Hazard Identification & Compliance

Assessment

459 Little Collins Street, Melbourne

August 2013 (Revised February 2014)

Auditor - Savills (VIC) Pty Ltd

Building Representative – Bruce Hosking

Number of Pages - 43

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 2 of 43

Disclaimer

This report was prepared for Savills for the purpose set out herein. Responsibility is

disclaimed for any loss or damage (including but not limited to damage resulting from

the use by Uniting Church (NSW) Trust Association Ltd of this report) suffered by any

other person for any reason whatsoever including but not limited to negligence on the

part of Savills (VIC) Pty Limited. This report is confidential to Uniting Church (NSW) Trust

Association Ltd and Savills (VIC) Pty Limited does not intend that any other person

accept or rely upon it.

This report is based on our inspections and the information provided. Whilst this report is

accurate to the best of our knowledge and belief, Savills (VIC) Pty Limited cannot

guarantee the completeness or accuracy of any descriptions or conclusions based on

the supplied information.

The recommendations contained in this report are advisory only. No representation or

opinion is given to the effect that all applicable statutory rules and regulations and

directions have been given or will be complied with or that there are no other hazards

in existence.

Audited By: M. Puglielli Date: 20th August 2013 (Revised Feb 2014)

Position: Divisional Director

Before printing, think about the environment

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 3 of 43

Executive Summary

Savills Facilities Management was engaged to perform a hazard identification and

compliance assessment (HICA) of 459 Little Collins Street, Melbourne. The key

objectives of this project were to identify the outstanding occupational health, safety,

environmental (OHS&E) and associated business risks to Uniting Church (NSW) Trust

Association Ltd and (where applicable) develop practical and cost-effective measures to mitigate these risks.

The project involved a comprehensive inspection of the premises, along with a review

of relevant documentation and discussions with key on-site and contractor personnel.

A detailed checklist was utilised during the site visit, with this checklist incorporating a list

of current legislation, standards and codes of practice for a range of OHS&E hazards,

such as:

• Legionella

• Asbestos / Hazardous Materials

• Dangerous Goods / Hazardous Substances

• Hazardous Waste

• Disability Access

• Radio Frequency Radiation

• Fire

• Confined Spaces

• Plant Equipment

• Working at Height

• Emergency Management

• Workplace Environment

• Traffic Hazards

• Environmental Hazards

• Electrical Hazards

In addition, hazards affecting public liability (e.g. slips, trips and falls) and contractor

management were assessed against best-practice measures.

A total of 29 control measures have been recommended as part of the HICA project,

with prompt action duly required to address risks associated with falls from height and

hazardous chemicals in particular.

If required, Savills FM can coordinate the rectification measures nominated in this report

to further assist Uniting Church (NSW) Trust Association Ltd effectively discharge its legal

and moral obligations in the management of 459 Little Collins Street, Melbourne.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 4 of 43

Table of Contents

SECTION PAGE NO.

Introduction 5

Methodology 5

Site Description 6

Legionella 7

Asbestos / Hazardous Materials 9

Dangerous Goods / Hazardous Substances 12

Hazardous Waste 15

Public Liability 16

Disability Access 17

Radio Frequency Radiation 19

Fire 20

Confined Spaces 23

Plant Equipment 25

Working at Height 28

Contractors 30

Emergency Management 31

Workplace Environment 32

Traffic Hazards 33

Environmental Hazards 34

Electrical Hazards 36

Photos 38

Risk Assessment 40

Appendix A – Implementation Plan for Control Measures 50

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 5 of 43

Introduction

Savills Facilities Management was engaged to perform a hazard identification and

compliance assessment (HICA) of 459 Little Collins Street, Melbourne. The key

objectives of this project were to identify the outstanding occupational health, safety,

environmental (OHS&E) and associated business risks to Uniting Church (NSW) Trust

Association Ltd and (where applicable) develop practical and cost-effective measures to mitigate these risks.

Methodology

The general scope of works included the following:

A visit to site to inspect the premises.

A review of available documentation.

Follow-up discussions with key on-site and contractor personnel, where required.

Provision of a comprehensive report, summarising the findings / observations,

along with recommended control measures.

The project included identification / evaluation of the potential health risks associated

with the system in accordance with the general principles of AS/NZS ISO 31000: 2009

Risk management - Principles and guidelines.

A detailed checklist was utilised during the site visit, with this checklist incorporating a

list of current legislation, standards, codes of practice or measures deemed ‘best

practice’ for a range of OHS&E hazards, such as:

• Legionella

• Asbestos / Hazardous Materials

• Dangerous Goods / Hazardous Substances

• Hazardous Waste

• Disability Access

• Radio Frequency Radiation

• Fire

• Confined Spaces

• Plant Equipment

• Working at Height

• Emergency Management

• Workplace Environment

• Traffic Hazards

• Environmental Hazards

• Electrical Hazards

In addition, hazards affecting public liability (e.g. slips, trips and falls) and contractor

management were assessed against best-practice measures.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 6 of 43

Site Description

459 Little Collins Street is a 16-level office tower with a basement car park that was

originally constructed in 1969 and has since undergone numerous upgrades. It is

classified as C grade building with a net lettable area of approximately 9,962 square

metres and a recent 2-Star NABERS Energy Rating. The building is supported on

reinforced concrete caissons, with plasterboard internal walls and ceilings. The

external façade of the building is rendered pre-fabricated concrete panels, with

glazed panels fitted to the front and the rear façades. The building is currently owned

by Uniting Church (NSW) Trust Association Ltd and managed by Savills (VIC) Pty Ltd.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 7 of 43

1. Legionella

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

1.1 At-risk employees are provided with information,

instruction and training regarding the associated

hazards and control processes.

Model Work Health and Safety Act 2010, Section 19 &

20

C No employees (other than the Facility

Manager) are required to access the

cooling tower area, with the FM and all

contractors required to have received

associated training as part of Savills’

policies/procedures.

1.2 The cooling towers are registered in accordance

with applicable government requirements.

C The Main A/C Cooling Tower System

(CTS 899) and the Tenant A/C Cooling

Tower System (CTS 7016) are registered

with the Department of Health until

16/06/2014.

1.3 A risk assessment/management process has been

prepared, reviewed, and/or audited in accordance

with applicable government requirements.

C The Risk Management Plans (RMPs) are

reviewed and audited on an annual

basis.

The RMPs were last reviewed by Savills

on 30/10/2012. The RMPs were last

audited by ECC on 09/07/2012 for the

period 02/06/11 to 1/06/12 inclusive and

all audit requirements were deemed to

have been met.

1.4 The cooling water systems are equipped with a

certified process designed to control microbial

growth in accordance with applicable government

requirements.

C The maintenance/testing program for

each system is conducted in

accordance with the Risk Category ‘A’

ratings.

1.5 The cooling towers are inspected in accordance

with applicable government requirements.

C The cooling tower systems are inspected

weekly and serviced fortnightly by Hydo-

Chem in accordance with the Risk

Category ‘A’ ratings.

1.6 The cooling towers are cleaned /disinfected in

accordance with applicable government

requirements.

C The cooling towers are disinfected and

cleaned by Hydro-Chem on a quarterly

basis.

1.7 Maintenance/testing records, RMP are maintained in

accordance with applicable government

requirements.

C Copies of maintenance/testing reports

are kept on-site, along with the current

registration, RMP Reviews and RMP Audit

certificates.

1.8 Heterotrophic Colony Count and Legionella analysis

is performed in accordance with applicable

government requirements.

C HCC and Legionella analysis is

conducted on a monthly basis and

results distributed electronically to all

stakeholders as soon as the results are

available.

1.9 Remedial actions in response to adverse bacterial

results are undertaken in accordance with

applicable government requirements.

N/A There have been no adverse bacterial

results recorded during the period of

review.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 8 of 43

Legionella (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

1.10 Relevant authorities have been formally advised of

adverse bacterial results in accordance with

applicable government requirements.

N/A There have been no adverse bacterial

results recorded during the period of

review requiring external notification.

1.11 Dosing / bleed-off devices are fitted to the cooling

tower systems in accordance with applicable

government requirements.

AS/NZS 3666.2 s.2.5.2

C The cooling tower systems are fitted with

monitoring/control equipment that

enables automatic bleed-off and

addition of dual biocides and corrosion

inhibitor.

1.12 Safe / ready access is provided to enable inspection,

cleaning and maintenance of the cooling towers in

accordance with applicable government

requirements.

AS/NZS 3666.2 s. 2.2.3

SC Safe/ready access to the cooling towers

CTS 899 & 7016 are provided for

inspection and maintenance activities.

Although, some improvements are

required to the safe access to cooling

tower 7016.

