.
2.10 A risk assessment of the asbestos at the workplace
has been undertaken by a competent person and
conducted prior to any works commencing that
might disturb asbestos.
Model Work Health & Safety Regs 2010 r. 7.3.13
Code of Practice How to Manage and Control
Asbestos in the Workplace
C
2.11 A risk assessment has been reviewed and (if
necessary) revised by a competent person if a
change is made that affects the risk of exposure to
asbestos at the workplace or the condition of
asbestos changes.
Model Work Health & Safety Regs 2010 r. 7.3.14
C
2.12 Any person who is suspected of being exposed to
asbestos fibres (following uncontrolled disturbance of
asbestos in the workplace) has been promptly
identified and provided with information about
exposure to airborne asbestos.
Model Work Health & Safety Regs 2010 r. 7.3.15
N/A
2.13 An Asbestos Register has been reviewed and (if
necessary) adjusted before demolition/refurbishment
is carried out at the workplace.
Model Work Health & Safety Regs 2010 r. 7.3.22
PC Ensure the Asbestos Register is reviewed
& updated before future demolition /
refurbishment is carried out. In addition,
Part 6 asbestos audits are conducted.
2.14 An Asbestos Register has been provided to the
person conducting demolition/refurbishment before
such works have been started.
Model Work Health & Safety Regs 2010 r. 7.3.23
C
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 11 of
43
Asbestos / Hazardous Materials (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
2.15 Asbestos likely to be disturbed by
demolition/refurbishment has been identified and
(practicably) removed before such works have been
started.
Model Work Health & Safety Regs 2010 r. 7.3.26
C
2.16 Details regarding asbestos removal work are
communicated to affected building occupants and
those within the immediate vicinity of the workplace.
Model Work Health & Safety Regs 2010 r. 7.3.42
N/A Removal of asbestos containing vinyl
floor tiles was carried out in the lift motor
room under controlled conditions by
LRM Global. Removal of asbestos
containing vinyl floor tiles was carried
out under controlled conditions on
builders controlled floor level 9 on
09/05/2012.
2.17 Access to an asbestos removal area has been
restricted to only authorised personnel.
Model Work Health & Safety Regs 2010 r. 7.3.44
C
2.18 An independent licensed assessor has undertaken air
monitoring of asbestos removal areas that require a
Class A asbestos removal licence.
Model Work Health & Safety Regs 2010 r. 7.3.48
C
2.19 The results of air monitoring are provided to contract
personnel, health & safety reps and building
occupants.
Model Work Health & Safety Regs 2010 r. 7.3.48
Code of Practice How to Safely Remove Asbestos
C Air monitoring results are provided to
affected contractor personnel. Air
monitoring results should also be relayed
to the building tenants.
2.20 A Hazardous Materials Survey (including lead,
synthetic mineral fibres, polychlorinated by-phenyls)
has been conducted and is available on site.
C A Hazardous Materials Survey was
conducted by Noel Arnold & Associates
in August 2009 and is located in the
Facility Manager’s Office. A review is
due August 2014.
2.21 The local authority has been suitably-notified where
premises contain more than 10kg of PCBs.
The Polychlorinated Biphenyls Management Plan,
Australian & New Zealand Environment and
Conservation Council (ANZECC).
N/A
2.22 Where appropriate, a PCB Management Plan is
available for the site.
The Polychlorinated Biphenyls Management Plan,
Australian & New Zealand Environment and
Conservation Council (ANZECC).
SC Given the relatively minor quantities
remaining, a PCB Management Plan has
not been prepared. PCBS have been
removed from basement car park areas,
with a clearance report provided
accordingly. Remaining PCBs in plant
room areas are scheduled for removal
by 2014.
2.23 Measures are in place to control ozone depleting
refrigerant gases, including provision of data to
management regarding any associated losses.
C NAMS conducts regular checks to
determine refrigerant leaks as part of its
maintenance agreement.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 12 of 43
3. Hazardous Chemicals
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
3.1 At-risk employees are provided with appropriate
information, instruction and training regarding the
hazards; risk identification/assessment; risk control
processes; emergency plans; and use of relevant
PPE.
Model Work Health & Safety Regs 2010 r. 7.1.56
C No employees are required to handle
dangerous goods or hazardous
substances, with all contractors
required to have received associated
training as part of Savills’
policies/procedures.
3.2 Hazardous chemicals are correctly labelled in
accordance with Schedule 9 of the Model Work
Health & Safety Regs.
Model Work Health & Safety Regs 2010 r. 7.1.6 & 7.1.7
C
3.3 Current versions of Material Safety Data Sheets are
readily available on site.
Model Work Health & Safety Regs 2010 r. 7.1.21
C All current MSDS were available for the
chemicals located in the Basement
Cleaners’ Room. All current MSDS for
the water treatment chemicals are
current and available on site.
3.4 A hazardous chemicals register (which includes the
current MSDS) has been maintained and is readily
available on site.
Model Work Health & Safety Regs 2010 r. 7.1.23
C A Dangerous Goods/Hazardous
Substances Register was developed
on 30 July 2012 by LRM Global
3.5 A suitably compliant manifest has been prepared,
maintained and suitably located where quantities of
dangerous goods exceed the nominated amount in
Schedule11, table 11.1 of the Model Work Health &
Safety Regs.
Model Work Health & Safety Regs 2010 r. 7.1.26
N/A Quantities of dangerous goods stored
on site are below the thresholds listed
in Schedule 11 of the Regulations.
3.6 The local regulator has been notified in writing if
manifest quantities of hazardous chemicals are
exceeded.
Model Work Health & Safety Regs 2010 r. 7.1.27
N/A
3.7 A suitably compliant outer warning placard is
displayed at the workplace where quantities of
dangerous goods exceed the nominated amount in
Schedule11, table 11.1 of the Model Work Health &
Safety Regs.
Model Work Health & Safety Regs 2010 r. 7.1.29
N/A
3.8 A suitably compliant dangerous goods placard is
displayed at the workplace where quantities of
dangerous goods exceed the nominated amount in
Schedule11, table 11.1 of the Model Work Health &
Safety Regs.
Model Work Health & Safety Regs 2010 r. 7.1.30
N/A
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 13 of 43
Hazardous Chemicals (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
3.9 Hazards associated with using, handling or storing
hazardous chemicals at the workplace have been
identified.
Model Work Health & Safety Regs 2010 r. 7.1.31
NC There does not appear to be any risk
assessments completed for dangerous
goods or hazardous substances that
are kept on site.
Ensure a site-specific risk assessment
that focuses on the use, handling or
storing of hazardous chemicals is
prepared prior to commencement of
works.
3.10 Exposure to hazardous chemicals is controlled via a
hierarchy of controls, preferentially via elimination,
substitution, reduction, isolation, engineering controls,
administrative controls then PPE.
Model Work Health & Safety Regs 2010 r. 7.1.32
C
3.11 Risk assessments have been reviewed at least once
every 5 years or more regularly if required.
Model Work Health & Safety Regs 2010 r. 7.1.33
N/A Once completed, the risk assessment
will need to be reviewed at least once
every 5 years.
