1 / 86100%
1
A HIGH-PERFORMANCE FAULT LOCATION ALGORITHM FOR
SHIPBOARD POWER SYSTEMS
INTRODUCTION
1.1 History of Ship Power Systems (SPS)
The ship's electric power system was first installed on the USS Trenton in 1883, marking the
beginning of the use of electricity on naval ships. The system is designed to supply power to
247 lights, using direct current (DC) at a voltage of 110 volts.
Figure 1.1 USS Trenton
The history of the development of electric power systems on ships shows a significant
evolution along with increasingly complex operational and technological needs. In the beginning,
until 1914–1917, the ship's electric power system mainly used direct current (DC) to run the
motors and provide lighting. However, during World War I, alternating current (AC)-based
power systems with a voltage of 230 volts and a frequency of 60 Hz were introduced to naval
ships, which was a major step in the modernization of the ship's electrical system.
Another major change occurred after World War II, when the ship's electrical system
2
continued to undergo significant improvements. One of the key changes is the adoption of a
4,160-volt high-voltage power system to accommodate the greater power needs of modern ships.
In addition, protective devices are being introduced to monitor important parameters in the
electric power system. The main function of these devices is to determine the optimal system
configuration in order to minimize damage to components, improve the continuity of the power
supply, and maintain the reliability of the system during operation.
In the early days, the protection of the electric power system was carried out using fuses.
However, over time, circuit breakers began to be added to improve the protection capabilities
and flexibility of the system. The end of the 20th century marked an important milestone with the
introduction of electronic solid-state-based overcurrent protective devices. The U.S. Navy
installed the device on a 4,160-volt power system on the Nimitz-class aircraft carriers, marking
the transition to a more advanced and reliable modern power system.
These innovations in electrical systems not only improve operational efficiency but also
provide better surveillance and protection capabilities to meet the challenges of harsh maritime
environments and complex mission demands.
1.2 Structure of SPS System
Power in a Ship Power System (SPS) is generated by several generators that are typically
placed in a ring configuration [1]-[7]. Typically, there are two types of loads in SPS: vital loads
and non-vital loads [1]-[5], [8], [9]. Navigation, communications, operations and weapons are
examples of vital loads while lighting and air-conditioning systems are part of non-vital loads
[1]-[4], [6], [8], [11]. SPS aims to supply energy for both types of loads. In fault conditions, the
system cannot supply electrical energy to the load. SPS requires a comprehensive protection
system to detect the exact location of faults and use several alternative paths to supply energy to
3
undamaged loads]. It is important to note that the fault location mechanism does not have to be
as fast as the protective mechanism that disconnects in milliseconds. In contrast, fault location
algorithms capture fault data quickly and try to find faults in a short enough time to direct
electrical power to vital loads. There are three main protection schemes in power systems:
overcurrent, distance, and differential
Ship power systems use a three-phase generator that is in a ring configuration and
generally operates at 60 Hz to generate AC voltage for the system. The generator is in a ring
configuration to have an alternative path for the vital load of the different generators. He allows
the system to supply power to a vital load when the normal path of the main generator is
damaged or destroyed
Figure 1.2 shows a single line diagram of the SPS 11-bus . The system consists of four
three-phase main generators in a ring configuration that operate at 60 Hz. In this system, the vital
load has an alternative path in addition to the normal path of another generator to receive energy
from the source in a disturbance situation. The vital load uses Automatic Bus Transfer (ABT) or
Manual Bus Transfer (MBT) to select the wrong path to receive energy from the generator [1]-
[6], [8]. Under normal conditions the ABT/MBT connects the normal path to the load. When an
error occurs, the ABT/MBT disconnects the normal path and connects the alternate path.
4
Figure 1.2 11-Bus SPS
1.3 Distance Protection and Its Drawbacks
Cable lengths in SPS are typically shorter (about 10–200 feet long [11]) than in large
distribution networks and thus small cable impedances (about 0.04/1000 feet
5
[11].) Using proximity protection in short-duration power systems is impractical because the
impedance of the cables is too low to be detected with a small error. An improved spacing
scheme can be used to detect faults in short-length cables. The Active Impedance Estimation
(AIE) error location method [13] uses a high-frequency voltage on a bus in an electrical system
and measures the injected current followed by calculating the impedance at that frequency.
Higher frequencies add to the resolution of the cable impedance and make fault location easier in
the ship's power system. In the AIE method when the system is exposed to a fault, a short-
duration voltage will be used to find the visible system impedance of the injection bus and find
the fault. This method is only applied to radial distribution systems. This method uses the
measured impedance value to find errors [13], [15]. Although the available AIEs can distinguish
between distant and close-up faults, they can be used primarily in lateral branches where the
Thevenin equivalent impedance is equal to the cable impedance and proportional to the fault
distance. Thus, in interconnected systems, such as ship power systems with ring topology,
available active impedance estimation methods have topological limitations.
1.4 Overcurrent Protection and Its Drawbacks
Another conventional method of detection and location of faults is the overcurrent
scheme. The main power of the SPS is produced by several generators. Having multiple power
supplies leads to complex overcurrent protection in the system that requires a time delay to avoid
over-tripping [7]. Due to the short length of the cables, SPS is considered a highly coupled
electrical system; That is, if a fault occurs at a single point of the system and rapid detection and
isolation is not provided by the protection system, the fault will spread throughout the system in
a short time and can lead to catastrophic consequences [2]. So, just use
6
Conventional overcurrent protection mechanisms are impractical in ship power systems due to
short wiring, time delay requirements, and multiple supplies, which complicates the scheme [7],
[11]. Overcurrent protection, however, can be used as a safety feature to enhance protection
capabilities in addition to other protection schemes.
1.5 Differential Protection and Its Drawbacks
Differential protection schemes, on the other hand, work well in systems with short wires.
Differential relays compare the inlet current to the protected equipment with the current leaving
the equipment. If these two currents are the same, as shown in figure 1.3(a), there is no error.
However, if these two currents are not the same, as shown in figure 1.3(b), which indicates that
there is a fault in the protected equipment, the relay trips [7], [11]. In this method, each piece of
equipment in the SPS requires a differential relay to find faults effectively. In addition, a
comprehensive communication system between all protected zones and related equipment is
required to cover the entire SPS, precisely. The vulnerability of communication systems to errors
greatly reduces the reliability of the system [9], [13]. In addition, this approach is expensive
because it requires many differential relays and a comprehensive communication infrastructure.
Figure 1.3(a) Differential Error Detection (No Error)
7
Figure 1.3(b) Differential Error Detection (With Error)
1.6 Proposed Methods
There is a need to develop a more efficient fault location scheme to find all faults that
occur in the ship's power system at a low cost. This thesis introduces an economical and reliable
fault location scheme for SPS. This method requires the application of short-duration voltages
with high frequencies under fault conditions and observation of changes in the voltage and
current of the system bus due to faults. Changes in voltage and current at the measurement point
are indicators of location and magnitude of error. Different errors may have the same effect on
the voltage and current at the measurement point. In this case, multi-estimation occurs [14]. As
such, the system requires multiple voltage and/or measurement point applications to have a
unique data set for each fault. The goal is to minimize the number of applications and voltage
measurements and to find its optimal place in the system to uniquely identify each fault. In this
paper, a three-phase symmetrical fault is analyzed; However, the proposed method can be
generalized to other types of errors.
8
CHAPTER 2 METHODOLOGY
2.1 Introduction
In this thesis, observations are made on the effect of any error on the voltage and/or
current of a particular set of measurements when a high-frequency voltage is applied to the
system on an injection bus. Relevant terms and definitions are given:
Injection bus: For convenience, here the term injection bus is called the bus where a high-frequency
voltage is applied. There may be several injection buses with different frequencies in SPS.
Measurement bus: The measurement bus is used to handle the bus where the voltage and/or current
is measured. It is important to mention that an injection bus may or may not be the same as a
measurement bus. In addition, more than one measurement bus can be used. In this sense, the
proposed approach generalizes the conventional method of error location of active impedance
estimation [1], [2].
Measurement set: The measurement set refers to the voltage and/or current measurement set on all
buses with specified injection, frequency, and Rfault buses . Measurement sets help compare
measurement results to find unique results and the best combination of injection and
measurement bus for fault locations.