1.13 Drift eliminators (with a drift loss rating of <0.002% of

the circulation rate) are fitted across the entire air

stream.

AS/NZS 3666.1 s.4.15 & s4

C

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 9 of 43

2. Asbestos / Hazardous Materials

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

2.1 At-risk employees are provided with information,

instruction and training regarding the associated

hazards and control processes.

Model Work Health and Safety Act 2010, Section 19 &

20

C No employees are required to access

areas where asbestos-containing

materials are located, with all building

contractors required to have received

associated training as part of Savills’

policies/procedures.

2.2 Exposure to airborne asbestos in the workplace is

either eliminated or (practicably) minimised (e.g. via

enclosing or sealing asbestos).

Model Work Health & Safety Regs 2010 r. 7.3.2

C The vinyl tiles on the tenanted floors are

unlikely to be disturbed, due to the

protection afforded by a covering of

carpet. The asbestos in the ductwork

joint mastic has not been sealed, due to

issues of access. The nature of these

asbestos-containing materials is such

that it does not pose a high risk of

exposure, given that Savills Contractor

Induction Guidelines forms the basis for

controlling works that may potentially

disturb or damage these materials.

2.3 Asbestos at the workplace has been identified (or a

presumption of its presence made) by a competent

person.

Model Work Health & Safety Regs 2010 r. 7.3.4

C An Asbestos Register was undertaken as

part of an Asbestos Management Plan

by Noel Arnold & Associates in August

2009.

2.4 The presence and location of asbestos has been

clearly indicated, preferably via labelling.

Model Work Health & Safety Regs 2010 r. 7.3.6

PC Where practicable, the majority of

asbestos-containing materials (i.e.

encapsulated fire doors, plant room

walls) has been appropriately labelled.

There are, however, other materials

identified in the Asbestos Register are

concealed in the ceiling space

2.5 An Asbestos Register (that details the location,

source, type, friability and condition of identified

asbestos, along with activities likely to damage /

disturb the asbestos and inaccessible areas likely to

contain asbestos) has been developed.

Model Work Health & Safety Regs 2010 r. 7.3.7

Code of Practice How to Manage and Control

Asbestos in the Workplace

C An Asbestos Register was undertaken as

part of an Asbestos Management Plan

by Noel Arnold & Associates in August

2009.

2.6 An Asbestos Register has been reviewed and (if

necessary) adjusted if the risk assessment or a control

measure is reviewed; or if further asbestos is identified

at the workplace.

Model Work Health & Safety Regs 2010 r. 7.3.8

C The last Asbestos survey was carried out

on the August 2009 by Noel Arnold and

Associates. An update is due August

2014.

Ensure the Asbestos Register is updated

to reflect the recent asbestos removal.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 10 of

43

Asbestos / Hazardous Materials (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

2.7 An Asbestos Register has been maintained and

made available to building occupants, contractors

and/or health & safety reps.

Model Work Health & Safety Regs 2010 r. 7.3.9

C The Asbestos Register is kept on site in

the Facility Manager’s Office and made

available to building occupants and

contractors as required.

2.8 An Asbestos Management Plan has been developed

and maintained on site.

Model Work Health & Safety Regs 2010 r. 7.3.11

Code of Practice How to Manage and Control

Asbestos in the Workplace

C An Asbestos Management Plan was

prepared by Noel Arnold & Associates in

August 2009. Ensure the Asbestos

Management plan is reviewed to reflect

the recent asbestos removal.

2.9 An Asbestos Management Plan has been reviewed

and revised at least once every 5 years or if there is a

review of the asbestos register, risk assessment or a

control measure.

Model Work Health & Safety Regs 2010 r. 7.3.12

C The Asbestos Register and Asbestos

Management Plan is due for review by

August 2014.

2.10 A risk assessment of the asbestos at the workplace

has been undertaken by a competent person and

conducted prior to any works commencing that

might disturb asbestos.

Model Work Health & Safety Regs 2010 r. 7.3.13

Code of Practice How to Manage and Control

Asbestos in the Workplace

C

2.11 A risk assessment has been reviewed and (if

necessary) revised by a competent person if a

change is made that affects the risk of exposure to

asbestos at the workplace or the condition of

asbestos changes.

Model Work Health & Safety Regs 2010 r. 7.3.14

C

2.12 Any person who is suspected of being exposed to

asbestos fibres (following uncontrolled disturbance of

asbestos in the workplace) has been promptly

identified and provided with information about

exposure to airborne asbestos.

Model Work Health & Safety Regs 2010 r. 7.3.15

N/A

2.13 An Asbestos Register has been reviewed and (if

necessary) adjusted before demolition/refurbishment

is carried out at the workplace.

Model Work Health & Safety Regs 2010 r. 7.3.22

PC Ensure the Asbestos Register is reviewed

& updated before future demolition /

refurbishment is carried out. In addition,

Part 6 asbestos audits are conducted.

2.14 An Asbestos Register has been provided to the

person conducting demolition/refurbishment before

such works have been started.

Model Work Health & Safety Regs 2010 r. 7.3.23

C

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 11 of

43

Asbestos / Hazardous Materials (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

2.15 Asbestos likely to be disturbed by

demolition/refurbishment has been identified and

(practicably) removed before such works have been

started.

Model Work Health & Safety Regs 2010 r. 7.3.26

C

2.16 Details regarding asbestos removal work are

communicated to affected building occupants and

those within the immediate vicinity of the workplace.

Model Work Health & Safety Regs 2010 r. 7.3.42

N/A Removal of asbestos containing vinyl

floor tiles was carried out in the lift motor

room under controlled conditions by

LRM Global. Removal of asbestos

containing vinyl floor tiles was carried

out under controlled conditions on

builders controlled floor level 9 on

09/05/2012.

2.17 Access to an asbestos removal area has been

restricted to only authorised personnel.

Model Work Health & Safety Regs 2010 r. 7.3.44

C

2.18 An independent licensed assessor has undertaken air

monitoring of asbestos removal areas that require a

Class A asbestos removal licence.

Model Work Health & Safety Regs 2010 r. 7.3.48

C

2.19 The results of air monitoring are provided to contract

personnel, health & safety reps and building

occupants.

Model Work Health & Safety Regs 2010 r. 7.3.48

Code of Practice How to Safely Remove Asbestos

C Air monitoring results are provided to

affected contractor personnel. Air

monitoring results should also be relayed

to the building tenants.

2.20 A Hazardous Materials Survey (including lead,

synthetic mineral fibres, polychlorinated by-phenyls)

has been conducted and is available on site.

C A Hazardous Materials Survey was

conducted by Noel Arnold & Associates

in August 2009 and is located in the

Facility Manager’s Office. A review is

due August 2014.

2.21 The local authority has been suitably-notified where

premises contain more than 10kg of PCBs.

The Polychlorinated Biphenyls Management Plan,

Australian & New Zealand Environment and

Conservation Council (ANZECC).

N/A

2.22 Where appropriate, a PCB Management Plan is

available for the site.

The Polychlorinated Biphenyls Management Plan,

Australian & New Zealand Environment and

Conservation Council (ANZECC).

SC Given the relatively minor quantities

remaining, a PCB Management Plan has

not been prepared. PCBS have been

removed from basement car park areas,

with a clearance report provided

accordingly. Remaining PCBs in plant

room areas are scheduled for removal

by 2014.

2.23 Measures are in place to control ozone depleting

refrigerant gases, including provision of data to

management regarding any associated losses.

C NAMS conducts regular checks to

determine refrigerant leaks as part of its

maintenance agreement.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 12 of 43

3. Hazardous Chemicals

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

3.1 At-risk employees are provided with appropriate

information, instruction and training regarding the

hazards; risk identification/assessment; risk control

processes; emergency plans; and use of relevant

PPE.

Model Work Health & Safety Regs 2010 r. 7.1.56

C No employees are required to handle

dangerous goods or hazardous

substances, with all contractors

required to have received associated

training as part of Savills’

policies/procedures.

3.2 Hazardous chemicals are correctly labelled in

accordance with Schedule 9 of the Model Work

Health & Safety Regs.

Model Work Health & Safety Regs 2010 r. 7.1.6 & 7.1.7

C

3.3 Current versions of Material Safety Data Sheets are

readily available on site.

Model Work Health & Safety Regs 2010 r. 7.1.21

C All current MSDS were available for the

chemicals located in the Basement

Cleaners’ Room. All current MSDS for

the water treatment chemicals are

current and available on site.

3.4 A hazardous chemicals register (which includes the

current MSDS) has been maintained and is readily

available on site.