3.12 Hazardous chemicals are appropriately isolated from
incompatible substances/materials (e.g. via
separation or segregation).
Model Work Health & Safety Regs 2010 r. 7.1.35
C Only minor quantities of Class 6 and
Class 8 chemicals are stored on-site
(mostly within the cooling tower areas
and the Cleaners Room).
3.13 Flammable or combustible substances are kept at
the lowest practicable quantity for the workplace.
Model Work Health & Safety Regs 2010 r. 7.1.37
C
3.14 Ignition sources in a hazardous area at the
workplace are either eliminated or practicably
minimised.
Model Work Health & Safety Regs 2010 r. 7.1.38
C
3.15 Measures are in place (including available
equipment/materials) to promptly contain, clean-up
and dispose of spillages of hazardous chemicals.
Model Work Health & Safety Regs 2010 r. 7.1.39
NC There is no bunding in the Basement
Cleaners’ Room (refer Photo 3.15a) to
assist in containing chemical spillages.
Ensure all chemicals are positioned
within suitable containment bunds. The
cooling tower chemical are well
bunded.
3.16 Containers of hazardous chemicals and any
associated pipe work/attachments are protected
against damage.
Model Work Health & Safety Regs 2010 r. 7.1.40
C
3.17 Fire protection equipment that is designed and built
for the types of hazardous chemicals at the
workplace is maintained on site at all times.
Model Work Health & Safety Regs 2010 r. 7.1.41
C An appropriate fire extinguisher is
located in close proximity of the
Basement Cleaners Room.
3.18 A copy of an appropriate emergency plan must be
provided to the emergency services authority if
manifest quantities of hazardous chemicals are
exceeded.
Model Work Health & Safety Regs 2010 r. 7.1.43
N/A
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 14 of 43
Hazardous Chemicals (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
3.19 Relevant safety equipment associated with the use,
handling or storage of hazardous chemicals is
maintained and readily accessible.
Model Work Health & Safety Regs 2010 r. 7.1.44
NC There are no eyewash facilities
provided in the Basement Cleaners’
Room or either of the cooling tower
areas and this should be duly rectified.
3.20 Bulk hazardous chemical containers and any
associated pipe work/attachments are securely
mounted and suitably protected against damage.
Model Work Health & Safety Regs 2010 r. 7.1.49
C
3.21 Containers of hazardous chemicals no longer in use
have been completely cleaned or disposed of or
correctly labelled.
Model Work Health & Safety Regs 2010 r. 7.1.50
C The underground fuel storage tank
located in the Ground Floor Loading
Dock has been de-commissioned by
Gen Care and a de-commissioning
certificate provided accordingly.
3.22 The local regulator has been notified where an
underground storage tank (that previously held
dangerous goods of class 2.1 or class 3, or C1
combustible liquids) has been abandoned.
Model Work Health & Safety Regs 2010 r. 7.1.52
N/A
3.23 Suitable and well-maintained PPE is provided to at-
risk employees.
Model Work Health & Safety Regs 2010 r.3.2.1 & 3.2.2
NC The cleaners have not provided their
cleaning staff with appropriate PPE and
(along with associated training) should
be duly provided.
3.24 Measures are in place to ensure the risk to
people/property at or beyond the site boundaries
are controlled by isolation.
Dangerous Goods (Storage & Handling) Regulations
2007 r. 415
N/A
3.25 Adequate ventilation is provided to maintain a safe
working atmosphere in the storage and handling
area.
Dangerous Goods (Storage & Handling) Regulations
2007 r. 425
C
3.26 Gas cylinders are secured in an upright position in
well-ventilated storage areas.
AS/NZS 1596: 2008, s. 2.3.
AS4332: 2004, s. 2.5
N/A There are no gas cylinders currently
stored on site.
3.27 Oxygen cylinders are stored at least 3 metres from
fuel gas cylinders.
AS/NZS 1596: 2008, s. 2.3.
AS4332: 2004, s. 2.5
N/A There are no gas cylinders currently
stored on site.
3.28 Full and empty gas cylinders are stored separately.
AS/NZS 1596: 2008, s. 4
AS4332: 2004, s. 8
N/A There are no gas cylinders currently
stored on site.
3.29 Signs such as “Danger: No Smoking, No Ignition
Sources” and “Restricted Area, Authorised Personnel
Only” are displayed in cylinder storage areas.
AS/NZS 1596: 2008, s. 12.
AS4332: 2004, s. 6.4
N/A There are no gas cylinders currently
stored on site.
3.30 Appropriate flashback arrestors are fitted to fuel gas
cylinders, fitted at the regulator outlet with a non-
return valve and a temperature actuated cut-off
valve.
AS/NZS 1596: 2008, s. 4.2
N/A There are no gas cylinders currently
stored on site.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 15 of 43
4. Hazardous Waste Management
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
4.1 At-risk employees are provided with information,
instruction and training regarding the associated
hazards and control processes.
Model Work Health and Safety Act 2010, Section 19 &
20
C No hazardous wastes are stored,
produced or disposed of from this
site.
4.2 Hazardous waste is appropriately stored on site in
accordance with local authority requirements.
N/A
4.3 Hazardous waste is appropriately removed and
disposed of in accordance with local authority
requirements.
N/A
4.4 Appropriate transport waste certificates are held on
site in accordance with local authority requirements.
N/A
4.5 Trade Waste Agreements (TWAs) are in place for
discharges to sewers other than domestic sewage
(kitchen/toilets) and all associated conditions
imposed by the local authority have been duly met.
C A TWA is in place for the 2000L Grease
interceptor (GRI-01) and expires
08/05/2012. A TWA has also been
obtained for the Cooling Towers on
site (Ref 34100109011)and expires 8th
of May 2021.
4.6 Waste management records are maintained for
liquid and solid hazardous wastes on site in
accordance with local authority requirements.
N/A
4.7 Prescribed waste requirements have been
determined for the facility in accordance with local
authority requirements.
N/A
4.8 Contractors engaged to dispose of prescribed waste
are suitably-licensed waste removal contractors.
N/A
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 16 of 43
5. Public Liability
Risk Element
L = Low Risk Level, M = Medium Risk Level, H = High Risk Level, N/A = Not Applicable
Ref Finding/Observation Risk
Level
Accept
-able Comments
5.1 Floor areas within the common areas of the
complex are free from protrusions.
Model Work Health & Safety Regs 2010 r. 3.1.1
L Yes
5.2 Areas that are wet and slippery are signposted.
Model Work Health & Safety Regs 2010 r. 3.1.1
L Yes Cleaners and/or the Facility Manager
control wet / slippery areas with
warning signs suitably displayed during
cleaning and inclement weather.
5.3
Entrances to the building are safe, clear, slip
resistant and free of trip hazards.
Model Work Health & Safety Regs 2010 r. 3.1.1
L No Slip testing of the external entry and
ground floor foyer areas was
conducted by Slip Smart during
December 2013, with the foyer
exhibiting a very high risk of slipping
during the wet test. Measures are in
place to address the risk posed by
rainwater entry and spills.
5.4 Entrances to tenancies are clear and free of trip
hazards.