Each error may have a different effect on the voltage or current of a particular
measurement bus. The goal of this paper is to find the optimal place for injection and the
measurement bus to have a unique set of measurements for each error. The unique measurement
is then referred to the specific fault to detect the exact location of the fault.
9
Since SPS operates at 60 Hz, voltage applications and voltage/current measurements
must be applied at higher frequencies to avoid interference with the protection system. That is,
superpositions can be used for analysis because the fault location algorithm works separately
from the normal operation of the system. The fault location algorithm does not look at the
voltage generated by the main generator at 60 Hz but can still detect the error.
2.2 Proposed Error Location Algorithm
Suppose I is the bus number that has a voltage application, M is the bus number that has a
measurement, and F is the bus number that is faulty. Then, the ordered triple (I,M,F) represents
the fault detection observation. In this case, V→I,M,F represents the voltage vector of the
measurement bus when the injection is on the I bus, the measurement on the M bus, and the error
on the F bus. If F = 0 it indicates the initial value when there are no errors in the system. A
similar definition is used for II,M,F current measurements. The goal is to observe the values of
VI,M,F and I→I,M,F for all faults, given the measurement and injection bus, and for comparing
value with normal values of current and voltage to see if the fault can be detected. The algorithm
starts from I=1, M=1 and applies a specific error to each bus and observes the voltage and
current changes on the measurement bus. For this purpose, the algorithm calculates ∆VI,M,F if
I M, and I→I,M,F if I = M; i.e.,
VI,M,F = VI,M,F VI,M,0
II,M,F = I→I,M,F I→I,M,0.
Figures 2.1 and 2.2 show the magnitude and phase angle of V I,M,F for the simulation
system described in figure 1.2 when I = 10, M = 9, Rfault = 1e−3, and f = 1000Hz for
10
different F values (1 F 11.) The error sequence with an impedance of Rfault = 1e−3
is applied to different system nodes as shown in the figure and the effect is observed. Figures 2.3
and 2.4 show the magnitude and angle of the II,M,F phase for the simulated system when
I = 2, M = 2, Rfault = 1e−3, and f = 1000Hz for different F values (1 ≤ F ≤ 11.) Note
that if I = M, the algorithm considers the current value whereas for I M considers the
voltage value.
Figure 2.1 The magnitude of V→I,M,F when I = 10, M = 9, Rfault = 1e−3, and f =
1000Hz for different F values
11
Figure 2.2 Phase angle V I,M,F when I = 10, M = 9, Rfault = 1e−3, and f = 1000Hz
for different F values
Figure 2.3 The magnitude of I→I,M,F when I = 2, M = 2, Rfault = 1e−3, and f =
1000Hz for different F values
12
Figure 2.4 Phase angle I→I,M,F when I = 2, M = 2, Rfault = 1e−3, and f =
1000Hz for different F values
In a ship's power system if
VI,M,FV→I,
M,0
V→I,
M,F
II,M,FII,
M,0
∆ I → Me
, M, F
||V
Me,
M,0
| = |
Me,M,0
| or |
|
|
II,M,
0
| = | | <
Me,M,0
|
0.001, ∆V→ and ∆I→ are difficult to detect. Table 2.1 shows the simulation results for the
system presented in figure 1.2 when I = 10, M = 9, Rfault = 1e−3, and f = 1000Hz. The
numbers in Table 2.1 are F-values that indicate which buses are damaged. The highlighted
numbers indicate which bus errors cannot be detected with the selected measurement and
injection buses. In other words,
Error cannot be detected when the relative value | V %| = |V
I,M,F |
= |VI,M,FVI,M,0| Lebih
Kecil
I, M, F
|
VI,M,0
|
|VI,M,0|
from 0.001 and/or |
I %| = |∆I→
I,M,F |
=
|
II,M,FII,M,0|
less than 0.001.
I, M, F
|II,M,0|
13
|I→I,M,0|
14
Table 2.1 Detectable and undetectable bus faults when I = 10, M = 9, Rfault = 1e−3, and
f = 1000Hz
Until
#
1 2 3 4 5 6 7 8 9 10 11
Delta
V/I
0.06 0.066 0.02 0.0008 0.069 0.025 0.023 0.064 0.07 0.01 0.0009
The algorithm checks all possible combinations with different values for M, I, and F to
find the optimal bus for injection and measurement that can detect all faults (various fault
impedances.) If one injection and measurement is insufficient to cover the entire system, the
system requires more injection and/or measurement buses to cover all faults. The proposed
approach looks for injection buses and measurements that result in the lowest number of
undetected errors (location and impedance.) Error not detected when
|V
I,M,F
%|
< 0.001,
or
|∆II,M,F%|
< 0.001.
Thus, the algorithm finds the case that has the lowest number of undetected errors
with
|V
I,M,F
%|
< 0.001, or |∆I→I,M,F %| < 0.001. For convenience, if the number
of undetected errors is 0 or 1, an injection measurement set consisting of an injection bus and a
selected measurement is selected. Then, the algorithm will check if these cases cause unique
changes to
|∆V
I,M,F
%|
or
|∆I→I,M,F%|for
different errors. If
|∆V
I,M,F
%|
or
|
∆I→I,M,F%|
having the same results for different errors (i.e., those that differ less than 0.001,) the
system faces multi-estimation. To check this, the algorithm evaluates
V
I , M , F
%
or
II,M,F
% for all fault conditions (location and impedance) to find similar pairs (i.e.,
those that differ less than 0.001,) voltage change vectors ∆V→I,M,F % and the
current change vectors ∆I→I,M,F %, given a set of injections and
15
measurement bus. In the event of similarities, the injection measurement set cannot offer unique
results for different errors. In this case the system observes multi-estimation.
The next step is to iterate on the algorithm for different combinations of injection and
measurement buses along with (and possibly their frequencies) to find the optimal bus for
injection and measurement in order to cover all errors with the minimum number of injection and
measurement buses and to avoid multi-estimation. The proposed algorithm is depicted in the
flowchart figure 2.5.
16
Figure 2.5 Algorithm finds the best injection and measurement placement
17
2.3 Error Location Algorithm Using Channel Current Measurement
So far, current measurement is only considered when the injection bus and the
measurement are the same. When the injection and metering buses are different, multiple lines
can be connected to the metering bus with different currents on each channel. Therefore, one
must determine which line is used for measurement. In this thesis, channel current measurements
are used to find faults based on the difference in measured current in faulty and non-faulty
systems. Using the results from voltage and current measurements helps reduce the number of
measuring equipment for the fault location leading to the lowest number of undetected faults. For
this purpose, one needs to measure the current on all the channels connected to the measurement
bus to see which one has the highest variation for the various faults being considered.
Since each bus connects multiple lines together and each of these lines has a different
flow, it is important to know which line to use for the fault location that results in the lowest
undetected error. Start with the naming of the paths connected to each measurement bus from 1
to n where n is the number of lines connected to the selected measurement bus. Note that for a
bus with two channels, only one current measurement is taken because the line has the same
current when the load current is ignored. This procedure is repeated for all measurement buses
(figure 2.6); that is, all power system buses. In the proposed method, the algorithm measures the
current on all channels connected to the measurement bus for different injection buses and
defective buses, then proceeds to the next measurement bus and repeats the same procedure for
the lines connected to that bus until it covers all the measurement buses (the entire system bus.)
18
Figure 2.6 11-Bus SPS
Suppose I is the number of the bus that has a voltage application (injection bus), B is the
number of the measurement bus, M is the number of lines connected to the measurement bus B,
and F is the number of the defective bus. In this case I→I,B,M,F represents the current vector
measured on the measurement bus B. If F = 0 it indicates a value that is not false; that is, when
there is no error in the system. The purpose is to observe the value of I→I,B,M,F for all errors,
remember the measurement, and to compare its value with the normal value of the current to see
if the error can be detected. The algorithm starts from B=1, I=1, M=1 and applies certain
errors to each
19
and observe the current changes in the measurement bus. For this purpose, the algorithm calculates
I
I,B,M,F
;
That is
II,B,M,F = I→I,B,M,F − I→I,B,M,0.