Model Work Health & Safety Regs 2010 r. 7.1.23

C A Dangerous Goods/Hazardous

Substances Register was developed

on 30 July 2012 by LRM Global

3.5 A suitably compliant manifest has been prepared,

maintained and suitably located where quantities of

dangerous goods exceed the nominated amount in

Schedule11, table 11.1 of the Model Work Health &

Safety Regs.

Model Work Health & Safety Regs 2010 r. 7.1.26

N/A Quantities of dangerous goods stored

on site are below the thresholds listed

in Schedule 11 of the Regulations.

3.6 The local regulator has been notified in writing if

manifest quantities of hazardous chemicals are

exceeded.

Model Work Health & Safety Regs 2010 r. 7.1.27

N/A

3.7 A suitably compliant outer warning placard is

displayed at the workplace where quantities of

dangerous goods exceed the nominated amount in

Schedule11, table 11.1 of the Model Work Health &

Safety Regs.

Model Work Health & Safety Regs 2010 r. 7.1.29

N/A

3.8 A suitably compliant dangerous goods placard is

displayed at the workplace where quantities of

dangerous goods exceed the nominated amount in

Schedule11, table 11.1 of the Model Work Health &

Safety Regs.

Model Work Health & Safety Regs 2010 r. 7.1.30

N/A

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 13 of 43

Hazardous Chemicals (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

3.9 Hazards associated with using, handling or storing

hazardous chemicals at the workplace have been

identified.

Model Work Health & Safety Regs 2010 r. 7.1.31

NC There does not appear to be any risk

assessments completed for dangerous

goods or hazardous substances that

are kept on site.

Ensure a site-specific risk assessment

that focuses on the use, handling or

storing of hazardous chemicals is

prepared prior to commencement of

works.

3.10 Exposure to hazardous chemicals is controlled via a

hierarchy of controls, preferentially via elimination,

substitution, reduction, isolation, engineering controls,

administrative controls then PPE.

Model Work Health & Safety Regs 2010 r. 7.1.32

C

3.11 Risk assessments have been reviewed at least once

every 5 years or more regularly if required.

Model Work Health & Safety Regs 2010 r. 7.1.33

N/A Once completed, the risk assessment

will need to be reviewed at least once

every 5 years.

3.12 Hazardous chemicals are appropriately isolated from

incompatible substances/materials (e.g. via

separation or segregation).

Model Work Health & Safety Regs 2010 r. 7.1.35

C Only minor quantities of Class 6 and

Class 8 chemicals are stored on-site

(mostly within the cooling tower areas

and the Cleaners Room).

3.13 Flammable or combustible substances are kept at

the lowest practicable quantity for the workplace.

Model Work Health & Safety Regs 2010 r. 7.1.37

C

3.14 Ignition sources in a hazardous area at the

workplace are either eliminated or practicably

minimised.

Model Work Health & Safety Regs 2010 r. 7.1.38

C

3.15 Measures are in place (including available

equipment/materials) to promptly contain, clean-up

and dispose of spillages of hazardous chemicals.

Model Work Health & Safety Regs 2010 r. 7.1.39

NC There is no bunding in the Basement

Cleaners’ Room (refer Photo 3.15a) to

assist in containing chemical spillages.

Ensure all chemicals are positioned

within suitable containment bunds. The

cooling tower chemical are well

bunded.

3.16 Containers of hazardous chemicals and any

associated pipe work/attachments are protected

against damage.

Model Work Health & Safety Regs 2010 r. 7.1.40

C

3.17 Fire protection equipment that is designed and built

for the types of hazardous chemicals at the

workplace is maintained on site at all times.

Model Work Health & Safety Regs 2010 r. 7.1.41

C An appropriate fire extinguisher is

located in close proximity of the

Basement Cleaners Room.

3.18 A copy of an appropriate emergency plan must be

provided to the emergency services authority if

manifest quantities of hazardous chemicals are

exceeded.

Model Work Health & Safety Regs 2010 r. 7.1.43

N/A

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 14 of 43

Hazardous Chemicals (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

3.19 Relevant safety equipment associated with the use,

handling or storage of hazardous chemicals is

maintained and readily accessible.

Model Work Health & Safety Regs 2010 r. 7.1.44

NC There are no eyewash facilities

provided in the Basement Cleaners’

Room or either of the cooling tower

areas and this should be duly rectified.

3.20 Bulk hazardous chemical containers and any

associated pipe work/attachments are securely

mounted and suitably protected against damage.

Model Work Health & Safety Regs 2010 r. 7.1.49

C

3.21 Containers of hazardous chemicals no longer in use

have been completely cleaned or disposed of or

correctly labelled.

Model Work Health & Safety Regs 2010 r. 7.1.50

C The underground fuel storage tank

located in the Ground Floor Loading

Dock has been de-commissioned by

Gen Care and a de-commissioning

certificate provided accordingly.

3.22 The local regulator has been notified where an

underground storage tank (that previously held

dangerous goods of class 2.1 or class 3, or C1

combustible liquids) has been abandoned.

Model Work Health & Safety Regs 2010 r. 7.1.52

N/A

3.23 Suitable and well-maintained PPE is provided to at-

risk employees.

Model Work Health & Safety Regs 2010 r.3.2.1 & 3.2.2

NC The cleaners have not provided their

cleaning staff with appropriate PPE and

(along with associated training) should

be duly provided.

3.24 Measures are in place to ensure the risk to

people/property at or beyond the site boundaries

are controlled by isolation.

Dangerous Goods (Storage & Handling) Regulations

2007 r. 415

N/A

3.25 Adequate ventilation is provided to maintain a safe

working atmosphere in the storage and handling

area.

Dangerous Goods (Storage & Handling) Regulations

2007 r. 425

C

3.26 Gas cylinders are secured in an upright position in

well-ventilated storage areas.

AS/NZS 1596: 2008, s. 2.3.

AS4332: 2004, s. 2.5

N/A There are no gas cylinders currently

stored on site.

3.27 Oxygen cylinders are stored at least 3 metres from

fuel gas cylinders.

AS/NZS 1596: 2008, s. 2.3.

AS4332: 2004, s. 2.5

N/A There are no gas cylinders currently

stored on site.

3.28 Full and empty gas cylinders are stored separately.

AS/NZS 1596: 2008, s. 4

AS4332: 2004, s. 8

N/A There are no gas cylinders currently

stored on site.

3.29 Signs such as “Danger: No Smoking, No Ignition

Sources” and “Restricted Area, Authorised Personnel

Only” are displayed in cylinder storage areas.

AS/NZS 1596: 2008, s. 12.

AS4332: 2004, s. 6.4

N/A There are no gas cylinders currently

stored on site.

3.30 Appropriate flashback arrestors are fitted to fuel gas

cylinders, fitted at the regulator outlet with a non-

return valve and a temperature actuated cut-off

valve.

AS/NZS 1596: 2008, s. 4.2

N/A There are no gas cylinders currently

stored on site.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 15 of 43

4. Hazardous Waste Management

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

4.1 At-risk employees are provided with information,

instruction and training regarding the associated

hazards and control processes.

Model Work Health and Safety Act 2010, Section 19 &

20

C No hazardous wastes are stored,

produced or disposed of from this

site.

4.2 Hazardous waste is appropriately stored on site in

accordance with local authority requirements.

N/A

4.3 Hazardous waste is appropriately removed and

disposed of in accordance with local authority

requirements.

N/A

4.4 Appropriate transport waste certificates are held on

site in accordance with local authority requirements.

N/A

4.5 Trade Waste Agreements (TWAs) are in place for

discharges to sewers other than domestic sewage

(kitchen/toilets) and all associated conditions

imposed by the local authority have been duly met.

C A TWA is in place for the 2000L Grease

interceptor (GRI-01) and expires

08/05/2012. A TWA has also been

obtained for the Cooling Towers on

site (Ref 34100109011)and expires 8th

of May 2021.

4.6 Waste management records are maintained for

liquid and solid hazardous wastes on site in

accordance with local authority requirements.

N/A

4.7 Prescribed waste requirements have been

determined for the facility in accordance with local

authority requirements.

N/A

4.8 Contractors engaged to dispose of prescribed waste

are suitably-licensed waste removal contractors.

N/A

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 16 of 43

5. Public Liability

Risk Element

L = Low Risk Level, M = Medium Risk Level, H = High Risk Level, N/A = Not Applicable

Ref Finding/Observation Risk

Level

Accept

-able Comments

5.1 Floor areas within the common areas of the

complex are free from protrusions.

Model Work Health & Safety Regs 2010 r. 3.1.1

L Yes

5.2 Areas that are wet and slippery are signposted.

Model Work Health & Safety Regs 2010 r. 3.1.1

L Yes Cleaners and/or the Facility Manager

control wet / slippery areas with

warning signs suitably displayed during

cleaning and inclement weather.