Model Work Health & Safety Regs 2010 r. 3.1.1
L Yes
5.5 There are inclement weather mats at the
entrances to the building.
Model Work Health & Safety Regs 2010 r. 3.1.1
M Yes
5.6 Areas are free from cables/cords, or if
cables/cords are used they are appropriately
covered to prevent trips.
Model Work Health & Safety Regs 2010 r. 3.1.1
L Yes
5.7 Housekeeping is adequate in public areas and
is uncluttered and free of rubbish.
Model Work Health & Safety Regs 2010 r. 3.1.1
L Yes
5.8 Paved areas are in good condition.
Model Work Health & Safety Regs 2010 r. 3.1.1
L Yes
5.9 Handrails are installed at stairs/steps.
Model Work Health & Safety Regs 2010 r. 3.1.1
M Yes
5.10 Expansion joints are in good condition and
sealed flush to the surface.
Model Work Health & Safety Regs 2010 r. 3.1.1
L Yes
5.11 Trip hazards associated with steps and stairs
(including treads) are controlled.
Model Work Health & Safety Regs 2010 r. 3.1.1
H Yes
5.12 Entrances are protected from storm water
incursion (rain does not enter the building).
Model Work Health & Safety Regs 2010 r. 3.1.1
M Yes
5.13 Processes are in place to isolate and clean-up
spills.
Model Work Health & Safety Regs 2010 r. 3.1.1
M Yes Cleaners are on site to manage any spills throughout the day.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 17 of 43
Public Liability (continued)
Risk Element
L = Low Risk Level, M = Medium Risk Level, H = High Risk Level, N/A = Not Applicable
Ref Finding/Observation Risk
Level
Accept
-able Comments
5.14 Regular inspections are undertaken of common
areas by centre management/property
manager.
Model Work Health & Safety Regs 2010 r. 3.1.1
H Yes The Facility Manager conducts
monthly inspections of the premises
and these are formally documented
and filed electronically.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 18 of 43
6. Disabled Access
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
6.1 There has been an extension to, or modification of,
any part of the building that necessitated submission
of a building permit application to the local authority
on/after 1 May 2011.
N/A There have been no triggers of the
provisions of the Commonwealth
Disabled (Access to Buildings-Premises)
Standards 2010 during the past 12
months.
6.2 A building certifier or building developer has formally
verified that the deemed-to-satisfy provisions of the
2010 Access Code for Buildings (i.e. clauses D3.1 to
D3.12; E3.6; F2.2; and F2.4) have been met for the
‘affected part1’ of the building.
Commonwealth Disabled (Access to Buildings-
Premises) Standards 2010, Clause 3.2 (1a)
N/A
6.3 Access has been provided to enable people to:
(a)(i) approach the building from the road boundary
and from any accessible car-parking spaces
associated with the building; and
(ii) approach the building from any accessible
associated building; and
(iii) access work and public spaces, accommodation
and facilities for personal hygiene; and
(b) identify accessways at appropriate locations
which are easy to find.
Commonwealth Disabled (Access to Buildings-
Premises) Standards 2010, Clause DP1
N/A
6.4 Exits have been provided from the building to allow
occupants to evacuate safely, with their number,
location and dimensions being appropriate to:
(a) the travel distance; and
(b) the number, mobility and other characteristics of
occupants; and
(c) the function or use of the building; and
(d) the height of the building; and
(e) whether the exit is from above or below ground
level.
Commonwealth Disabled (Access to Buildings-
Premises) Standards 2010, Clause DP4
N/A
6.5 Accessways to exits have dimensions appropriate to:
(a) the number, mobility and other characteristics of
occupants; and
(b) the function or use of the building.
Commonwealth Disabled (Access to Buildings-
Premises) Standards 2010, Clause DP6
N/A
1 An ‘affected part’ is: (a) the principal pedestrian entrance of an existing building that contains a new
part; and (b) any part of an existing building, that contains a new part, that is necessary to provide a
continuous accessible path of travel from the entrance to the new part.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 19 of 43
Disability Access (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
6.6 Car-parking spaces for use by people with a disability
have been:
(a) provided, to the degree necessary, to give
equitable access for car-parking; and
(b) designated and easy to find.
Commonwealth Disabled (Access to Buildings-
Premises) Standards 2010, Clause DP82
N/A
6.7 An inbuilt communication system for entry,
information, entertainment, or for the provision of a
service, is provided that is suitable for occupants who
are deaf or hearing impaired.
Commonwealth Disabled (Access to Buildings-
Premises) Standards 2010, Clause DP93
N/A
6.8 Passenger lifts required to be accessible are suitable
for use by people with a disability.
Commonwealth Disabled (Access to Buildings-
Premises) Standards 2010, Clause EP3.4
N/A
6.9 Suitable sanitary facilities for personal hygiene are
provided in a convenient location (within or
associated with the building) to the degree
necessary, appropriate to:
(a) the function or use of the building; and
(b) the number and gender of the occupants; and
(c) the disability or other particular needs of the
occupants.
Commonwealth Disabled (Access to Buildings-
Premises) Standards 2010, Clause FP2.1
N/A
2 Clause DP8 does not apply to a building where: (a) a parking service is provided; and (b) direct access to any car-parking spaces by the general public or occupants is not available.
3 Clause DP9 does not apply to an inbuilt communication system used only for emergency warning purposes.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 20 of 43
7. Radio Frequency Radiation
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
7.1 At-risk employees are provided with information,
instruction and training regarding the associated
hazards and control processes.
Model Work Health and Safety Act 2010, Section 19 &
20
N/A There are no radio frequency
radiation devices on site.
7.2 Risk assessments have been undertaken for
plant/equipment capable of emitting harmful
radiation, and a register kept.
Arpansa Radiation Protection Standard Part 5.1.2a
N/A
7.3 Radio frequency radiation (RFR) exposure levels
associated with transmitter towers or receivers have
been determined where appropriate.
Arpansa Radiation Protection Standard Part 5.1.2b
N/A
7.4 A site plan that shows RFR hazard zones exists where
exposure standards are exceeded.
Arpansa Radiation Protection Standard Part 5.1.2b
N/A
7.5 Radiation Safety Manual has been developed.
Arpansa Radiation Protection Standard Part 5.1.1
N/A
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 21 of 43
8. Fire Safety
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
8.1 Annual fire safety measures report/certificate is
current and displayed appropriately.
BCA 2005
C All aspects relating to fire safety and
compliance have been assessed
within the Contractor’s Performance
Assessment Report and the Egress
Analysis Report (refer to separate
reports prepared by Savills in July
2013).
Any specific non-conformance(s)
observed during the site inspection
are duly recorded in the above
mentioned reports.
8.2 There is a programmed preventative maintenance
schedule for the maintenance of each fire safety
measure in the building.
BCA 2005
C
8.3 Maintenance records/logbooks for essential services
are kept on site and are readily available if required.
BCA 2005
C
8.4 Occupancy certificates/permits are available and
kept on site.
BCA 2005
8.5 Penetrations in boundary walls are adequately fire
stopped (e.g. plant rooms).