In a ship's power system, an error cannot be detected when the relative value
of |∆I→
I,B,M,F
%|
which is the same as |∆I→I,B,M,F| = |I→I,B,M,F−I→I,B,M,0|, less than 0.001.
|MeI,B,M,0| |ME→ME,B,M,0|
The algorithm checks all possible combinations with different values for, I, B, M, and F
to find the optimal bus for injection and optimal line current measurement that can observe all
errors (various fault impedances.) If one injection bus and measurement bus are insufficient to
cover the entire system, the system requires more injection and/or current measurement buses
from the measurement bus or even more measurement buses to cover all faults. The proposed
approach seeks a set of injection and measurement buses that results in the lowest number of
undetected errors (location and impedance.) An error is not detected when
|∆I→I,B,M,F %| < 0.001. The algorithm evaluates all injection buses and measurements to
cover the entire system.
Once the algorithm finds the case that has the lowest number of undetected errors with
|
∆I
I,B,M,F
%|
< 0.001, it will check if these cases cause unique changes to
|∆I→I,B,M,F
%|for
different faults with the selected measurement and injection bus. If
|∆I
I,B,M,F
%|
having the same results for different errors (i.e., those that differ less than 0.001,) the system
faces multi-estimation. To check this, the algorithm evaluates
I
I,B,M,F
%
for all fault
conditions (location and impedance) to find similar pairs (i.e., those that differ less than 0.001,)
of current change vectors
20
I
I,B,M,F
%,
given a set of injection and measurement buses. One has to iterate on the algorithm
to
Combinations of different injection and measurement buses (and possibly with different injection
frequencies) to find the optimal bus for injection and measurement in order to cover all errors
with the minimum number of injection and measurement buses and to avoid multi-estimation.
The proposed algorithm is illustrated in the flowchart figure 2.7.
Figure 2.7 Algorithm finds the best injection and measurement placement by Using Current
21
Measurement
22
ARTICLE 3
INJECTION FREQUENCY EFFECT
3.1 Introduction
Using standard error analysis, one can find ∆V and ∆I for the proposed fault location
algorithm based on the Zbus matrix elements. To find the relationship between the
injection frequency and the location of the fault, one needs to trace the effect of the frequency in
the Zbus matrix element. For this purpose one needs to develop a Zbus matrix.
3.2 Background Impedance Matrix
The bus impedance matrix is an important tool for the fault analysis of the power system [1].
There are various ways to find the system impedance matrix. The inversion of the reception
matrix is more suitable for small systems. In the proposed method, the target is to obtain a
mathematical relationship between frequency and impedance; However, inversion makes it too
difficult to keep track of relationships. In addition, for large systems, the inversion of the
admission matrix becomes very time-consuming.
The bus impedance matrix can also be directly found from the structure of the power system
[1]. To build an impedance matrix directly, one starts with a simple 1×1 impedance matrix
between the bus and the reference node and then modifies this simple network by adding the bus
and the next line between the buses one by one.
To understand how to modify the Zbus impedance matrix, consider the notations h, i, j, and k
for the existing bus and m and n for the new bus, respectively, as shown in Cases 1 to 4 depicted
in figures 3.1 to 3.4 below. There are four different cases that can be utilized in modifying
Zbus.
Case 1. Added a Zbus branch between the reference node and the new bus m
bu
s
23
un
til
To update Zorig's original impedance matrix when there is an impedance (Z)
bus 𝑏
added between the reference node (0) and the new bus (m), one needs to add rows and columns
to Zorig with the values in equation (3.1) [1].
Ne
w
Bus
(3.1)
Figure 3.1 Case 1. Added Zb branch between the reference node and the new bus m
Case 2. Added Zb branch between the existing k bus and the new m bus
To update the original impedance matrix Zorig when there is a new bus (m)
connected via Eg to the existing bus (k) equation (3.2) can be used [1].
Ne
w
Bus
(3.2)
Z orig
0
bus
0
0
0 
Zb
Z
k1
Z1k
From
orig
W
it
h
2k
until
Zk 2ZKnZkk
Eg
W
it
h
Nk
W
it
W
it
24
Figure 3.2 Case 2. Added Zb branch between the existing k bus and the new m bus
Case 3. Adding a Zb branch between existing k buses to a reference node
In this case there is an impedance of Zb between bus k (existing bus) and bus (0)
(reference node). To get Znew , one needs to add a temporary bus (m) connected via
Zb to the k bus (figure 3.3), then one needs to repeat case 2 and then delete the m row and m
column with Kron reduction. To use the Kron reduction to find every elemental equation (3.3) is
used [1].
Zhi
(new)
=
Zhi
zh
(N+1)Z(N+1)
i
Zkk+Zb
(3.3)
Figure 2.3 Case 3. Adding a Zb branch between existing k buses to a reference node
bu
s
25
bu
s
Case 4. Add Zb branch between existing j bus to existing k bus
To get the Znew original impedance matrix for this case one needs to form
The matrix uses equation (3.4) [1].
New Z
Ori
g
Bus
kol.j kol.k
(3.4)
bus baris. j
baris.k
Zth, jk Zb 
Figure 3.4 Case 4. Add Zb branch between existing j bus to existing k bus
where Zth,jk = Zjj + Zkk − 2Zjk and then delete the n rows and n columns by the Kroon
reduction [1].
By knowing how to modify Zbus using these four cases, one can find Zbus from the
system. The Zbus impedance matrix can be obtained starting from a single bus connected
through a branch impedance to a reference node and then extending this simple network, based
on the system topology and the four cases mentioned above, to modify the Zbus and find a
large system impedance matrix. This approach was used in chapter 3.3 to find the relationship
between the frequency of injection and the location of the error.
Z
26
3.3 Effect of Injection Frequency on Fault Location
In SPS, the wires are resistive, inductive and in the form of RL which makes the
impedance of each wire equal to Z = R + jLω. Note that ω = 2πf which makes ω depends
on the frequency of injection. Therefore, the impedance of the cable also depends on the
frequency. The resistance (R) and inductance (L) of the cable are also related to the length of the
cable in the SPS. That is, R = rl where r is the resistance per mile and l is the length of the
cable. With the same approach, L = al where a is the inductance per mile and l is the length of
the cable. Under the assumption that the same cable is used across the SPS, the values for a and r
remain the same for the entire system and the only parameter that changes is the length which
makes R and L different for each cable. Let each element of Zbus be represented by the
complex number Zij =
Rij + jωLij. Then, Zij can be converted to Zij = Ψl where Ψ ∈ C1 is a constant complex
number and equal to Ψ = r + jωa. In addition, one can consider R = rl = const = K. By
Considering this can write:
Z = R + jLω = L
(
+ jω) =
al
(K +
)
𝐿
=
KC(ω)l
To the
Since K is considered a constant and a is the same inductance per mile for all the wires used in
SPS, there are only two variables in this equation which are l and ω.
In the proposed approach, the algorithm is supposed to look at the ∆V and ∆I values
to find the location of the fault in the system. Using standard error analysis, an observant change
in bus voltage on bus h (when an error occurs on bus p) can be described as:
Z (h, p)
27
∆Vh = Z(p, p)
+ R
× Vpref
erro
r
28
where Z(h,p) is the (h,p) entrée of the impedance matrix and Z(p,p) is the Thevenin
Impedance system visible from the p bus, and Vpref is the prefault voltage at the fault point in
the system. As shown in the equation, one needs to look for the impedance matrix (Zbus) to
find ∆Vh. Since the proposed algorithm is related to injection and measurement frequencies, one
needs to find the relationship between the impedance matrix and frequency to find the right
frequency to get the best results and find the unique values of ∆V and ∆I for each error. This
will then lead to finding the exact location of the fault for different Rfault values.
One can find Zbus by finding Ybus and flipping it, but this is inconvenient because
making it impossible for one to track the effect of frequency in the formulation of the fault site.
For this reason, the Zbus direct building algorithm is used to precisely find its relationship with
injection frequency. In the process of searching for Zbus it seems that all these matrix elements
have a(K + jω) in their numerator. Note that the Kron subtraction in this process will maintain
this value in the numerator of each Zbus element. As mentioned, for the analysis of the error
one needs to look at the values of ∆V and ∆I to find the exact location of the error. Because
every element of Zbus has
KC(ω) = a(K + jω), one can reset the equation as:
KC(ω)ZC(h, p)
∆Vh = KC(ω)ZC(p, p) +
R
where ZC(h, p) and ZC(p, p) are the elements of the Zbus
matrix.