5.3

Entrances to the building are safe, clear, slip

resistant and free of trip hazards.

Model Work Health & Safety Regs 2010 r. 3.1.1

L No Slip testing of the external entry and

ground floor foyer areas was

conducted by Slip Smart during

December 2013, with the foyer

exhibiting a very high risk of slipping

during the wet test. Measures are in

place to address the risk posed by

rainwater entry and spills.

5.4 Entrances to tenancies are clear and free of trip

hazards.

Model Work Health & Safety Regs 2010 r. 3.1.1

L Yes

5.5 There are inclement weather mats at the

entrances to the building.

Model Work Health & Safety Regs 2010 r. 3.1.1

M Yes

5.6 Areas are free from cables/cords, or if

cables/cords are used they are appropriately

covered to prevent trips.

Model Work Health & Safety Regs 2010 r. 3.1.1

L Yes

5.7 Housekeeping is adequate in public areas and

is uncluttered and free of rubbish.

Model Work Health & Safety Regs 2010 r. 3.1.1

L Yes

5.8 Paved areas are in good condition.

Model Work Health & Safety Regs 2010 r. 3.1.1

L Yes

5.9 Handrails are installed at stairs/steps.

Model Work Health & Safety Regs 2010 r. 3.1.1

M Yes

5.10 Expansion joints are in good condition and

sealed flush to the surface.

Model Work Health & Safety Regs 2010 r. 3.1.1

L Yes

5.11 Trip hazards associated with steps and stairs

(including treads) are controlled.

Model Work Health & Safety Regs 2010 r. 3.1.1

H Yes

5.12 Entrances are protected from storm water

incursion (rain does not enter the building).

Model Work Health & Safety Regs 2010 r. 3.1.1

M Yes

5.13 Processes are in place to isolate and clean-up

spills.

Model Work Health & Safety Regs 2010 r. 3.1.1

M Yes Cleaners are on site to manage any spills throughout the day.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 17 of 43

Public Liability (continued)

Risk Element

L = Low Risk Level, M = Medium Risk Level, H = High Risk Level, N/A = Not Applicable

Ref Finding/Observation Risk

Level

Accept

-able Comments

5.14 Regular inspections are undertaken of common

areas by centre management/property

manager.

Model Work Health & Safety Regs 2010 r. 3.1.1

H Yes The Facility Manager conducts

monthly inspections of the premises

and these are formally documented

and filed electronically.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 18 of 43

6. Disabled Access

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

6.1 There has been an extension to, or modification of,

any part of the building that necessitated submission

of a building permit application to the local authority

on/after 1 May 2011.

N/A There have been no triggers of the

provisions of the Commonwealth

Disabled (Access to Buildings-Premises)

Standards 2010 during the past 12

months.

6.2 A building certifier or building developer has formally

verified that the deemed-to-satisfy provisions of the

2010 Access Code for Buildings (i.e. clauses D3.1 to

D3.12; E3.6; F2.2; and F2.4) have been met for the

‘affected part1’ of the building.

Commonwealth Disabled (Access to Buildings-

Premises) Standards 2010, Clause 3.2 (1a)

N/A

6.3 Access has been provided to enable people to:

(a)(i) approach the building from the road boundary

and from any accessible car-parking spaces

associated with the building; and

(ii) approach the building from any accessible

associated building; and

(iii) access work and public spaces, accommodation

and facilities for personal hygiene; and

(b) identify accessways at appropriate locations

which are easy to find.

Commonwealth Disabled (Access to Buildings-

Premises) Standards 2010, Clause DP1

N/A

6.4 Exits have been provided from the building to allow

occupants to evacuate safely, with their number,

location and dimensions being appropriate to:

(a) the travel distance; and

(b) the number, mobility and other characteristics of

occupants; and

(c) the function or use of the building; and

(d) the height of the building; and

(e) whether the exit is from above or below ground

level.

Commonwealth Disabled (Access to Buildings-

Premises) Standards 2010, Clause DP4

N/A

6.5 Accessways to exits have dimensions appropriate to:

(a) the number, mobility and other characteristics of

occupants; and

(b) the function or use of the building.

Commonwealth Disabled (Access to Buildings-

Premises) Standards 2010, Clause DP6

N/A

1 An ‘affected part’ is: (a) the principal pedestrian entrance of an existing building that contains a new

part; and (b) any part of an existing building, that contains a new part, that is necessary to provide a

continuous accessible path of travel from the entrance to the new part.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 19 of 43

Disability Access (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

6.6 Car-parking spaces for use by people with a disability

have been:

(a) provided, to the degree necessary, to give

equitable access for car-parking; and

(b) designated and easy to find.

Commonwealth Disabled (Access to Buildings-

Premises) Standards 2010, Clause DP82

N/A

6.7 An inbuilt communication system for entry,

information, entertainment, or for the provision of a

service, is provided that is suitable for occupants who

are deaf or hearing impaired.

Commonwealth Disabled (Access to Buildings-

Premises) Standards 2010, Clause DP93

N/A

6.8 Passenger lifts required to be accessible are suitable

for use by people with a disability.

Commonwealth Disabled (Access to Buildings-

Premises) Standards 2010, Clause EP3.4

N/A

6.9 Suitable sanitary facilities for personal hygiene are

provided in a convenient location (within or

associated with the building) to the degree

necessary, appropriate to:

(a) the function or use of the building; and

(b) the number and gender of the occupants; and

(c) the disability or other particular needs of the

occupants.

Commonwealth Disabled (Access to Buildings-

Premises) Standards 2010, Clause FP2.1

N/A

2 Clause DP8 does not apply to a building where: (a) a parking service is provided; and (b) direct access to any car-parking spaces by the general public or occupants is not available.

3 Clause DP9 does not apply to an inbuilt communication system used only for emergency warning purposes.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 20 of 43

7. Radio Frequency Radiation

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

7.1 At-risk employees are provided with information,

instruction and training regarding the associated

hazards and control processes.

Model Work Health and Safety Act 2010, Section 19 &

20

N/A There are no radio frequency

radiation devices on site.

7.2 Risk assessments have been undertaken for

plant/equipment capable of emitting harmful

radiation, and a register kept.

Arpansa Radiation Protection Standard Part 5.1.2a

N/A

7.3 Radio frequency radiation (RFR) exposure levels

associated with transmitter towers or receivers have

been determined where appropriate.

Arpansa Radiation Protection Standard Part 5.1.2b

N/A

7.4 A site plan that shows RFR hazard zones exists where

exposure standards are exceeded.

Arpansa Radiation Protection Standard Part 5.1.2b

N/A

7.5 Radiation Safety Manual has been developed.

Arpansa Radiation Protection Standard Part 5.1.1

N/A

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 21 of 43

8. Fire Safety

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

8.1 Annual fire safety measures report/certificate is

current and displayed appropriately.

BCA 2005

C All aspects relating to fire safety and

compliance have been assessed

within the Contractor’s Performance

Assessment Report and the Egress

Analysis Report (refer to separate

reports prepared by Savills in July

2013).

Any specific non-conformance(s)

observed during the site inspection

are duly recorded in the above

mentioned reports.

8.2 There is a programmed preventative maintenance

schedule for the maintenance of each fire safety

measure in the building.

BCA 2005

C

8.3 Maintenance records/logbooks for essential services

are kept on site and are readily available if required.

BCA 2005

C

8.4 Occupancy certificates/permits are available and

kept on site.

BCA 2005

8.5 Penetrations in boundary walls are adequately fire

stopped (e.g. plant rooms).

BCA 2005 C3

C

8.6 Fire doors are suitably tagged.

BCA 2005 C3.4

C

8.7 Fire doors self closing.

BCA 2005 C3.4

C

8.8 Appropriate fire doors have signage that indicates

‘Fire Door, Do Not Obstruct, Do Not Keep Open’

BCA 2005 C3.4

C

8.9 Fire isolated exits (corridors) are devoid of

combustible materials and free of obstructions.

BCA 2005 C & D

C

8.10 Fire isolated exits contain Fire Safety Notices (NSW

only)

EP&A Regs NSW 2000

N/A

8.11 Paths of travel to exits are free of obstructions (i.e.

exit path width of 1000mm is maintained at all times

(within tenancies)

BCA 2005 Part B1.10

C

8.12 Exit doors are free to open into a clear space and

are not obstructed externally.

BCA 2005 Part D2.20 (b)

C

8.13 Fire extinguishers are mounted and location signage

is clearly visible and identifiable.

AS2444

C

8.14 Access to fire extinguishers is within 15 metres. (Within

each tenancy)

AS2444

C

8.15 Access to fire extinguishers is clear of obstructions.

AS2444

C

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 22 of 43

Fire Safety (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

8.16 The yellow maintenance record tags are securely

tied to the fire extinguisher.