BCA 2005 C3
C
8.6 Fire doors are suitably tagged.
BCA 2005 C3.4
C
8.7 Fire doors self closing.
BCA 2005 C3.4
C
8.8 Appropriate fire doors have signage that indicates
‘Fire Door, Do Not Obstruct, Do Not Keep Open’
BCA 2005 C3.4
C
8.9 Fire isolated exits (corridors) are devoid of
combustible materials and free of obstructions.
BCA 2005 C & D
C
8.10 Fire isolated exits contain Fire Safety Notices (NSW
only)
EP&A Regs NSW 2000
N/A
8.11 Paths of travel to exits are free of obstructions (i.e.
exit path width of 1000mm is maintained at all times
(within tenancies)
BCA 2005 Part B1.10
C
8.12 Exit doors are free to open into a clear space and
are not obstructed externally.
BCA 2005 Part D2.20 (b)
C
8.13 Fire extinguishers are mounted and location signage
is clearly visible and identifiable.
AS2444
C
8.14 Access to fire extinguishers is within 15 metres. (Within
each tenancy)
AS2444
C
8.15 Access to fire extinguishers is clear of obstructions.
AS2444
C
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 22 of 43
Fire Safety (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
8.16 The yellow maintenance record tags are securely
tied to the fire extinguisher.
AS2444
C
8.17 The fire hose reel location signage is clearly visible
(e.g. where mounted in a cabinet, the door of the
cabinet shall display the words ‘Fire Hose Reel’
AS2441
C
8.18 The fire hose reels are properly wound and in the
interlock positions.
AS2441
C
8.19 Access to the fire hose reels is not restricted
/obstructed.
AS2441
C
8.20 The yellow maintenance record tags are securely
tied to the fire hose reels.
AS2441
C
8.21 Where fire hydrants are mounted in a cabinet, the
door of the cabinet shall display the word ‘Fire
Hydrant’.
AS2419.1
C Fire Hydrant cupboard located in the
basement car park have
appropriate sign displayed.
8.22 Access to the hydrants is not restricted / obstructed.
AS2419.1
C
8.23 The yellow maintenance record tags are securely
tied to the fire hydrants.
AS2419.1
C
8.24 Adequate clearance is maintained below the
sprinkler heads, i.e. a clear space of 500mm is
provided around the sprinkler heads (e.g. storage of
goods is not too close to the sprinkler heads).
AS2118.1
C
8.25 Sprinkler block plan is displayed in the sprinkler valve
room or fire control room.
AS2118.1
C
8.26 Representative smoke/heat detectors observed
appear to be free of damage and securely fixed to
their mountings.
C
8.27 Fire indicator panel is free of damage and securely
fixed.
C
8.28 Emergency lighting is securely mounted and free
from damage (shops >300m2)
BCA 2005 Part E4.2b
C
8.29 Emergency lighting is in good working order. C
8.30 Exit signs are securely mounted and free from
damage. (shops >300m2)
C
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 23 of 43
Fire Safety (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
8.31 Exit signs are generally visible and illuminated
AS2293.1
C
8.32 Exit signs are directing occupants to the correct
egress paths.
BCA 2005 Part E4.5
C
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 24 of 43
9. Confined Spaces4
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
9.1 Persons working in a confined space are provided
with information, instruction and training regarding
the associated hazards, control measures, use of PPE,
the confined space entry permit system and the
emergency procedures.
Model Work Health & Safety Regs 2010 r. 4.3.19
C All contractors are responsible for
undertaking site-specific risk
assessments and providing relevant
information, instruction and training to
their staff that are required to work in
a confined space.
9.2 Confined spaces have been identified on site.
AS2865: 2001 clause 8.1
PC The pits in the Basement Car Park and
Sprinkler Room; the Level 16 Water
Storage Tanks (refer Photo 9.2); and
some of the air handling units have
been identified as potential confined
spaces. A formal audit of all confined
spaces within the building has not
been conducted.
Undertake a Confined Spaces Audit
with the input from key contractors
(e.g. plumbing and mechanical
service providers). Once conducted,
a site plan of all identified confined
spaces should be prepared and
made available to all relevant
contractors.
9.3 Confined space entry points are clearly marked and
easily identified.
NC Suitably-label all identified confined
spaces.
9.4 All risks to health or safety associated with work in a
confined space have been identified through a risk
assessment process, which is reviewed / revised as
necessary.
Model Work Health & Safety Regs 2010 r. 4.3.7
C Risk assessments are to be
completed by the relevant
contractor before commencing any tasks within the confined spaces.
9.5 Measures designed to control the specific risks
associated with work in a confined space are in
place and reviewed/revised as necessary.
Model Work Health & Safety Regs 2010 r. 4.3.8 &
4.3.20
C Measures designed to control the
specific risks with work in a confined
space are evaluated / modified (as
necessary) by the relevant
contractor before commencing any tasks.
9.6 A confined space entry permit system (in
accordance with the requirements outlined in r. 4.3.9
of the Model Work Health & Safety Regs 2010) is in
place and is a condition of entry therein.
Model Work Health & Safety Regs 2010 r. 4.3.9
C All contractors are required to comply
with Savills’ Confined Space Entry
Permit System should entry therein be
required.
9.7 Signs prohibiting unauthorised access to confined
spaces are prominently displayed next to each entry
immediately before and during work being
performed.
Model Work Health & Safety Regs 2010 r. 4.3.10
C Included as a requirement of the
Confined Space Entry Procedure in
Savills’ OHS&E Contractor Induction
Manual.
4 A Confined Space shall encompass Restricted Access / Egress Spaces, with all measures (other than items 9.7, 9.8 & 9.9) listed herein deemed applicable.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 25 of 43
Confined Spaces (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
9.8 A continuous communication system between those
within and outside the confined space is in place
and is a condition of entry therein.
Model Work Health & Safety Regs 2010 r. 4.3.11
C Included as a requirement of the
Confined Space Entry Procedure in
Savills’ OHS&E Contractor Induction
Manual.
9.9 A lock-out and tag system is in place to reduce the
risk of any substance being introduced or any
plant/service being activated or energised in a
confined space.
Model Work Health & Safety Regs 2010 r. 4.3.12
C Included as a requirement of the
Confined Space Entry Procedure in
Savills’ OHS&E Contractor Induction
Manual.
9.10 Measures are in place to ensure a safe atmosphere
within the confined space is provided.
Model Work Health & Safety Regs 2010 r. 4.3.13 &
4.3.14
C Included as a requirement of the
Confined Space Entry Procedure in
Savills’ OHS&E Contractor Induction
Manual.
9.11 Measures are in place to ensure the concentration of
any flammable gas/vapour is kept below unsafe
levels.
Model Work Health & Safety Regs 2010 r. 4.3.15
C Included as a requirement of the
Confined Space Entry Procedure in
Savills’ OHS&E Contractor Induction
Manual.
9.12 No ignition source is introduced to the confined
space where there is a likelihood of fire or explosion.
Model Work Health & Safety Regs 2010 r. 4.3.16
C Included as a requirement of the
Confined Space Entry Procedure in
Savills’ OHS&E Contractor Induction
Manual.
9.13 Plant and equipment used to control risk associated
with the entry to and work in a confined space is
regularly maintained (i.e. gas monitor is tested and
calibrated annually).