KC(ω)
× Vpref
Similarly, for current measurements since ∆Vh is available for each h in the grid
according to the fault analysis of a standard power system, the change in channel current can be
erro
r
29
expressed as:
30
∆ Forward = ∆Vh
∆Vu
Zhu
= × (∆Vh − ∆Vu)
1
Zhu =
H
u
1
=Y(h, u)
∆Yehu = y(h, u) × (∆wu − ∆wow)
where H is the measurement bus and U is the adjacent bus connected to H by the Hu transmission line,
Zhu is the line impedance and Y(h, u) is the (h, u) entrée of the acceptance matrix. Because Ybus
=
1
Zbu
s
It seems that all of these matrix elements have 1
(K+jω)
in their numerator. Note that Kron
The subtraction in this process will maintain this value in the numerator of each Ybus element.
As mentioned, for error analysis one needs to look at the ∆V and ∆I values to find the exact
location of the
error. Because every element of
Ybus
Have
1
KC) =1
a(K+jω) , one can rearrange the equation as:
Forward
1
=KC(ω
)
YC(h, u) ×
(∆Vu
− ∆Vh)
where YC(h, u) is the element of Ybus × matrix KR(ω).
From the above equation it can be concluded that if the Rfault is a small value, the
frequency will not have a critical effect on the ∆V and ∆I values and the location of the fault,
but if the Rfault is large, one can get a higher ∆V and ∆I by increasing the frequency.
3.4 Reference
31
[1] Grainger, J. J., & Stevenson, W. D. Analysis of energy systems (Vol. 621). New York:
McGraw- Hill., 1994.
32
CHAPTER 4
SIMULATION RESULTS
4.1 Introduction
The 11-bus SPS in Figure 1.2 is considered a case study. The proposed algorithm is
applied to this system in Matlab/Simulink to find the minimum number of injections and
measurements and the best place for them to cover all errors in the network. The algorithm
checks all possible places for measurements and injections to see which errors are covered and
which are not.
4.2 Simulation Results for f=1000Hz
Table 4.1 shows the number of errors (occurring on the bus) that were not detected for the
selected M and I values. The algorithm is also capable of showing which errors are not covered
in each case (numbers in parentheses). Table 4.1 shows the results when Rfault = 1e−4 and
f = 1000Hz in both injections and measurements. For example, based on Table 4.1, if we have
an injection on bus 2 and a measurement on bus 3, we have two undetected errors that are on bus
6 and bus 9.
Table 4.1 Results of the application of the proposed approach when Rfault = 1e−4
and f = 1000Hz
33
M
ME
1 2 3 4 5 6
11
(11)
7
(3,4,5,7,8,10,11)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,11)
24
(4,6,9,11)
2
(4,11)
2
(6,9)
2
(6,9)
4
(4,6,9,11)
9
(1,3,4,5,7,8,9,10,11)
32
(4,11)
2
(4,11)
2
(6,9)
8
(1,2,5,6,7,8,9,10)
2
(4,11)
2
(4,11)
41
(11)
1
(11)
8
(2,5,6,7,8,9,10,11)
7
(2,5,6,7,8,9,10)
1
(11)
1
(11)
55
(4,7,8,10,11)
5
(4,7,8,10,11)
3
(7,8,10)
3
(7,8,10)
7
(1,2,3,4,6,9,11)
5
(4,7,8,10,11)
62
(4,11)
3
(3,4,11) 0 0 2
(4,11)
10
(1,2,3,4,5,7,8,9,10,11)
72
(4,11)
2
(4,11) 0 0 3
(3,4,11)
2
(4,11)
83
(4,10,11)
3
(4,10,11)
1
(10)
1
(10)
4
(3,4,10,11)
3
(4,10,11)
92
(4,11)
3
(3,4,11) 0 0 2
(4,11)
3
(3,4,11)
10 2
(4,11)
2
(4,11) 0 0 3
(3,4,11)
2
(4,11)
11 0 0 6
(2,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10) 0 0
Table 4.1 Results of the application of the proposed approach when Rfault = 1e−4
and f = 1000Hz
34
M
ME
7 8 9 10 11
16
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,11)
6
(2,3,4,6,9,11)
7
(2,5,6,7,8,9,10)
24
(4,6,9,11)
4
(4,6,9,11)
9
(1,3,4,5,6,7,8,10,11)
4
(4,6,9,11)
2
(6,9)
32
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
8
(1,2,5,6,7,8,9,10)
41
(11)
1
(11)
1
(11)
1
(11)
9
(1,2,3,5,6,7,8,9,10))
59
(1,2,3,4,6,8,9,10,11)
8
(1,2,3,4,6,7,9,11)
5
(4,7,8,10,11)
8
(1,2,3,4,6,7,9,11)
3
(7,8,10)
62
(4,11)
2
(4,11)
3
(3,4,11)
2
(4,11) 0
710
(1,2,3,4,5,6,8,9,10,11)
3
(3,4,11)
2
(4,11)
3
(3,4,11) 0
84
(3,4,10,11)
9
(1,2,3,4,5,6,7,9,11)
3
(4,10,11)
9
(1,2,3,4,5,6,7,9,11))
1
(10)
92
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,10,11)
2
(4,11) 0
10 3
(3,4,11)
3
(3,4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,9,11) 0
11 0 0 0 0 10
(1,2,3,4,5,6,7,8,9,10)
31
Table 4.1 shows that there are some cases with the lowest number (0 or 1) of undetected
errors. Zero indicates that the measurements on the M bus can observe all system faults when
the injection is performed on the I bus. If there are no zeros in the table, the system will consider
more than one injection bus and/or measurement to observe all possible desired errors.
Furthermore, the case with the lowest number of undetected errors should be checked for multi-
estimation. In other words, these cases must prove that they have a unique effect on the
measurement chosen for each error. If the measurements for multiple errors are the same, multi-
estimation has occurred, since these errors are not recognizable to each other and thus increase
the number of undetected errors. In our simulations, there are no cases in Table 4.1 that involve
multi-estimation. The highlighted sections in the table show cases that require multi-estimation.
Tables 4.2, 4.3, 4.4, and 4.5 show that assuming a higher Rfault for a system with the
same value for frequency (1000 Hz) the results will change slightly. In this case some cases
involve multi-estimation.