AS2444

C

8.17 The fire hose reel location signage is clearly visible

(e.g. where mounted in a cabinet, the door of the

cabinet shall display the words ‘Fire Hose Reel’

AS2441

C

8.18 The fire hose reels are properly wound and in the

interlock positions.

AS2441

C

8.19 Access to the fire hose reels is not restricted

/obstructed.

AS2441

C

8.20 The yellow maintenance record tags are securely

tied to the fire hose reels.

AS2441

C

8.21 Where fire hydrants are mounted in a cabinet, the

door of the cabinet shall display the word ‘Fire

Hydrant’.

AS2419.1

C Fire Hydrant cupboard located in the

basement car park have

appropriate sign displayed.

8.22 Access to the hydrants is not restricted / obstructed.

AS2419.1

C

8.23 The yellow maintenance record tags are securely

tied to the fire hydrants.

AS2419.1

C

8.24 Adequate clearance is maintained below the

sprinkler heads, i.e. a clear space of 500mm is

provided around the sprinkler heads (e.g. storage of

goods is not too close to the sprinkler heads).

AS2118.1

C

8.25 Sprinkler block plan is displayed in the sprinkler valve

room or fire control room.

AS2118.1

C

8.26 Representative smoke/heat detectors observed

appear to be free of damage and securely fixed to

their mountings.

C

8.27 Fire indicator panel is free of damage and securely

fixed.

C

8.28 Emergency lighting is securely mounted and free

from damage (shops >300m2)

BCA 2005 Part E4.2b

C

8.29 Emergency lighting is in good working order. C

8.30 Exit signs are securely mounted and free from

damage. (shops >300m2)

C

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 23 of 43

Fire Safety (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

8.31 Exit signs are generally visible and illuminated

AS2293.1

C

8.32 Exit signs are directing occupants to the correct

egress paths.

BCA 2005 Part E4.5

C

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 24 of 43

9. Confined Spaces4

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

9.1 Persons working in a confined space are provided

with information, instruction and training regarding

the associated hazards, control measures, use of PPE,

the confined space entry permit system and the

emergency procedures.

Model Work Health & Safety Regs 2010 r. 4.3.19

C All contractors are responsible for

undertaking site-specific risk

assessments and providing relevant

information, instruction and training to

their staff that are required to work in

a confined space.

9.2 Confined spaces have been identified on site.

AS2865: 2001 clause 8.1

PC The pits in the Basement Car Park and

Sprinkler Room; the Level 16 Water

Storage Tanks (refer Photo 9.2); and

some of the air handling units have

been identified as potential confined

spaces. A formal audit of all confined

spaces within the building has not

been conducted.

Undertake a Confined Spaces Audit

with the input from key contractors

(e.g. plumbing and mechanical

service providers). Once conducted,

a site plan of all identified confined

spaces should be prepared and

made available to all relevant

contractors.

9.3 Confined space entry points are clearly marked and

easily identified.

NC Suitably-label all identified confined

spaces.

9.4 All risks to health or safety associated with work in a

confined space have been identified through a risk

assessment process, which is reviewed / revised as

necessary.

Model Work Health & Safety Regs 2010 r. 4.3.7

C Risk assessments are to be

completed by the relevant

contractor before commencing any tasks within the confined spaces.

9.5 Measures designed to control the specific risks

associated with work in a confined space are in

place and reviewed/revised as necessary.

Model Work Health & Safety Regs 2010 r. 4.3.8 &

4.3.20

C Measures designed to control the

specific risks with work in a confined

space are evaluated / modified (as

necessary) by the relevant

contractor before commencing any tasks.

9.6 A confined space entry permit system (in

accordance with the requirements outlined in r. 4.3.9

of the Model Work Health & Safety Regs 2010) is in

place and is a condition of entry therein.

Model Work Health & Safety Regs 2010 r. 4.3.9

C All contractors are required to comply

with Savills’ Confined Space Entry

Permit System should entry therein be

required.

9.7 Signs prohibiting unauthorised access to confined

spaces are prominently displayed next to each entry

immediately before and during work being

performed.

Model Work Health & Safety Regs 2010 r. 4.3.10

C Included as a requirement of the

Confined Space Entry Procedure in

Savills’ OHS&E Contractor Induction

Manual.

4 A Confined Space shall encompass Restricted Access / Egress Spaces, with all measures (other than items 9.7, 9.8 & 9.9) listed herein deemed applicable.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 25 of 43

Confined Spaces (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

9.8 A continuous communication system between those

within and outside the confined space is in place

and is a condition of entry therein.

Model Work Health & Safety Regs 2010 r. 4.3.11

C Included as a requirement of the

Confined Space Entry Procedure in

Savills’ OHS&E Contractor Induction

Manual.

9.9 A lock-out and tag system is in place to reduce the

risk of any substance being introduced or any

plant/service being activated or energised in a

confined space.

Model Work Health & Safety Regs 2010 r. 4.3.12

C Included as a requirement of the

Confined Space Entry Procedure in

Savills’ OHS&E Contractor Induction

Manual.

9.10 Measures are in place to ensure a safe atmosphere

within the confined space is provided.

Model Work Health & Safety Regs 2010 r. 4.3.13 &

4.3.14

C Included as a requirement of the

Confined Space Entry Procedure in

Savills’ OHS&E Contractor Induction

Manual.

9.11 Measures are in place to ensure the concentration of

any flammable gas/vapour is kept below unsafe

levels.

Model Work Health & Safety Regs 2010 r. 4.3.15

C Included as a requirement of the

Confined Space Entry Procedure in

Savills’ OHS&E Contractor Induction

Manual.

9.12 No ignition source is introduced to the confined

space where there is a likelihood of fire or explosion.

Model Work Health & Safety Regs 2010 r. 4.3.16

C Included as a requirement of the

Confined Space Entry Procedure in

Savills’ OHS&E Contractor Induction

Manual.

9.13 Plant and equipment used to control risk associated

with the entry to and work in a confined space is

regularly maintained (i.e. gas monitor is tested and

calibrated annually).

C Included as a requirement of the

Confined Space Entry Procedure in

Savills’ OHS&E Contractor Induction

Manual.

9.14 Emergency procedures are established to enable

the safe/timely rescue and provision of first aid to a

person in or rescued from a confined space.

Model Work Health & Safety Regs 2010 r. 4.3.17 &

4.3.18

C Included as a requirement of the

Confined Space Entry Procedure in

Savills’ OHS&E Contractor Induction

Manual.

9.15 Records of relevant documentation (i.e. personnel

training, risk assessments and copies of confined

space entry permits issued) are kept on site.

Model Work Health & Safety Regs 2010 r. 4.3.21

C

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 26 of 43

10. Plant & Certification of Operators

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

10.1 At-risk employees are provided with information and

instruction in hazard identification/risk control; plant

safety procedures; and use of relevant PPE.

Model Work Health & Safety Regs 2010 r. 5.1.28

C Other than the Facility Manager, no

employees are required to access

plant equipment areas, with the

Facility Manager and all contractors

required to have received associated

training as part of Savills

policies/procedures.

10.2 All OH&S hazards associated with the systems of work

relating to plant equipment have been identified

through a risk assessment process.

PC A risk assessment has been provided

for the lifts, but not for the boilers and

air-compressor on site.

Ensure site-specific plant risk

assessments are prepared for the

boilers and air compressor.

10.3 The risks associated with plant equipment are

minimised via a hierarchy of controls, preferentially

via substitution, isolation, engineering controls,

documented administrative controls (e.g. safe work

method statements) or the use of PPE.

Model Work Health & Safety Regs 2010 r. 5.1.21

C

10.4 Measures are in place to control risks to health and

safety associated with plant or its associated systems

of work are reviewed / revised as necessary.

Model Work Health & Safety Regs 2010 r. 5.1.23

C As per Savills’ policies / procedures,

measures designed to control the

specific health and safety risks are

required to be evaluated / modified

(as necessary) by the relevant

contractor before commencing any tasks.

10.5 Measures are in place to prevent unauthorised

alterations to or interference with plant equipment.

Model Work Health & Safety Regs 2010 r. 5.1.24

C Plant equipment is only accessible to

authorised personnel.

10.6 A permit to work system is in place to avoid

inadvertent energising of plant that has been

isolated but not physically disconnected from the

electrical supply.

C Included as a requirement of the

Permits to Work Procedure in Savills’

OHS&E Contractor Induction Manual.

10.7 Plant equipment that is not in use is left in a state that

does not create a health or safety risk.

Model Work Health & Safety Regs 2010 r. 5.1.26

N/A There are no disused items of plant on

site.