C Included as a requirement of the
Confined Space Entry Procedure in
Savills’ OHS&E Contractor Induction
Manual.
9.14 Emergency procedures are established to enable
the safe/timely rescue and provision of first aid to a
person in or rescued from a confined space.
Model Work Health & Safety Regs 2010 r. 4.3.17 &
4.3.18
C Included as a requirement of the
Confined Space Entry Procedure in
Savills’ OHS&E Contractor Induction
Manual.
9.15 Records of relevant documentation (i.e. personnel
training, risk assessments and copies of confined
space entry permits issued) are kept on site.
Model Work Health & Safety Regs 2010 r. 4.3.21
C
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 26 of 43
10. Plant & Certification of Operators
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
10.1 At-risk employees are provided with information and
instruction in hazard identification/risk control; plant
safety procedures; and use of relevant PPE.
Model Work Health & Safety Regs 2010 r. 5.1.28
C Other than the Facility Manager, no
employees are required to access
plant equipment areas, with the
Facility Manager and all contractors
required to have received associated
training as part of Savills
policies/procedures.
10.2 All OH&S hazards associated with the systems of work
relating to plant equipment have been identified
through a risk assessment process.
PC A risk assessment has been provided
for the lifts, but not for the boilers and
air-compressor on site.
Ensure site-specific plant risk
assessments are prepared for the
boilers and air compressor.
10.3 The risks associated with plant equipment are
minimised via a hierarchy of controls, preferentially
via substitution, isolation, engineering controls,
documented administrative controls (e.g. safe work
method statements) or the use of PPE.
Model Work Health & Safety Regs 2010 r. 5.1.21
C
10.4 Measures are in place to control risks to health and
safety associated with plant or its associated systems
of work are reviewed / revised as necessary.
Model Work Health & Safety Regs 2010 r. 5.1.23
C As per Savills’ policies / procedures,
measures designed to control the
specific health and safety risks are
required to be evaluated / modified
(as necessary) by the relevant
contractor before commencing any tasks.
10.5 Measures are in place to prevent unauthorised
alterations to or interference with plant equipment.
Model Work Health & Safety Regs 2010 r. 5.1.24
C Plant equipment is only accessible to
authorised personnel.
10.6 A permit to work system is in place to avoid
inadvertent energising of plant that has been
isolated but not physically disconnected from the
electrical supply.
C Included as a requirement of the
Permits to Work Procedure in Savills’
OHS&E Contractor Induction Manual.
10.7 Plant equipment that is not in use is left in a state that
does not create a health or safety risk.
Model Work Health & Safety Regs 2010 r. 5.1.26
N/A There are no disused items of plant on
site.
10.8 Relevant records (e.g. commissioning, inspections,
maintenance, alterations, decommissioning and
dismantling) for registrable items of plant are kept on
site that cover the lifetime of the plant as a minimum.
Model Work Health & Safety Regs 2010 r. 5.1.27
C All associated records relating to
registrable items of plant are kept in
the Facility Manager’s Office.
10.9 Suitable guarding or a physical barrier is in place to
protect against hazards (e.g. moving parts, contact
with extreme temperatures, electrocution), whilst still
allowing maintenance on the associated plant
equipment to be safely/readily performed where
necessary.
Model Work Health & Safety Regs 2010 r. 5.1.29 &
5.1.30
C
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 27 of 43
Plant & Certification of Operators (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
10.10 Operator-protective devices are provided,
maintained and used to reduce the risks of powered
mobile plant overturning, objects falling on the
operator or the operator being ejected from the
plant.
Model Work Health & Safety Regs 2010 r. 5.1.34 &
5.1.35
N/A There is no powered mobile plant on site.
10.11 Warning devices are provided, maintained and used
to reduce the risks of powered mobile colliding with
pedestrians.
Model Work Health & Safety Regs 2010 r. 5.1.35
N/A
10.12 Measures are in place to suitably control the risk of
powered mobile plant colliding with pedestrians or
other powered mobile plant.
N/A
10.13 Suitable working platforms or equivalent
arrangements are provided to protect maintenance
personnel from the risk of a fall from height or being
struck by falling objects.
Model Work Health & Safety Regs 2010 r. 5.1.41
PC There is a potential fall hazard
associated the air-handling units in the
Level 16 Plant Room and these
collective hazards should be duly
rectified.
10.14 Suitable access barriers are provided to minimise the
risk of an unauthorised person falling down a lift well.
Model Work Health & Safety Regs 2010 r. 5.1.41
C Undertaken by Thyssen Krupp as part
of a scheduled maintenance
program.
10.15 A safe means of entry to/exit from the base of the lift
well is provided.
Model Work Health & Safety Regs 2010 r. 5.1.41
C
10.16 The safe working load specified in the design of the
lift is prominently displayed in the lift.
Model Work Health & Safety Regs 2010 r. 5.1.41
AS 1735.2: 2001 s. 23.22
C
10.17 Each lift car shall be provided with a communication
facility and an audible alarm.
AS 1735.2: 2001 s. 32.4
C
10.18 Where buildings have more than one lift, every lift
shall be consecutively and clearly numbered.
AS 1735.2: 2001 s. 32.5
C
10.19 Periodic inspection/maintenance of lifts is carried out
to the manufacturer’s recommendations, but in no
case at intervals of more than one year.
AS 1735.2: 2001 Appendix E
C Undertaken by Thyssen Krupp, with
inspections performed fortnightly and
services conducted monthly.
10.20 Pressure equipment is installed, tested,
commissioned, operated and maintained so as to
eliminate risks to health and safety arising from its use.
Model Work Health & Safety Regs 2010 r. 5.1.43
C
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 28 of 43
Plant & Certification of Operators (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
10.21 Pressure equipment has been designed for ease of
maintenance/inspection and fitted with suitable
safety protection devices (e.g. pressure-relief valves).
AS 1200 Appendix J3
C
10.22 Air receivers are inspected externally/internally every
2/4 years respectively.
TBC Please confirm
10.23 Pressure relief valves are examined and tested every
4 years.
TBC Please confirm
10.24 Items of plant requiring registration have been
registered, including boilers (Hazard Level A, B or C),
pressure vessels (Hazard Level A, B or C), lifts and
building maintenance units.
Model Work Health & Safety Regs 2010 r. 5.2.7
C The cooling towers, lifts and air
receiver are registered with WorkSafe
Victoria.
10.25 Registration is evident on or near the plant.
NOHSC:1010(1994) clause 72(ii) National Standard for
Plant
C Registration certificates are displayed
in the lift motor room and on the air
compressor.
10.26 A formal notice has been suitably provided each
year to the local regulator stating that registrable
items of plant have been maintained in a safe
condition and are safe to operate.
Model Work Health & Safety Regs 2010 r. 5.2.37
N/A
10.27 Plant is inspected and maintained according to the
recommendations of the designer and manufacturer
to ensure safe/effective operation.
C A programmed maintenance plan is
in place for plant equipment on site,
with NAMS servicing the air receiver,
boilers, chillers, cooling towers, fans
and pumps; and Thyssen Krupp
servicing the lifts.