Table 4.2 Results of the application of the proposed approach when Rfault = 1e−3
and f = 1000Hz
32
M
ME
1 2 3 4 5 6
11
(11)
7
(3,4,5,7,8,10,11)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,11)
24
(4,6,9,11)
2
(4,11)
2
(6,9)
2
(6,9)
4
(4,6,9,11)
9
(1,3,4,5,7,8,9,10,11)
32
(4,11)
2
(4,11)
2
(6,9)
8
(1,2,5,6,7,8,9,10)
2
(4,11)
2
(4,11)
41
(11)
1
(11)
8
(2,5,6,7,8,9,10,11)
7
(2,5,6,7,8,9,10)
1
(11)
1
(11)
55
(4,7,8,10,11)
5
(4,7,8,10,11)
3
(7,8,10)
3
(7,8,10)
7
(1,2,3,4,6,9,11)
5
(4,7,8,10,11)
62
(4,11)
3
(3,4,11) 0 0 2
(4,11)
10
(1,2,3,4,5,7,8,9,10,11)
72
(4,11)
2
(4,11) 0 0 3
(3,4,11)
2
(4,11)
83
(4,10,11)
3
(4,10,11)
1
(10)
1
(10)
4
(3,4,10,11)
3
(4,10,11)
92
(4,11)
3
(3,4,11) 0 0 2
(4,11)
3
(3,4,11)
10 2
(4,11)
2
(4,11) 0 0 3
(3,4,11)
2
(4,11)
11 0 0 6
(2,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10) 00
Table 4.2 Results of the application of the proposed approach when Rfault = 1e−3
and f = 1000Hz
33
M
ME
7 8 9 10 11
16
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,11)
6
(2,3,4,6,9,11)
7
(2,5,6,7,8,9,10)
24
(4,6,9,11)
4
(4,6,9,11)
9
(1,3,4,5,6,7,8,10,11)
4
(4,6,9,11)
2
(6,9)
32
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
8
(1,2,5,6,7,8,9,10)
41
(11)
1
(11)
1
(11)
1
(11)
9
(1,2,3,5,6,7,8,9,10))
59
(1,2,3,4,6,8,9,10,11)
8
(1,2,3,4,6,7,9,11)
5
(4,7,8,10,11)
8
(1,2,3,4,6,7,9,11)
3
(7,8,10)
62
(4,11)
2
(4,11)
3
(3,4,11)
2
(4,11) 0
710
(1,2,3,4,5,6,8,9,10,11)
3
(3,4,11)
2
(4,11)
3
(3,4,11) 0
84
(3,4,10,11)
9
(1,2,3,4,5,6,7,9,11)
3
(4,10,11)
9
(1,2,3,4,5,6,7,9,11))
1
(10)
92
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,10,11)
2
(4,11) 0
10 3
(3,4,11)
3
(3,4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,9,11) 0
11 0 0 0 0 10
(1,2,3,4,5,6,7,8,9,10)
Table 4.3 Results of the application of the proposed approach when Rfault = 1e−2
and f = 1000Hz
34
M
ME
1 2 3 4 5 6
12
(1,11)
8
(1,3,4,5,7,8,10,11)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
7
(1,2,3,4,6,9,11)
8
(1,3,4,5,7,8,10,11)
25
(2,4,6,9,11)
3
(2,4,11)
3
(2,6,9)
3
(2,6,9)
5
(2,4,6,9,11)
10
(1,2,3,4,5,7,8,9,10,11)
31
(11)
1
(11)
2
(6,9)
8
(1,2,5,6,7,8,9,10)
1
(11)
1
(11)
40 0 7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10) 0 0
56
(4,5,7,8,10,11))
6
(4,5,7,8,10,11)
4
(5,7,8,10)
4
(5,7,8,10)
8
(1,2,3,4,5,6,9,11)
6
(4,5,7,8,10,11)
63
(4,6,11)
4
(3,4,6,11)
1
(6)
1
(6)
3
(4,6,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
73
(4,7,11)
3
(4,7,11)
1
(7)
1
(7)
4
(3,4,7,11)
3
(4,7,11)
83
(4,10,11)
3
(4,10,11)
1
(10)
1
(10)
4
(3,4,10,11)
3
(4,10,11)
93
(4,9,11)
4
(3,4,9,11)
1
(9)
1
(9)
3
(4,9,11)
4
(3,4,9,11)
10 3
(4,10,11)
3
(4,10,11)
1
(10)
1
(10)
4
(3,4,10,11)
3
(4,10,11)
11 1
(11)
1
(11)
8
(2,5,6,7,8,9,10,11)
9
(1,2,5,6,7,8,9,10,11)
1
(11)
1
(11)
Table 4.3 Results of the application of the proposed approach when Rfault = 1e−2
and f = 1000Hz
35
M
ME
7 8 9 10 11
17
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
8
(1,3,4,5,7,8,10,11)
7
(1,2,3,4,6,9,11)
8
(1,2,5,6,7,8,9,10)
25
(2,4,6,9,11)
5
(2,4,6,9,11)
10
(1,2,3,4,5,6,7,8,10,11)
5
(2,4,6,9,11)
3
(2,6,9)
31
(11)
1
(11)
1
(11)
1
(11)
8
(1,2,5,6,7,8,9,10)
40 0 0 0 9
(1,2,3,5,6,7,8,9,10)
510
(1,2,3,4,5,6,8,9,10,11)
9
(1,2,3,4,5,6,7,9,11)
6
(4,5,7,8,10,11)
9
(1,2,3,4,5,6,7,9,11)
4
(5,7,8,10)
63
(4,6,11)
3
(4,6,11)
4
(3,4,6,11)
3
(4,6,11)
1
(6)
711
(1,2,3,4,5,6,7,8,9,10,11)
4
(3,4,7,11)
3
(4,7,11)
4
(3,4,7,11)
1
(7)
84
(3,4,10,11)
10
(1,2,3,4,5,6,7,8,9,11)
3
(4,10,11)
8
(1,2,3,4,6,7,9,11))
1
(10)
93
(4,9,11)
3
(4,9,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
3
(4,9,11)
1
(9)
10 4
(3,4,10,11)
4
(3,4,10,11)
3
(4,10,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
1
(10)
11 1
(11)
1
(11)
1
(11)
1
(11)
11
(1,2,3,4,5,6,7,8,9,10,11)
Table 4.4 Results of the application of the proposed approach when Rfault = 1e−1
and f = 1000Hz
36
M
ME
1 2 3 4 5 6
13
(1,4,11)
8
(1,3,4,5,7,8,10,11)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
7
(1,2,3,4,6,9,11)
8
(1,3,4,5,7,8,10,11)
26
(2,3,4,6,9,11)
4
(2,3,4,11)
3
(2,6,9)
3
(2,6,9)
6
(2,3,4,6,9,11)
10
(1,2,3,4,5,7,8,9,10,11)
33
(3,4,11)
3
(3,4,11)
9
(1,2,3,5,6,7,8,9,10)
9
(1,2,3,5,6,7,8,9,10)
3
(3,4,11)
3
(3,4,11)
42
(4,11)
2
(4,11)
10
(1,2,4,5,6,7,8,9,10,11)
9
(1,2,4,5,6,7,8,9,10)
2
(4,11)
2
(4,11)
57
(3,4,5,7,8,10,11)
7
(3,4,5,7,8,10,11)
4
(5,7,8,10)
4
(5,7,8,10)
8
(1,2,3,4,5,6,9,11)
7
(3,4,5,7,8,10,11)
64
(3,4,6,11)
4
(3,4,6,11)
1
(6)
1
(6)
4
(3,4,6,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
74
(3,4,7,11)
4
(3,4,7,11)
1
(7)
1
(7)
4
(3,4,7,11)
4
(3,4,7,11)
85
(3,4,8,10,11)
5
(3,4,8,10,11)
2
(8,10)
2
(8,10)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
94
(3,4,9,11)
4
(3,4,9,11)
1
(9)
1
(9)
4
(3,4,9,11)
4
(3,4,10,11)
10 4
(3,4,10,11)
4
(3,4,10,11)
1
(10)
1
(10)
4
(3,4,10,11)
4
(3,4,10,11)
11 1
(11)
1
(11)
9
(1,2,5,6,7,8,9,10,11)
9
(1,2,5,6,7,8,9,10,11)
1
(11)
1
(11)
Table 4.4 Results of the application of the proposed approach when Rfault = 1e−1
and f = 1000Hz
37
M
ME
7 8 9 10 11
17
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
8
(1,3,4,5,7,8,10,11)
7
(1,2,3,4,6,9,11)
8
(1,2,5,6,7,8,9,10)
26
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
10
(1,2,3,4,5,6,7,8,10,11)
6
(2,3,4,6,9,11)
3
(2,6,9)
33
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
9
(1,2,3,5,6,7,8,9,10)
42
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,9,10)
510
(1,2,3,4,5,6,8,9,10,11)
9
(1,2,3,4,5,6,7,9,11)
7
(3,4,5,7,8,10,11)
9
(1,2,3,4,5,6,7,9,11)
4
(5,7,8,10)
64
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
1
(6)
711
(1,2,3,4,5,6,7,8,9,10,11)
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
1
(7)
85
(3,4,8,10,11)
10
(1,2,3,4,5,6,7,8,9,11)
5
(3,4,8,10,11)
10
(1,2,3,4,5,6,7,8,9,11)
2
(8,10)
94
(3,4,9,11)
4
(3,4,9,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