10.8 Relevant records (e.g. commissioning, inspections,

maintenance, alterations, decommissioning and

dismantling) for registrable items of plant are kept on

site that cover the lifetime of the plant as a minimum.

Model Work Health & Safety Regs 2010 r. 5.1.27

C All associated records relating to

registrable items of plant are kept in

the Facility Manager’s Office.

10.9 Suitable guarding or a physical barrier is in place to

protect against hazards (e.g. moving parts, contact

with extreme temperatures, electrocution), whilst still

allowing maintenance on the associated plant

equipment to be safely/readily performed where

necessary.

Model Work Health & Safety Regs 2010 r. 5.1.29 &

5.1.30

C

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 27 of 43

Plant & Certification of Operators (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

10.10 Operator-protective devices are provided,

maintained and used to reduce the risks of powered

mobile plant overturning, objects falling on the

operator or the operator being ejected from the

plant.

Model Work Health & Safety Regs 2010 r. 5.1.34 &

5.1.35

N/A There is no powered mobile plant on site.

10.11 Warning devices are provided, maintained and used

to reduce the risks of powered mobile colliding with

pedestrians.

Model Work Health & Safety Regs 2010 r. 5.1.35

N/A

10.12 Measures are in place to suitably control the risk of

powered mobile plant colliding with pedestrians or

other powered mobile plant.

N/A

10.13 Suitable working platforms or equivalent

arrangements are provided to protect maintenance

personnel from the risk of a fall from height or being

struck by falling objects.

Model Work Health & Safety Regs 2010 r. 5.1.41

PC There is a potential fall hazard

associated the air-handling units in the

Level 16 Plant Room and these

collective hazards should be duly

rectified.

10.14 Suitable access barriers are provided to minimise the

risk of an unauthorised person falling down a lift well.

Model Work Health & Safety Regs 2010 r. 5.1.41

C Undertaken by Thyssen Krupp as part

of a scheduled maintenance

program.

10.15 A safe means of entry to/exit from the base of the lift

well is provided.

Model Work Health & Safety Regs 2010 r. 5.1.41

C

10.16 The safe working load specified in the design of the

lift is prominently displayed in the lift.

Model Work Health & Safety Regs 2010 r. 5.1.41

AS 1735.2: 2001 s. 23.22

C

10.17 Each lift car shall be provided with a communication

facility and an audible alarm.

AS 1735.2: 2001 s. 32.4

C

10.18 Where buildings have more than one lift, every lift

shall be consecutively and clearly numbered.

AS 1735.2: 2001 s. 32.5

C

10.19 Periodic inspection/maintenance of lifts is carried out

to the manufacturer’s recommendations, but in no

case at intervals of more than one year.

AS 1735.2: 2001 Appendix E

C Undertaken by Thyssen Krupp, with

inspections performed fortnightly and

services conducted monthly.

10.20 Pressure equipment is installed, tested,

commissioned, operated and maintained so as to

eliminate risks to health and safety arising from its use.

Model Work Health & Safety Regs 2010 r. 5.1.43

C

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 28 of 43

Plant & Certification of Operators (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

10.21 Pressure equipment has been designed for ease of

maintenance/inspection and fitted with suitable

safety protection devices (e.g. pressure-relief valves).

AS 1200 Appendix J3

C

10.22 Air receivers are inspected externally/internally every

2/4 years respectively.

TBC Please confirm

10.23 Pressure relief valves are examined and tested every

4 years.

TBC Please confirm

10.24 Items of plant requiring registration have been

registered, including boilers (Hazard Level A, B or C),

pressure vessels (Hazard Level A, B or C), lifts and

building maintenance units.

Model Work Health & Safety Regs 2010 r. 5.2.7

C The cooling towers, lifts and air

receiver are registered with WorkSafe

Victoria.

10.25 Registration is evident on or near the plant.

NOHSC:1010(1994) clause 72(ii) National Standard for

Plant

C Registration certificates are displayed

in the lift motor room and on the air

compressor.

10.26 A formal notice has been suitably provided each

year to the local regulator stating that registrable

items of plant have been maintained in a safe

condition and are safe to operate.

Model Work Health & Safety Regs 2010 r. 5.2.37

N/A

10.27 Plant is inspected and maintained according to the

recommendations of the designer and manufacturer

to ensure safe/effective operation.

C A programmed maintenance plan is

in place for plant equipment on site,

with NAMS servicing the air receiver,

boilers, chillers, cooling towers, fans

and pumps; and Thyssen Krupp

servicing the lifts.

10.28 A process is in place to ensure that operators of plant

have appropriate licences and/or certificates of

competence.

NOHSC:1010(1994) clause 31(a) National Standard

for Plant

C Included as a requirement of Savills’

OHS&E Contractor Induction Manual.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 29 of 43

11. Working at Height

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

11.1 At-risk employees are provided with information,

instruction and training regarding the associated

hazards and control processes.

Model Work Health and Safety Act 2010, Section 19 &

20

C No employees (other than the Facility

Manager) are required to access the

roof, with the Facility Manager and all

relevant contractors required to have

received associated training as part of

Savills policies/procedures.

11.2 All fall hazards at the site have been identified.

Model Work Health & Safety Regs 2010 r. 4.4.2

PC There is no evidence of a formal

Working at Height Survey having been

completed. In addition to window-

cleaning activities, other potential fall

hazards include unprotected areas

associated with the air-handling units

in the Level 16 Plant Room (refer Photo

11.2b). Measures to address these

potential fall hazards should be

promptly instigated.

In the interim, access to these areas

should be tightly controlled and the

Working on Roofs Permit (refer

Annexure L in Savills’ OH&S Contractor

Induction Guidelines) utilised for

contractors requiring access to roof

areas.

11.3 Risk assessments have been completed and are

maintained on site for each task involved in working

at heights.

NC There is no evidence of risk

assessments having been completed

for tasks involved in working at heights

on site.

Ensure risk assessments are prepared

for each task involved in working at

heights.

11.4 The risk of a fall is controlled via a hierarchy of

controls, preferentially via a passive fall-prevention

device, work-positioning system, a fall-arrest system,

a ladder or a documented administrative control

(e.g. safe work method statement).

Model Work Health & Safety Regs 2010 r. 4.4.3

C A fixed ladder is provided for access

to the rooftop, with all serviceable

items of plant positioned well-within

the edge of the roof (which is

protected by a 1-metre parapet wall).

Column-fixing points (that are subject

to annual re-certification) are

provided for window-cleaning

activities.

11.5 Measures to control the risk of a fall or falling object

are suitable, set up correctly and maintained in

sound working order.

Model Work Health & Safety Regs 2010 r. 4.4.5 & 4.4.8

C

11.6 Emergency procedures are established to enable

the safe/timely rescue to a person who requires

emergency assistance associated with a fall.

Model Work Health & Safety Regs 2010 r. 4.4.6

C The Facility Manager is to ensure the

safe / timely rescue and provision of

first aid to a person who has fallen is

provided on all applicable JSAs.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 30 of 43

Working at Height (continued)

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

11.7 Measures to control the risk of a fall or falling object

are reviewed / revised as necessary.

Model Work Health & Safety Regs 2010 r. 4.4.7 & 4.4.8

C

11.8 Where a ladder is used, it must be fit for the purpose

and set up in a correct manner.

AS 1657:1992 s. 5

C

11.9 Where access is required through a horizontal

opening, handrails / handgrips above the level of the

opening are provided and guard-railing fitted to

protect against exposed edges of access openings /

landings.

AS 1657:1992 s. 5

N/A There is no access required through a

horizontal opening.

11.10 An appropriate ladder cage or a suitable protective

device is fitted where a person could fall from a

ladder more than 6.0 m.

AS 1657:1992 s. 5

C

11.11 Anchor points and static lines (where fitted) are

regularly tested (i.e. minimum 12-monthly).

N/A Anchor points or static lines have not

been fitted.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 31 of 43

12. Contractor Management

Risk Element

L = Low Risk Level, M = Medium Risk Level, H = High Risk Level, N/A = Not Applicable

Ref Finding/Observation Risk

Level

Accept

-able Comments

12.1 OH&S requirements are included in tender and

contractor documents.

Model Work Health and Safety Act 2010, Section

19 & 20

M Yes

OH&S requirements are included in

contractor documents issued by

Savills.

12.2 Contractors provide written job safety analysis,

risk assessments or safe work procedures for

proposed works prior to commencing work.

Model Work Health and Safety Act 2010, Section

19 & 20

H Yes

Copies of JSAs or risk assessments are

obtained prior to commencement of

any works.

12.3 Contractors receive site-specific induction

training.