10.28 A process is in place to ensure that operators of plant
have appropriate licences and/or certificates of
competence.
NOHSC:1010(1994) clause 31(a) National Standard
for Plant
C Included as a requirement of Savills’
OHS&E Contractor Induction Manual.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 29 of 43
11. Working at Height
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
11.1 At-risk employees are provided with information,
instruction and training regarding the associated
hazards and control processes.
Model Work Health and Safety Act 2010, Section 19 &
20
C No employees (other than the Facility
Manager) are required to access the
roof, with the Facility Manager and all
relevant contractors required to have
received associated training as part of
Savills policies/procedures.
11.2 All fall hazards at the site have been identified.
Model Work Health & Safety Regs 2010 r. 4.4.2
PC There is no evidence of a formal
Working at Height Survey having been
completed. In addition to window-
cleaning activities, other potential fall
hazards include unprotected areas
associated with the air-handling units
in the Level 16 Plant Room (refer Photo
11.2b). Measures to address these
potential fall hazards should be
promptly instigated.
In the interim, access to these areas
should be tightly controlled and the
Working on Roofs Permit (refer
Annexure L in Savills’ OH&S Contractor
Induction Guidelines) utilised for
contractors requiring access to roof
areas.
11.3 Risk assessments have been completed and are
maintained on site for each task involved in working
at heights.
NC There is no evidence of risk
assessments having been completed
for tasks involved in working at heights
on site.
Ensure risk assessments are prepared
for each task involved in working at
heights.
11.4 The risk of a fall is controlled via a hierarchy of
controls, preferentially via a passive fall-prevention
device, work-positioning system, a fall-arrest system,
a ladder or a documented administrative control
(e.g. safe work method statement).
Model Work Health & Safety Regs 2010 r. 4.4.3
C A fixed ladder is provided for access
to the rooftop, with all serviceable
items of plant positioned well-within
the edge of the roof (which is
protected by a 1-metre parapet wall).
Column-fixing points (that are subject
to annual re-certification) are
provided for window-cleaning
activities.
11.5 Measures to control the risk of a fall or falling object
are suitable, set up correctly and maintained in
sound working order.
Model Work Health & Safety Regs 2010 r. 4.4.5 & 4.4.8
C
11.6 Emergency procedures are established to enable
the safe/timely rescue to a person who requires
emergency assistance associated with a fall.
Model Work Health & Safety Regs 2010 r. 4.4.6
C The Facility Manager is to ensure the
safe / timely rescue and provision of
first aid to a person who has fallen is
provided on all applicable JSAs.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 30 of 43
Working at Height (continued)
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
11.7 Measures to control the risk of a fall or falling object
are reviewed / revised as necessary.
Model Work Health & Safety Regs 2010 r. 4.4.7 & 4.4.8
C
11.8 Where a ladder is used, it must be fit for the purpose
and set up in a correct manner.
AS 1657:1992 s. 5
C
11.9 Where access is required through a horizontal
opening, handrails / handgrips above the level of the
opening are provided and guard-railing fitted to
protect against exposed edges of access openings /
landings.
AS 1657:1992 s. 5
N/A There is no access required through a
horizontal opening.
11.10 An appropriate ladder cage or a suitable protective
device is fitted where a person could fall from a
ladder more than 6.0 m.
AS 1657:1992 s. 5
C
11.11 Anchor points and static lines (where fitted) are
regularly tested (i.e. minimum 12-monthly).
N/A Anchor points or static lines have not
been fitted.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 31 of 43
12. Contractor Management
Risk Element
L = Low Risk Level, M = Medium Risk Level, H = High Risk Level, N/A = Not Applicable
Ref Finding/Observation Risk
Level
Accept
-able Comments
12.1 OH&S requirements are included in tender and
contractor documents.
Model Work Health and Safety Act 2010, Section
19 & 20
M Yes
OH&S requirements are included in
contractor documents issued by
Savills.
12.2 Contractors provide written job safety analysis,
risk assessments or safe work procedures for
proposed works prior to commencing work.
Model Work Health and Safety Act 2010, Section
19 & 20
H Yes
Copies of JSAs or risk assessments are
obtained prior to commencement of
any works.
12.3 Contractors receive site-specific induction
training.
Model Work Health and Safety Act 2010, Section
19 & 20
H Yes
The ‘Rapid Induct’ system is utilised by
all base-building contractors, with site-
specific induction training for all
contractors provided by the Facility
Manager.
12.4 Contractors are given a site contact person and
that person meets with the contractor prior to
starting work to review safe work practices.
Model Work Health and Safety Act 2010, Section
19 & 20
H Yes
The Facility Manager is the primary
contact person on site and is
responsible for the coordination of all
works performed; part of this is to
ensure safe work practices are
complied with.
12.5 Contractor OH&S performance is monitored
and unsatisfactory performance is followed up.
Model Work Health and Safety Act 2010, Section
19 & 20
H Yes
Contractor OH&S performance is
managed by the Facility Manager.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 32 of 43
13. Emergency Management
Compliance Element
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
13.1 A documented Emergency Management Plan (EMP)
is provided and is reviewed at least once every 5
years.
AS3745 s. 3
Model Work Health & Safety Regs 2010 r. 3.4.1
C Emergency Management Procedures
were prepared by La Nouvelle
Musique (formally ADF Training) in July
2009 and up-dated in June 2013.
Stage 2 training was conducted
during November 2013.
13.2 Appropriate diagrams that provide emergency and
evacuation information are displayed throughout the
facility.
AS3745 s. 3.5
Model Work Health & Safety Regs 2010 r. 3.4.3
PC Emergency evacuation signs
prepared by La Nouvelle Musique are
displayed throughout the tenanted
areas of the building, but not the car
park and plant room areas and this
should be duly rectified.
13.3 The EMP is accessible to all building occupants, with
sufficient information from the emergency response
procedures specifically distributed to all occupants.
AS3745 s. 3.6
Model Work Health & Safety Regs 2010 r. 3.4.3
C The EMP is made available to all
tenants.
13.4 An up-to-date register of all Emergency Control
Organisation members is kept readily available and
occupants are made aware of the identity of their
wardens.
AS3745 s. 5
Model Work Health & Safety Regs 2010 r. 3.4.1
C A list of the names/roles of emergency
responders are provided to all building
occupants (e.g. via distribution of
minutes of training meetings to each
tenancy).
13.5 Tenants, contractors and employees receive
information and training in emergency procedures
appropriate to the allocated emergency response
responsibilities
AS3745 s. 6
Model Work Health & Safety Regs 2010 r. 3.4.3
C Training is conducted on a six-monthly
basis by La Nouvelle Musique.
13.6 A program is in place for annual testing /
implementation of the emergency response
exercises, including full-scale building evacuations.
AS3745 s. 7.3
Model Work Health & Safety Regs 2010 r. 3.4.2
C Full-scale building evacuation
exercises are conducted on a yearly
basis La Nouvelle Musique, with the
latest building evacuation conducted
in November 2013.
13.7 Competent persons have assessed the suitability,
location and accessibility of emergency equipment.
C
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 33 of 43
14. Workplace Environment
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
14.1 Noise level measurements have been taken in those
areas identified as likely to be in excess of the noise
exposure standard.