4
(3,4,9,11)
1
(9)
10 4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
1
(10)
11 1
(11)
1
(11)
1
(11)
1
(11)
11
(1,2,3,4,5,6,7,8,9,10,11)
Table 4.5 Results of the implementation of the proposed approach when
Rfault =
1 and f = 1000Hz
38
M
I 1 2 3 4 5 6
14
(1,3,4,11)
8
(1,3,4,5,7,8,10,11)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
7
(1,2,3,4,6,9,11)
8
(1,3,4,5,7,8,10,11)
26
(2,3,4,6,9,11)
4
(2,3,4,11)
3
(2,6,9)
3
(2,6,9)
6
(2,3,4,6,9,11)
10
(1,2,3,4,5,7,8,9,10,11)
33
(3,4,11)
3
(3,4,11)
9
(1,2,3,5,6,7,8,9,10)
9
(1,2,3,5,6,7,8,9,10)
3
(3,4,11)
3
(3,4,11)
42
(4,11)
2
(4,11)
10
(1,2,4,5,6,7,8,9,10,11)
9
(1,2,4,5,6,7,8,9,10)
2
(4,11)
2
(4,11)
57
(3,4,5,7,8,10,11)
7
(3,4,5,7,8,10,11)
4
(5,7,8,10)
4
(5,7,8,10)
8
(1,2,3,4,5,6,9,11)
7
(3,4,5,7,8,10,11)
64
(3,4,6,11)
4
(3,4,6,11)
1
(6)
1
(6)
4
(3,4,6,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
74
(3,4,7,11)
4
(3,4,7,11)
1
(7)
1
(7)
7
(2,3,4,6,7,9,11)
4
(3,4,7,11)
85
(3,4,8,10,11)
5
(3,4,8,10,11)
2
(8,10)
2
(8,10)
8
(2,3,4,6,8,9,10,11)
5
(3,4,8,10,11)
94
(3,4,9,11)
4
(3,4,9,11)
1
(9)
1
(9)
4
(3,4,9,11)
4
(3,4,9,11)
10 4
(3,4,10,11)
4
(3,4,10,11)
1
(10)
1
(10)
7
(2,3,4,6,9,10,11)
4
(3,4,10,11)
11 1
(11)
1
(11)
9
(1,2,5,6,7,8,9,10,11)
9
(1,2,5,6,7,8,9,10,11)
1
(11)
1
(11)
Table 4.5 Results of the implementation of the proposed approach when
Rfault =
1 and f = 1000Hz
39
M
I 7 8 9 10 11
17
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
8
(1,3,4,5,7,8,10,11)
7
(1,2,3,4,6,9,11)
8
(1,2,5,6,7,8,9,10)
26
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
10
(1,2,3,4,5,6,7,8,10,11)
6
(2,3,4,6,9,11)
3
(2,6,9)
33
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
9
(1,2,3,5,6,7,8,9,10)
42
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,9,10)
510
(1,2,3,4,5,6,8,9,10,11)
9
(1,2,3,4,5,6,7,9,11)
7
(3,4,5,7,8,10,11)
9
(1,2,3,4,5,6,7,9,11)
4
(5,7,8,10)
64
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
1
(6)
711
(1,2,3,4,5,6,7,8,9,10,11)
7
(2,3,4,6,7,9,11)
4
(3,4,7,11)
7
(2,3,4,6,7,9,11)
1
(7)
88
(2,3,4,6,8,9,10,11)
10
(1,2,3,4,5,6,7,8,9,11)
5
(3,4,8,10,11)
10
(1,2,3,4,5,6,7,8,9,11)
2
(8,10)
94
(3,4,9,11)
4
(3,4,9,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
4
(3,4,9,11)
1
(9)
10 7
(2,3,4,6,9,10,11)
8
(1,2,3,4,6,9,10,11)
4
(3,4,10,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
1
(10)
11 1
(11)
1
(11)
1
(11)
1
(11)
11
(1,2,3,4,5,6,7,8,9,10,11)
40
This algorithm is also applied to systems with Rfault = 1 and f = 1000Hz. As shown
in Table 4.5, in this scenario all cases that have the lowest number of undetected faults suffer
from multi-estimation (highlighted figure). That is, for higher Rfaults, the combination of
injection and measurement buses with f = 1000Hz cannot cover all fault locations unless
multiple injection and measurement buses are selected. This requires the algorithm to run at a
higher frequency (f=7000Hz.)
4.3 Simulation Result for f=7000Hz
The algorithm repeats all the steps with f = 7000Hz for different Rfault values
(1e−4, 1e−3, 1e−2, 1e−1, and 1) to minimize the number of multi-estimates. Each Rfault
will generate a table similar to Table 4.1 showing the number of undetected errors for each case
(Tables 4.6, 4.7, 4.8, .49, and 4.10).
Table 4.6 Results of the implementation of the proposed approach when Rfault =
1e−4 and f = 7000Hz
41
M
I 1 2 3 4 5 6
11
(11)
7
(3,4,5,7,8,10,11)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,11)
24
(4,6,9,11)
2
(4,11)
2
(6,9)
2
(6,9)
4
(4,6,9,11)
9
(1,3,4,5,7,8,9,10,11)
32
(4,11)
2
(4,11)
2
(6,9)
8
(1,2,5,6,7,8,9,10)
2
(4,11)
2
(4,11)
41
(11)
1
(11)
8
(2,5,6,7,8,9,10,11)
7
(2,5,6,7,8,9,10)
1
(11)
1
(11)
55
(4,7,8,10,11)
5
(4,7,8,10,11)
3
(7,8,10)
3
(7,8,10)
7
(1,2,3,4,6,9,11)
5
(4,7,8,10,11)
62
(4,11)
3
(3,4,11) 0 0 2
(4,11)
10
(1,2,3,4,5,7,8,9,10,11)
72
(4,11)
2
(4,11) 0 0 3
(3,4,11)
2
(4,11)
83
(4,10,11)
3
(4,10,11)
1
(10)
1
(10)
4
(3,4,10,11)
3
(4,10,11)
92
(4,11)
3
(3,4,11) 0 0 2
(4,11)
3
(3,4,11)
10 2
(4,11)
2
(4,11) 0 0 3
(3,4,11)
2
(4,11)
11 0 0 6
(2,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10) 0 0
Table 4.6 Results of the implementation of the proposed approach when Rfault =
1e−4 and f = 7000Hz
42
M
ME
7 8 9 10 11
16
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,11)
6
(2,3,4,6,9,11)
7
(2,5,6,7,8,9,10)
24
(4,6,9,11)
4
(4,6,9,11)
9
(1,3,4,5,6,7,8,10,11)
4
(4,6,9,11)
2
(6,9)
32
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
8
(1,2,5,6,7,8,9,10)
41
(11)
1
(11)
1
(11)
1
(11)
9
(1,2,3,5,6,7,8,9,10))
59
(1,2,3,4,6,8,9,10,11)
8
(1,2,3,4,6,7,9,11)
5
(4,7,8,10,11)
8
(1,2,3,4,6,7,9,11)
3
(7,8,10)
62
(4,11)
2
(4,11)
3
(3,4,11)
2
(4,11) 0
710
(1,2,3,4,5,6,8,9,10,11)
3
(3,4,11)
2
(4,11)
3
(3,4,11) 0
84
(3,4,10,11)
9
(1,2,3,4,5,6,7,9,11)
3
(4,10,11)
9
(1,2,3,4,5,6,7,9,11))
1
(10)
92
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,10,11)
2
(4,11) 0
10 3
(3,4,11)
3
(3,4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,9,11) 0
11 0 0 0 0 10
(1,2,3,4,5,6,7,8,9,10)
Table 4.7 Results of the implementation of the proposed approach when Rfault =
1e−3 and f = 7000Hz
43
M
ME
1 2 3 4 5 6
11
(11)
7
(3,4,5,7,8,10,11)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,11)
24
(4,6,9,11)
2
(4,11)
2
(6,9)
2
(6,9)
4
(4,6,9,11)
9
(1,3,4,5,7,8,9,10,11)
32
(4,11)
2
(4,11)
2
(6,9)
8
(1,2,5,6,7,8,9,10)
2
(4,11)
2
(4,11)
41
(11)
1
(11)
8
(2,5,6,7,8,9,10,11)
7
(2,5,6,7,8,9,10)
1
(11)
1
(11)
55
(4,7,8,10,11)
5
(4,7,8,10,11)
3
(7,8,10)
3
(7,8,10)
7
(1,2,3,4,6,9,11)
5
(4,7,8,10,11)
62
(4,11)
3
(3,4,11) 0 0 2
(4,11)
10
(1,2,3,4,5,7,8,9,10,11)
72
(4,11)
2
(4,11) 0 0 3
(3,4,11)
2
(4,11)
83
(4,10,11)
3
(4,10,11)
1
(10)
1
(10)
4
(3,4,10,11)
3
(4,10,11)
92
(4,11)
3
(3,4,11) 0 0 2
(4,11)
3
(3,4,11)
10 2
(4,11)
2
(4,11) 0 0 3
(3,4,11)