Model Work Health and Safety Act 2010, Section

19 & 20

H Yes

The ‘Rapid Induct’ system is utilised by

all base-building contractors, with site-

specific induction training for all

contractors provided by the Facility

Manager.

12.4 Contractors are given a site contact person and

that person meets with the contractor prior to

starting work to review safe work practices.

Model Work Health and Safety Act 2010, Section

19 & 20

H Yes

The Facility Manager is the primary

contact person on site and is

responsible for the coordination of all

works performed; part of this is to

ensure safe work practices are

complied with.

12.5 Contractor OH&S performance is monitored

and unsatisfactory performance is followed up.

Model Work Health and Safety Act 2010, Section

19 & 20

H Yes

Contractor OH&S performance is

managed by the Facility Manager.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013 Page 32 of 43

13. Emergency Management

Compliance Element

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

13.1 A documented Emergency Management Plan (EMP)

is provided and is reviewed at least once every 5

years.

AS3745 s. 3

Model Work Health & Safety Regs 2010 r. 3.4.1

C Emergency Management Procedures

were prepared by La Nouvelle

Musique (formally ADF Training) in July

2009 and up-dated in June 2013.

Stage 2 training was conducted

during November 2013.

13.2 Appropriate diagrams that provide emergency and

evacuation information are displayed throughout the

facility.

AS3745 s. 3.5

Model Work Health & Safety Regs 2010 r. 3.4.3

PC Emergency evacuation signs

prepared by La Nouvelle Musique are

displayed throughout the tenanted

areas of the building, but not the car

park and plant room areas and this

should be duly rectified.

13.3 The EMP is accessible to all building occupants, with

sufficient information from the emergency response

procedures specifically distributed to all occupants.

AS3745 s. 3.6

Model Work Health & Safety Regs 2010 r. 3.4.3

C The EMP is made available to all

tenants.

13.4 An up-to-date register of all Emergency Control

Organisation members is kept readily available and

occupants are made aware of the identity of their

wardens.

AS3745 s. 5

Model Work Health & Safety Regs 2010 r. 3.4.1

C A list of the names/roles of emergency

responders are provided to all building

occupants (e.g. via distribution of

minutes of training meetings to each

tenancy).

13.5 Tenants, contractors and employees receive

information and training in emergency procedures

appropriate to the allocated emergency response

responsibilities

AS3745 s. 6

Model Work Health & Safety Regs 2010 r. 3.4.3

C Training is conducted on a six-monthly

basis by La Nouvelle Musique.

13.6 A program is in place for annual testing /

implementation of the emergency response

exercises, including full-scale building evacuations.

AS3745 s. 7.3

Model Work Health & Safety Regs 2010 r. 3.4.2

C Full-scale building evacuation

exercises are conducted on a yearly

basis La Nouvelle Musique, with the

latest building evacuation conducted

in November 2013.

13.7 Competent persons have assessed the suitability,

location and accessibility of emergency equipment.

C

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 33 of 43

14. Workplace Environment

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

14.1 Noise level measurements have been taken in those

areas identified as likely to be in excess of the noise

exposure standard.

NC Undertake noise level measurements

in noisy areas such as the Chiller Plant

Room, Fire Hydrant Pump Room and

the Fire Sprinkler Pump Room.

14.2 Exposure to workplace noise (above the noise

exposure standard) is controlled via a hierarchy of

controls, preferentially via source elimination,

exposure reduction, administrative controls or

hearing protection.

Model Work Health & Safety Regs 2010 r. 4.1.2

C Provide suitable hearing protection for

Savills employees in the Chiller Plant

Room, Fire Hydrant Pump Room and

the Fire Sprinkler Pump Room.

Contractors provide their own PPE.

14.3 Measures implemented to control workplace noise

have been reviewed / revised if conditions have

changed or there are concerns as to the

effectiveness of such controls.

Model Work Health & Safety Regs 2010 r. 4.1.3

N/A

14.4 Signs, labelling of plant or other appropriate means

are provided that identify when and where hearing

protectors are to be worn.

NC Affix hearing protection signs to the

doors leading to the Chiller Plant

Room (refer Photo 14.4), Fire Hydrant

Pump Room and the Fire Sprinkler

Pump Room.

14.5 Where hearing protectors are provided, audiometric

testing of relevant employees is performed at least

every 2 years.

N/A All contractors are responsible for

providing audiometric testing of their

employees that are exposed to

workplace noise.

14.6 Sufficient clear space for work areas and access

ways is provided to ensure employees can move

about freely without strain or injury.

Model Work Health & Safety Regs 2010 r. 3.1.1

C

14.7 Floors and other surfaces in the workplace are

designed, installed and maintained to allow work to

be carried out without risk to health and safety.

Model Work Health & Safety Regs 2010 r. 3.1.1

C

14.8 Lighting is provided that is appropriate for the various

types of tasks/activities being performed throughout

the building.

Model Work Health & Safety Regs 2010 r. 3.1.1

C

14.9 Light fittings are observed to be in good condition

and lights are operating correctly (i.e. no flickering)

Model Work Health & Safety Regs 2010 r. 3.1.1

C

14.10 Adequate ventilation rates, air quality levels and a

comfortable temperature range are maintained

throughout the building.

Model Work Health & Safety Regs 2010 r. 3.1.1

C

14.11 There is no cause to indicate concerns regarding the

quality of drinking water.

AZECC (Australian Drinking Water Guidelines) 2004,

NHMRC

C

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 34 of 43

15. Traffic Hazards

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

15.1 Appropriate speed humps have been installed in

aisles to control excessive speeding where the aisle

length is >100 metres or where there are >40 parking

spaces provided on either side.

AS/NZS 2890.1: 2004 s. 2.3.3, 4.9

N/A Not considered necessary given the

size of the car park.

15.2 Parking spaces/aisles are adequately sized and

clearly marked.

AS/NZS 2890.1: 2004 s. 2.4, 4.4

C

15.3 Wheel-stops or barriers are fitted to prevent vehicles

from running over the edge of a raised platform or

deck of a multi-storey car park.

AS/NZS 2890.1: 2004 s. 2.4.5

N/A

15.4 Protection is provided for pedestrians in the form of

marked crossing, kerbing, footpaths, barriers/guard

rails and signage.

AS/NZS 2890.1: 2004 s. 4

N/A Not considered necessary given the

size of the car park.

15.5 Road marking lines, directional arrows and signs are

clearly visible and unambiguous for drivers.

AS/NZS 2890.1: 2004 s. 4

N/A Not considered necessary given the

size of the car park.

15.6 Speed limits are clearly sign posted.

AS/NZS 2890.1: 2004 s. 4.3.4

N/A Not considered necessary given the

size of the car park.

15.7 Parking areas, circulation areas and pedestrian

pathways are adequately lit.

AS/NZS 2890.1: 2004 s. 4.7

C

15.8 Parking spaces for special loading/unloading

purposes (e.g. emergency services vehicles, people

with disabilities) are provided and clearly marked.

AS/NZS 2890.1: 2004 s. 4.7

BCA s. D3.5

N/A

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 35 of 43

16. Environmental Hazards

Risk Element

L = Low Risk Level, M = Medium Risk Level, H = High Risk Level, N/A = Not Applicable

Ref Finding/Observation Risk

Level

Accept

-able Comments

16.1 1 Previous environmental reports have been

provided by the property owner or relevant

environmental authority.

N/A N/A No previous reports available.

16.2 1 There is no soil or groundwater contamination

identified in previous reports.

N/A N/A No previous reports available.

16.3 1 There are no limitations to the current land use

based on above contamination if present.

National Environmental Protection Measure

1999 Schedule 7(a)

N/A N/A No previous reports available.

16.4 1 There are no restrictions placed on contact

with soils and/or groundwaters if

contamination is present.

NIOSH Exposure Standards

National Environmental Protection Measure

1999 Schedule 7(a)

N/A N/A No previous reports available.

16.5 1 There are no significant OH&S risks based on

potential contamination.

NIOSH Exposure Standards

National Environmental Protection Measure

1999 Schedule 7(a

M-H Yes

16.6 1 There are no environmental clean-up notices

or equivalent issued by the relevant

environmental authority.

M-H Yes

16.7 There are no potentially contaminating land

uses or tenants associated with the site.

M-H Yes There is a grease trap associated with

the Ground Level Café, although a

maintenance regime is in place to

reduce the potential for

contamination from this trap.

16.8 There are no nearby land users with potential

to cause significant contamination (e.g.

petrochemical plant).

H Yes

16.9 There are no licensed discharges from the site. M-H Yes

16.10 There are no hazardous wastes generated or

stored on the site.

M-H Yes

16.11 There is no evidence (e.g. fuel spills, odours) to

indicate significant environmental risks or

contamination is present that would require

further investigation.