NC Undertake noise level measurements
in noisy areas such as the Chiller Plant
Room, Fire Hydrant Pump Room and
the Fire Sprinkler Pump Room.
14.2 Exposure to workplace noise (above the noise
exposure standard) is controlled via a hierarchy of
controls, preferentially via source elimination,
exposure reduction, administrative controls or
hearing protection.
Model Work Health & Safety Regs 2010 r. 4.1.2
C Provide suitable hearing protection for
Savills employees in the Chiller Plant
Room, Fire Hydrant Pump Room and
the Fire Sprinkler Pump Room.
Contractors provide their own PPE.
14.3 Measures implemented to control workplace noise
have been reviewed / revised if conditions have
changed or there are concerns as to the
effectiveness of such controls.
Model Work Health & Safety Regs 2010 r. 4.1.3
N/A
14.4 Signs, labelling of plant or other appropriate means
are provided that identify when and where hearing
protectors are to be worn.
NC Affix hearing protection signs to the
doors leading to the Chiller Plant
Room (refer Photo 14.4), Fire Hydrant
Pump Room and the Fire Sprinkler
Pump Room.
14.5 Where hearing protectors are provided, audiometric
testing of relevant employees is performed at least
every 2 years.
N/A All contractors are responsible for
providing audiometric testing of their
employees that are exposed to
workplace noise.
14.6 Sufficient clear space for work areas and access
ways is provided to ensure employees can move
about freely without strain or injury.
Model Work Health & Safety Regs 2010 r. 3.1.1
C
14.7 Floors and other surfaces in the workplace are
designed, installed and maintained to allow work to
be carried out without risk to health and safety.
Model Work Health & Safety Regs 2010 r. 3.1.1
C
14.8 Lighting is provided that is appropriate for the various
types of tasks/activities being performed throughout
the building.
Model Work Health & Safety Regs 2010 r. 3.1.1
C
14.9 Light fittings are observed to be in good condition
and lights are operating correctly (i.e. no flickering)
Model Work Health & Safety Regs 2010 r. 3.1.1
C
14.10 Adequate ventilation rates, air quality levels and a
comfortable temperature range are maintained
throughout the building.
Model Work Health & Safety Regs 2010 r. 3.1.1
C
14.11 There is no cause to indicate concerns regarding the
quality of drinking water.
AZECC (Australian Drinking Water Guidelines) 2004,
NHMRC
C
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 34 of 43
15. Traffic Hazards
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
15.1 Appropriate speed humps have been installed in
aisles to control excessive speeding where the aisle
length is >100 metres or where there are >40 parking
spaces provided on either side.
AS/NZS 2890.1: 2004 s. 2.3.3, 4.9
N/A Not considered necessary given the
size of the car park.
15.2 Parking spaces/aisles are adequately sized and
clearly marked.
AS/NZS 2890.1: 2004 s. 2.4, 4.4
C
15.3 Wheel-stops or barriers are fitted to prevent vehicles
from running over the edge of a raised platform or
deck of a multi-storey car park.
AS/NZS 2890.1: 2004 s. 2.4.5
N/A
15.4 Protection is provided for pedestrians in the form of
marked crossing, kerbing, footpaths, barriers/guard
rails and signage.
AS/NZS 2890.1: 2004 s. 4
N/A Not considered necessary given the
size of the car park.
15.5 Road marking lines, directional arrows and signs are
clearly visible and unambiguous for drivers.
AS/NZS 2890.1: 2004 s. 4
N/A Not considered necessary given the
size of the car park.
15.6 Speed limits are clearly sign posted.
AS/NZS 2890.1: 2004 s. 4.3.4
N/A Not considered necessary given the
size of the car park.
15.7 Parking areas, circulation areas and pedestrian
pathways are adequately lit.
AS/NZS 2890.1: 2004 s. 4.7
C
15.8 Parking spaces for special loading/unloading
purposes (e.g. emergency services vehicles, people
with disabilities) are provided and clearly marked.
AS/NZS 2890.1: 2004 s. 4.7
BCA s. D3.5
N/A
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 35 of 43
16. Environmental Hazards
Risk Element
L = Low Risk Level, M = Medium Risk Level, H = High Risk Level, N/A = Not Applicable
Ref Finding/Observation Risk
Level
Accept
-able Comments
16.1 1 Previous environmental reports have been
provided by the property owner or relevant
environmental authority.
N/A N/A No previous reports available.
16.2 1 There is no soil or groundwater contamination
identified in previous reports.
N/A N/A No previous reports available.
16.3 1 There are no limitations to the current land use
based on above contamination if present.
National Environmental Protection Measure
1999 Schedule 7(a)
N/A N/A No previous reports available.
16.4 1 There are no restrictions placed on contact
with soils and/or groundwaters if
contamination is present.
NIOSH Exposure Standards
National Environmental Protection Measure
1999 Schedule 7(a)
N/A N/A No previous reports available.
16.5 1 There are no significant OH&S risks based on
potential contamination.
NIOSH Exposure Standards
National Environmental Protection Measure
1999 Schedule 7(a
M-H Yes
16.6 1 There are no environmental clean-up notices
or equivalent issued by the relevant
environmental authority.
M-H Yes
16.7 There are no potentially contaminating land
uses or tenants associated with the site.
M-H Yes There is a grease trap associated with
the Ground Level Café, although a
maintenance regime is in place to
reduce the potential for
contamination from this trap.
16.8 There are no nearby land users with potential
to cause significant contamination (e.g.
petrochemical plant).
H Yes
16.9 There are no licensed discharges from the site. M-H Yes
16.10 There are no hazardous wastes generated or
stored on the site.
M-H Yes
16.11 There is no evidence (e.g. fuel spills, odours) to
indicate significant environmental risks or
contamination is present that would require
further investigation.
AS4482.1-2005
AS4482.2-1999
National Environmental Protection Measure
1999 Schedule 7(a)
M-H Yes
16.12 There is no cause to indicate concerns
regarding noise emissions from any operations
on the site.
L-M Yes
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 36 of 43
17. Electrical Safety
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
17.1 At-risk employees are provided with information,
instruction and training regarding the associated
hazards and control processes.
Model Work Health and Safety Act 2010, Section 19
& 20
C No employees are required to work on
electrical equipment, with all relevant
contractors required to have received
associated training as part of Savills
policies/procedures.
17.2 Control measures are in place to minimise the risks
associated with electrical hazards.
Model Work Health & Safety Regs 2010 r. 4.7.7
C RCD’s are fitted to most base-building
electrical circuits; only licensed /
inducted personnel are permitted to
conduct electrical works; and routine
inspection / testing is undertaken on
electrical equipment.
17.3 Measures implemented to control risks associated
with electrical hazards have been reviewed /
revised if conditions have changed or there are
concerns as to the effectiveness of such controls.
Model Work Health & Safety Regs 2010 r. 4.7.8
N/A
17.4 Routine inspection / testing of electrical equipment
(including residual current devices [RCDs]) is
performed by a competent person undertaken to
detect obvious damage, wear or other conditions
which might render it unsafe.