2
(4,11)
11 0 0 6
(2,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10) 0 0
Table 4.7 Results of the implementation of the proposed approach when Rfault =
1e−3 and f = 7000Hz
44
M
I 7 8 9 10 11
16
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,11)
6
(2,3,4,6,9,11)
7
(2,5,6,7,8,9,10)
24
(4,6,9,11)
4
(4,6,9,11)
9
(1,3,4,5,6,7,8,10,11)
4
(4,6,9,11)
2
(6,9)
32
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
8
(1,2,5,6,7,8,9,10)
41
(11)
1
(11)
1
(11)
1
(11)
9
(1,2,3,5,6,7,8,9,10))
59
(1,2,3,4,6,8,9,10,11)
8
(1,2,3,4,6,7,9,11)
5
(4,7,8,10,11)
8
(1,2,3,4,6,7,9,11)
3
(7,8,10)
62
(4,11)
2
(4,11)
3
(3,4,11)
2
(4,11) 0
710
(1,2,3,4,5,6,8,9,10,11)
3
(3,4,11)
2
(4,11)
3
(3,4,11) 0
84
(3,4,10,11)
9
(1,2,3,4,5,6,7,9,11)
3
(4,10,11)
9
(1,2,3,4,5,6,7,9,11))
1
(10)
92
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,10,11)
2
(4,11) 0
10 3
(3,4,11)
3
(3,4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,9,11) 0
11 0 0 0 0 10
(1,2,3,4,5,6,7,8,9,10)
Table 4.8 Results of the implementation of the proposed approach when Rfault =
1e−2 and f = 7000Hz
45
M
ME
1 2 3 4 5 6
11
(11)
7
(3,4,5,7,8,10,11)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,11)
24
(4,6,9,11)
2
(4,11)
2
(6,9)
2
(6,9)
4
(4,6,9,11)
9
(1,3,4,5,7,8,9,10,11)
32
(4,11)
2
(4,11)
2
(6,9)
8
(1,2,5,6,7,8,9,10)
2
(4,11)
2
(4,11)
41
(11)
1
(11)
8
(2,5,6,7,8,9,10,11)
7
(2,5,6,7,8,9,10)
1
(11)
1
(11)
55
(4,7,8,10,11)
5
(4,7,8,10,11)
3
(7,8,10)
3
(7,8,10)
7
(1,2,3,4,6,9,11)
5
(4,7,8,10,11)
62
(4,11)
3
(3,4,11) 0 0 2
(4,11)
10
(1,2,3,4,5,7,8,9,10,11)
72
(4,11)
2
(4,11) 0 0 3
(3,4,11)
2
(4,11)
83
(4,10,11)
3
(4,10,11)
1
(10)
1
(10)
4
(3,4,10,11)
3
(4,10,11)
92
(4,11)
3
(3,4,11) 0 0 2
(4,11)
3
(3,4,11)
10 2
(4,11)
2
(4,11) 0 0 3
(3,4,11)
2
(4,11)
11 0 0 6
(2,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10) 0 0
Table 4.8 Results of the implementation of the proposed approach when Rfault =
1e−2 and f = 7000Hz
46
M
ME
78910 11
16
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,11)
6
(2,3,4,6,9,11)
7
(2,5,6,7,8,9,10)
24
(4,6,9,11)
4
(4,6,9,11)
9
(1,3,4,5,6,7,8,10,11)
4
(4,6,9,11)
2
(6,9)
32
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
8
(1,2,5,6,7,8,9,10)
41
(11)
1
(11)
1
(11)
1
(11)
9
(1,2,3,5,6,7,8,9,10))
59
(1,2,3,4,6,8,9,10,11)
8
(1,2,3,4,6,7,9,11)
5
(4,7,8,10,11)
8
(1,2,3,4,6,7,9,11)
3
(7,8,10)
62
(4,11)
2
(4,11)
3
(3,4,11)
2
(4,11) 0
710
(1,2,3,4,5,6,8,9,10,11)
3
(3,4,11)
2
(4,11)
3
(3,4,11) 0
84
(3,4,10,11)
9
(1,2,3,4,5,6,7,9,11)
3
(4,10,11)
9
(1,2,3,4,5,6,7,9,11))
1
(10)
92
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,10,11)
2
(4,11) 0
10 3
(3,4,11)
3
(3,4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,9,11) 0
11 0 0 0 0 10
(1,2,3,4,5,6,7,8,9,10)
Table 4.9 Results of the application of the proposed approach when Rfault = 1e−1
and f = 7000Hz
47
M
ME
1 2 3 4 5 6
12
(1,11)
8
(1,3,4,5,7,8,10,11)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
7
(1,2,3,4,6,9,11)
8
(1,3,4,5,7,8,10,11)
25
(2,4,6,9,11)
3
(2,4,11)
3
(2,6,9)
3
(2,6,9)
5
(2,4,6,9,11)
10
(1,2,3,4,5,7,8,9,10,11)
33
(3,4,11)
3
(3,4,11)
3
(3,6,9)
9
(1,2,3,5,6,7,8,9,10)
3
(3,4,11)
3
(3,4,11)
42
(4,11)
2
(4,11)
9
(2,4,5,6,7,8,9,10,11)
8
(2,4,5,6,7,8,9,10)
2
(4,11)
2
(4,11)
56
(4,5,7,8,10,11)
6
(4,5,7,8,10,11)
4
(5,7,8,10)
4
(5,7,8,10)
8
(1,2,3,4,5,6,9,11)
6
(4,5,7,8,10,11)
63
(4,6,11)
4
(3,4,6,11)
1
(6)
1
(6)
3
(4,6,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
73
(4,7,11)
3
(4,7,11)
1
(7)
1
(7)
4
(3,4,7,11)
3
(4,7,11)
84
(4,8,10,11)
4
(4,8,10,11)
2
(8,10)
2
(8,10)
5
(3,4,8,10,11)
4
(4,8,10,11)
93
(4,9,11)
4
(3,4,9,11)
1
(9)
1
(9)
3
(4,9,11)
4
(3,4,9,11)
10 3
(4,10,11)
3
(4,10,11)
1
(10)
1
(10)
4
(3,4,10,11)
3
(4,10,11)
11 1
(11)
1
(11)
8
(2,5,6,7,8,9,10,11)
9
(1,2,5,6,7,8,9,10,11)
1
(11)
1
(11)
Table 4.9 Results of the application of the proposed approach when Rfault = 1e−1
and f = 7000Hz
48
M
ME↓ 7 8 9 10 11
17
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
8
(1,3,4,5,7,8,10,11)
7
(1,2,3,4,6,9,11)
8
(1,2,5,6,7,8,9,10)
25
(2,4,6,9,11)
5
(2,4,6,9,11)
10
(1,2,3,4,5,6,7,8,10,11)
5
(2,4,6,9,11)
3
(2,6,9)
33
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
9
(1,2,3,5,6,7,8,9,10)
42
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,9,10)
510
(1,2,3,4,5,6,8,9,10,11)
9
(1,2,3,4,5,6,7,9,11)
6
(4,5,7,8,10,11)
9
(1,2,3,4,5,6,7,9,11)
4
(5,7,8,10)
63
(4,6,11)
3
(4,6,11)
4
(3,4,6,11)
3
(4,6,11)
1
(6)
711
(1,2,3,4,5,6,7,8,9,10,11)
4
(3,4,7,11)
3
(4,7,11)
4
(3,4,7,11)
1
(7)
85
(3,4,8,10,11)
10
(1,2,3,4,5,6,7,8,9,11)
4
(4,8,10,11)
10
(1,2,3,4,5,6,7,8,9,11)
2
(8,10)
93
(4,9,11)
3
(4,9,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
3
(4,9,11)
1
(9)
10 4
(3,4,10,11)
4
(3,4,10,11)
3
(4,10,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
1
(10)
11 1
(11)
1
(11)
1
(11)
1
(11)
11
(1,2,3,4,5,6,7,8,9,10,11)
Table 4.10 Results of the implementation of the proposed approach when
Rfault =
1 and f = 7000Hz
49
M
ME
1 2 3 4 5 6
14
(1,3,4,11)
8
(1,3,4,5,7,8,10,11)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
7
(1,2,3,4,6,9,11)
8
(1,3,4,5,7,8,10,11)
26
(2,3,4,6,9,11)
4
(2,3,4,11)
3
(2,6,9)
3
(2,6,9)
6
(2,3,4,6,9,11)
10
(1,2,3,4,5,7,8,9,10,11)
33
(3,4,11)
3
(3,4,11)
9
(1,2,3,5,6,7,8,9,10)
9
(1,2,3,5,6,7,8,9,10)
3
(3,4,11)
3
(3,4,11)
42
(4,11)
2
(4,11)
10
(1,2,4,5,6,7,8,9,10,11)
9
(1,2,4,5,6,7,8,9,10)
2
(4,11)
2
(4,11)
57
(3,4,5,7,8,10,11)
7
(3,4,5,7,8,10,11)
4
(5,7,8,10)
4
(5,7,8,10)
8
(1,2,3,4,5,6,9,11)
7
(3,4,5,7,8,10,11)
64
(3,4,6,11)
4
(3,4,6,11)
1
(6)
1
(6)
4
(3,4,6,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
74
(3,4,7,11)
4
(3,4,7,11)
1
(7)
1
(7)
4
(3,4,7,11)
4
(3,4,7,11)
85
(3,4,8,10,11)
5
(3,4,8,10,11)
2
(8,10)
2
(8,10)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
94
(3,4,9,11)
4
(3,4,9,11)
1
(9)