AS4482.1-2005

AS4482.2-1999

National Environmental Protection Measure

1999 Schedule 7(a)

M-H Yes

16.12 There is no cause to indicate concerns

regarding noise emissions from any operations

on the site.

L-M Yes

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 36 of 43

17. Electrical Safety

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

17.1 At-risk employees are provided with information,

instruction and training regarding the associated

hazards and control processes.

Model Work Health and Safety Act 2010, Section 19

& 20

C No employees are required to work on

electrical equipment, with all relevant

contractors required to have received

associated training as part of Savills

policies/procedures.

17.2 Control measures are in place to minimise the risks

associated with electrical hazards.

Model Work Health & Safety Regs 2010 r. 4.7.7

C RCD’s are fitted to most base-building

electrical circuits; only licensed /

inducted personnel are permitted to

conduct electrical works; and routine

inspection / testing is undertaken on

electrical equipment.

17.3 Measures implemented to control risks associated

with electrical hazards have been reviewed /

revised if conditions have changed or there are

concerns as to the effectiveness of such controls.

Model Work Health & Safety Regs 2010 r. 4.7.8

N/A

17.4 Routine inspection / testing of electrical equipment

(including residual current devices [RCDs]) is

performed by a competent person undertaken to

detect obvious damage, wear or other conditions

which might render it unsafe.

Model Work Health & Safety Regs 2010 r. 4.7.9 &

4.7.22

AS/NZS 3760:2010, Appendix A1(b) & Table 4

C Annual inspection / testing of

electrical equipment and RCD’s is

performed by Hisbos, with this

equipment last tested on 24/12/2012.

17.5 Tags fitted to electrical equipment are durable,

legible, non-reusable, non-metallic and include the

name of the person / company who performed

the test, the test/inspection date, the nature &

outcome of the test, a re-test date and a

reference to AS/NZS 3760.

Model Work Health & Safety Regs 2010 r. 4.7.9

AS/NZS 3760:2010, s. 2.4.2.1

C

17.6 Any untested electrical equipment is not used in

the workplace.

Model Work Health & Safety Regs 2010 r. 4.7.10

C

17.7 Any electrical equipment deemed to be unsafe is

disconnected and removed from service until it is

repaired or tested and found to be safe.

Model Work Health & Safety Regs 2010 r. 4.7.11

C Hisbos have been requested to

provide a “repair register” to record

all faulty equipment (that shows

details of services or corrective

actions)

17.8 Measures are in place to ensure that electrical

equipment that has been de-energised to allow

electrical work to be carried out on it cannot be

inadvertently re energised while the work is being

carried out.

Model Work Health & Safety Regs 2010 r. 4.7.12

C Included as a requirement of the

Isolation Procedure in Savills’ OHS&E

Contractor Induction Manual.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 37 of 43

Electrical Safety (continued)

C = Compliant, SC = Substantially Compliant, PC = Partially Compliant, NC = Not Compliant,

N/A = Not Applicable

Ref Finding/Observation Compliance Comments

17.9 Before work is undertaken on energised electrical

equipment, a risk assessment is conducted by a

competent person.

Model Work Health & Safety Regs 2010 r. 4.7.15

C

17.10 Any work undertaken on energised electrical

equipment is conducted by a competent person in

accordance with a safe work method statement

prepared for the work.

Model Work Health & Safety Regs 2010 r. 4.7.18

C

17.11 Each electrical circuit is protected by a RCD that is

incorporated before/part of each socket outlet.

Model Work Health & Safety Regs 2010 r. 4.7.21

SC Most base-building electrical circuits

are protected by RCD’s.

Ensure RCDs are fitted to all remaining

electrical circuits.

17.12 On-site documentation includes a register of all

equipment; a record of formal inspection and tests;

a 'repair' register; and a record of all faulty

equipment showing details of services or corrective

actions.

AS/NZS 3760:2010, s. 2.5.1

SC A register of all electrical appliances

that are subject to formal inspection

and regular testing / tagging has been

prepared. A 'repair' register and a

record of all faulty equipment (that

shows details of services or corrective

actions), however, has not been

prepared and this should be duly

rectified.

17.13 A thermographic survey of electrical switchboards

has been conducted.

C Hotspot Thermography conducted

thermographic surveys of all electrical

switchboards in March 2013.

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 38 of 43

18. Photos

Photo Ref. 2.4: Asbestos gaskets associated

with calorifier that are not suitably-labelled

Photo Ref. 3.15: No chemical bunding in

Basement Cleaners’ Room

Photo Ref. 9.2: Level 16 Water Storage Tanks

posing confined space hazards

Photo Ref. 11.2: Unprotected areas associated

with air handling plant in Level 16 Plant Room

Photo Ref. 14.4: Lack of hearing protection

signage fitted to the door leading to the Chiller

Plant Room and Fire Pump Room

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013Page 39 of 43

Left Blank

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013

Page 40 of 43

Appendix A: Implementation Plan for Control Measures

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013

Page 41 of 43

Implementation Plan for Suggested Control Measures

Ref.

No. Additional Control Measure(s)

Suggested

Time-frame

Suggested

Person(s)

Implementation

Date Comments

2.4 Where practicable, arrange for labels to be fitted to

asbestos-containing materials. Completed

Facility

Manager Completed

2.6 Arrange for a review / update of the Asbestos Register. By August

2014

Facility

Manager

LRM Global to

provide proposal

2.7

Advise all tenants regarding the location of the

Asbestos Register and the Asbestos Management Plan,

within which the hazards posed by asbestos-containing

materials located within their tenancies and the

associated controls are specifically documented.

Contractors must be similarly advised as part of the site

specific inductions.

By March 2014 Facility

Manager Completed

2.13 Ensure the Asbestos Register is reviewed & updated

before future demolition / refurbishment is carried out. On-going

Facility

Manager

3.4

Ensure a Dangerous Goods / Hazardous Substances

Register is prepared and, when completed, kept up-to-

date on site in the Facility Manager’s Office.

By December

2013

Facility

Manager Completed

3.9

Arrange for a site-specific risk assessment to be

developed that focuses on the use, handling or storing

of hazardous chemicals.

By March 2014 Facility

Manager

3.15 Ensure all chemicals are positioned within suitable

containment bunds.

By February

2014

Facility

Manager

3.19 Provide eyewash facilities in the Basement Cleaners’

Room and cooling tower areas. By March 2014

Facility

Manager

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013

Page 42 of 43

Ref.

No. Additional Control Measure(s)

Suggested

Time-frame

Suggested

Person(s)

Implementation

Date Comments

3.23

Formally request the cleaning contractor provides

relevant PPE, along with associated training, to all on-

site employees.

By March

2014

Facility

Manager

Cleaning Contract

will be going out

to tender in 2014

9.2

Arrange for a Confined Spaces Audit to be undertaken

with input from key contractors (e.g. plumbing and

mechanical service providers). Once conducted, a site

plan of all identified confined spaces should be

prepared and made available to all relevant

contractors.

By March 2014 Facility

Manager

9.3 Suitably-label all identified confined spaces. By March 2014 Facility

Manager

10.2 Arrange for site-specific plant risk assessments to be

prepared for the boilers and air compressor. By March 2014

Facility

Manager

11.2

Control access to unprotected sections associated with

the Level 16 air handling units and ensure the Working

on Roofs Permit (refer Annexure L in Savills’ OH&S

Contractor Induction Guidelines) is used by contractors

requiring access to roof areas.

On-going Facility

Manager

11.3 Ensure risk assessments are prepared for each task

involved in working at heights. On-going

Facility

Manager

Ref.

No. Additional Control Measure(s)

Suggested

Time-frame

Suggested

Person(s)

Implementation

Date Comments

13.2

Arrange for emergency evacuation signs to be

prepared / displayed in the car park and plant room

areas.

By March 2014 Facility

Manager

459 Little Collins Street, Melbourne, Hazard Identification & Compliance Assessment – Revised August 2013

Page 43 of 43

14.1

Arrange for noise level measurements to be undertaken

in noisy areas, such as the Chiller Plant Room, Fire

Hydrant Pump Room and the Fire Sprinkler Pump Room.

By February

2014

Facility

Manager

14.4

Affix hearing protection signs to the doors leading to

the Chiller Plant Room, Fire Hydrant Pump Room and

the Fire Sprinkler Pump Room.

By Mach 2014 Facility

Manager

17.11 Ensure RCDs are fitted to all remaining electrical circuits. By August

2014

Facility

Manager

17.12

Arrange for a repair register and a record of all faulty

equipment (that shows details of services or corrective

actions) to be prepared.

By March 2014 Facility

Manager