Model Work Health & Safety Regs 2010 r. 4.7.9 &
4.7.22
AS/NZS 3760:2010, Appendix A1(b) & Table 4
C Annual inspection / testing of
electrical equipment and RCD’s is
performed by Hisbos, with this
equipment last tested on 24/12/2012.
17.5 Tags fitted to electrical equipment are durable,
legible, non-reusable, non-metallic and include the
name of the person / company who performed
the test, the test/inspection date, the nature &
outcome of the test, a re-test date and a
reference to AS/NZS 3760.
Model Work Health & Safety Regs 2010 r. 4.7.9
AS/NZS 3760:2010, s. 2.4.2.1
C
17.6 Any untested electrical equipment is not used in
the workplace.
Model Work Health & Safety Regs 2010 r. 4.7.10
C
17.7 Any electrical equipment deemed to be unsafe is
disconnected and removed from service until it is
repaired or tested and found to be safe.
Model Work Health & Safety Regs 2010 r. 4.7.11
C Hisbos have been requested to
provide a “repair register” to record
all faulty equipment (that shows
details of services or corrective
actions)
17.8 Measures are in place to ensure that electrical
equipment that has been de-energised to allow
electrical work to be carried out on it cannot be
inadvertently re energised while the work is being
carried out.
Model Work Health & Safety Regs 2010 r. 4.7.12
C Included as a requirement of the
Isolation Procedure in Savills’ OHS&E
Contractor Induction Manual.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 37 of 43
Electrical Safety (continued)
C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,
N/A = Not Applicable
Ref Finding/Observation Compliance Comments
17.9 Before work is undertaken on energised electrical
equipment, a risk assessment is conducted by a
competent person.
Model Work Health & Safety Regs 2010 r. 4.7.15
C
17.10 Any work undertaken on energised electrical
equipment is conducted by a competent person in
accordance with a safe work method statement
prepared for the work.
Model Work Health & Safety Regs 2010 r. 4.7.18
C
17.11 Each electrical circuit is protected by a RCD that is
incorporated before/part of each socket outlet.
Model Work Health & Safety Regs 2010 r. 4.7.21
SC Most base-building electrical circuits
are protected by RCD’s.
Ensure RCDs are fitted to all remaining
electrical circuits.
17.12 On-site documentation includes a register of all
equipment; a record of formal inspection and tests;
a 'repair' register; and a record of all faulty
equipment showing details of services or corrective
actions.
AS/NZS 3760:2010, s. 2.5.1
SC A register of all electrical appliances
that are subject to formal inspection
and regular testing / tagging has been
prepared. A 'repair' register and a
record of all faulty equipment (that
shows details of services or corrective
actions), however, has not been
prepared and this should be duly
rectified.
17.13 A thermographic survey of electrical switchboards
has been conducted.
C Hotspot Thermography conducted
thermographic surveys of all electrical
switchboards in March 2013.
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 38 of 43
18. Photos
Photo Ref. 2.4: Asbestos gaskets associated
with calorifier that are not suitably-labelled
Photo Ref. 3.15: No chemical bunding in
Basement Cleaners’ Room
Photo Ref. 9.2: Level 16 Water Storage Tanks
posing confined space hazards
Photo Ref. 11.2: Unprotected areas associated
with air handling plant in Level 16 Plant Room
Photo Ref. 14.4: Lack of hearing protection
signage fitted to the door leading to the Chiller
Plant Room and Fire Pump Room
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 39 of 43
Left Blank
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013
Page 40 of 43
Appendix A: Implementation Plan for Control Measures
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013
Page 41 of 43
Implementation Plan for Suggested Control Measures
Ref.
No. Additional Control Measure(s)
Suggested
Time-frame
Suggested
Person(s)
Implementation
Date Comments
2.4 Where practicable, arrange for labels to be fitted to
asbestos-containing materials. Completed
Facility
Manager Completed
2.6 Arrange for a review / update of the Asbestos Register. By August
2014
Facility
Manager
LRM Global to
provide proposal
2.7
Advise all tenants regarding the location of the
Asbestos Register and the Asbestos Management Plan,
within which the hazards posed by asbestos-containing
materials located within their tenancies and the
associated controls are specifically documented.
Contractors must be similarly advised as part of the site
specific inductions.
By March 2014 Facility
Manager Completed
2.13 Ensure the Asbestos Register is reviewed & updated
before future demolition / refurbishment is carried out. On-going
Facility
Manager
3.4
Ensure a Dangerous Goods / Hazardous Substances
Register is prepared and, when completed, kept up-to-
date on site in the Facility Manager’s Office.
By December
2013
Facility
Manager Completed
3.9
Arrange for a site-specific risk assessment to be
developed that focuses on the use, handling or storing
of hazardous chemicals.
By March 2014 Facility
Manager
3.15 Ensure all chemicals are positioned within suitable
containment bunds.
By February
2014
Facility
Manager
3.19 Provide eyewash facilities in the Basement Cleaners’
Room and cooling tower areas. By March 2014
Facility
Manager
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013
Page 42 of 43
Ref.
No. Additional Control Measure(s)
Suggested
Time-frame
Suggested
Person(s)
Implementation
Date Comments
3.23
Formally request the cleaning contractor provides
relevant PPE, along with associated training, to all on-
site employees.
By March
2014
Facility
Manager
Cleaning Contract
will be going out
to tender in 2014
9.2
Arrange for a Confined Spaces Audit to be undertaken
with input from key contractors (e.g. plumbing and
mechanical service providers). Once conducted, a site
plan of all identified confined spaces should be
prepared and made available to all relevant
contractors.
By March 2014 Facility
Manager
9.3 Suitably-label all identified confined spaces. By March 2014 Facility
Manager
10.2 Arrange for site-specific plant risk assessments to be
prepared for the boilers and air compressor. By March 2014
Facility
Manager
11.2
Control access to unprotected sections associated with
the Level 16 air handling units and ensure the Working
on Roofs Permit (refer Annexure L in Savills’ OH&S
Contractor Induction Guidelines) is used by contractors
requiring access to roof areas.
On-going Facility
Manager
11.3 Ensure risk assessments are prepared for each task
involved in working at heights. On-going
Facility
Manager
Ref.
No. Additional Control Measure(s)
Suggested
Time-frame
Suggested
Person(s)
Implementation
Date Comments
13.2
Arrange for emergency evacuation signs to be
prepared / displayed in the car park and plant room
areas.
By March 2014 Facility
Manager
459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013
Page 43 of 43
14.1
Arrange for noise level measurements to be undertaken
in noisy areas, such as the Chiller Plant Room, Fire
Hydrant Pump Room and the Fire Sprinkler Pump Room.
By February
2014
Facility
Manager
14.4
Affix hearing protection signs to the doors leading to
the Chiller Plant Room, Fire Hydrant Pump Room and
the Fire Sprinkler Pump Room.
By Mach 2014 Facility
Manager
17.11 Ensure RCDs are fitted to all remaining electrical circuits. By August
2014
Facility
Manager
17.12
Arrange for a repair register and a record of all faulty
equipment (that shows details of services or corrective
actions) to be prepared.
By March 2014 Facility
Manager