1
(9)
4
(3,4,9,11)
4
(3,4,9,11)
10 4
(3,4,10,11)
4
(3,4,10,11)
1
(10)
1
(10)
4
(3,4,10,11)
4
(3,4,10,11)
11 1
(11)
1
(11)
9
(1,2,5,6,7,8,9,10,11)
9
(1,2,5,6,7,8,9,10,11)
1
(11)
1
(11)
Table 4.10 Results of the implementation of the proposed approach when
Rfault =
1 and f = 7000Hz
50
M
ME
7 8 9 10 11
17
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
8
(1,3,4,5,7,8,10,11)
7
(1,2,3,4,6,9,11)
8
(1,2,5,6,7,8,9,10)
26
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
10
(1,2,3,4,5,6,7,8,10,11)
6
(2,3,4,6,9,11)
3
(2,6,9)
33
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
9
(1,2,3,5,6,7,8,9,10)
42
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,7,8,9,10)
510
(1,2,3,4,5,6,8,9,10,11)
9
(1,2,3,4,5,6,7,9,11)
7
(3,4,5,7,8,10,11)
9
(1,2,3,4,5,6,7,9,11)
4
(5,7,8,10)
64
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
1
(6)
711
(1,2,3,4,5,6,7,8,9,10,11)
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
1
(7)
85
(3,4,8,10,11)
10
(1,2,3,4,5,6,7,8,9,11)
5
(3,4,8,10,11)
10
(1,2,3,4,5,6,7,8,9,11)
2
(8,10)
94
(3,4,9,11)
4
(3,4,9,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
4
(3,4,9,11)
1
(9)
10 4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
11
(1,2,3,4,5,6,7,8,9,10,11)
1
(10)
11 1
(11)
1
(11)
1
(11)
1
(11)
11
(1,2,3,4,5,6,7,8,9,10,11)
51
The algorithm compares all of these tables together to find the optimal bus for injection
and measurement to find the unique location of the error with minimal multi-estimation. Table
4.10 shows the results for Rfault = 1 when f = 7000Hz. This table is compared with other
tables at f = 7000Hz for different Rfaults to find the optimal measurement and injection
location. Cases with circles have the lowest number of undetected errors for all possible
Rfaults that do not involve multi-estimation.
The optimal injection measurement set for the system analyzed in this paper requires two
injections and two measurements to cover all errors (1e−4, 1e−3, 1e−2, 1e−1, and 1) in the
system. By comparing the table for f = 7000Hz it is shown that the first injection should be on
bus 6 with the measurement on bus 3. The second injection and measurement pair can be one of
these cases: I = 9, M = 3, or I = 11, M = 1, or I = 11, M = 2, or I = 11, M = 5, or
I = 11, M = 6, or I = 11, M = 7, or I = 11, M = 8, or I = 11, M = 9, or I = 11, M = 10.
4.4 Error Location Results Using Channel Current Measurement
Since each bus connects multiple lines together and each of these lines has a different
flow, one needs to know which line is used for the fault location and which lane produces the
lowest undetected error.
The 11-bus SPS in figure 4.1 is considered a case study. In this image each row has a
number that is used for the current measurement. The proposed algorithm is applied to this
system in Matlab/Simulink to find the minimum number of injections and measurements and the
best place for them to cover all errors in the network. The algorithm checks all possible places
for measurements and injections to see which errors are covered and which are not. The
proposed algorithm is tested for Rfault = 1 and Rfault = 1e−3 for f = 1000Hz and
f = 7000Hz. In this section, each table shows the results for current and voltage
52
Measurement. In this section, the circle in the table shows cases with better results for current
measurements than voltage measurements. The highlighted table shows cases that require multi-
estimation.
Figure 4.1 11-Bus SPS
53
4.5 Current Measurement Results for Rfault = 1e−3 and f = 1000Hz
Table 4.11 Voltage and current measurements for Bus-1 when Rfault = 1e−3 and f =
1000Hz
Msr
Inj
Bus-1
Voltase Current
Bus-1 Bus-1-Line-1 Bus-1-Line-2 Bus-1-Line-3 Bus-1-Line-4
Until
-1
10
(2,3,4,5,6,7,8,
9,10,11)
1
(11)
7
(2,5,6,7,8,9,10
)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,1
1)
Until
-2
4
(4,6,9,11)
4
(4,6,9,11)
2
(6,9)
4
(4,6,9,11)
4
(4,6,9,11)
Until
-3
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Until
-4
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
Until
-5
5
(4,7,8,10,11)
5
(4,7,8,10,11)
3
(7,8,10)
5
(4,7,8,10,11)
5
(4,7,8,10,11)
Until
-6
2
(4,11)
2
(4,11)
02
(4,11)
2
(4,11)
Until
-7
2
(4,11)
2
(4,11)
03
(3,4,11)
2
(4,11)
Until
-8
3
(4,10,11)
3
(4,10,11)
1
(10)
4
(3,4,10,11)
3
(4,10,11)
Until
-9
2
(4,11)
2
(4,11)
02
(4,11)
2
(4,11)
Until
-10
2
(4,11)
2
(4,11)
03
(3,4,11)
2
(4,11)
Until
-11 00000
Table 4.12 Voltage and current measurements for Bus-2 when Rfault = 1e−3 and f =
1000Hz
54
Msr
Inj
Bus-2
Voltase Current
Bus-2 Bus-2-Line-1 Bus-2-Line-2 Bus-2-Line-3 Bus-2-Line-4
Bus-
1
7
(3,4,5,7,8,10
,11)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,11
)
4
(3,4,7,11)
7
(3,4,5,7,8,10,1
1)
Bus-
2
10
(1,3,4,5,6,7,
8,9,10,11)
2
(4,11)
4
(4,6,9,11)
9
(1,3,4,5,7,8,9,
10,11)
9
(1,3,4,5,6,7,8,1
0,11)
Bus-
3
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
4
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
Bus-
5
5
(4,7,8,10,11)
5
(4,7,8,10,11)
5
(4,7,8,10,11)
3
(4,7,11)
5
(4,7,8,10,11)
Bus-
6
3
(3,4,11)
3
(3,4,11)
2
(4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
7
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
8
3
(4,10,11)
3
(4,10,11)
3
(4,10,11)
3
(4,10,11)
3
(4,10,11)
Bus-
9
3
(3,4,11)
3
(3,4,11)
2
(4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
10
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
11 0 0 0 0 0
Table 4.13 Voltage and current measurements for Bus-3 when Rfault = 1e−3 and f =
1000Hz
55
Msr
Inj
Bus-3
Voltase Current
Bus-3 Bus-3-Line-1 Bus-3-Line-2 Bus-3-Line-3
Bus-
1
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
Bus-
2
2
(6,9)
2
(6,9)
2
(6,9)
2
(6,9)
Bus-
3
10
(1,2,4,5,6,7,8,9,10,11)
2
(6,9)
2
(4,11)
8
(1,2,5,6,7,8,9,10)
Bus-
4
8
(2,5,6,7,8,9,10,11)
8
(2,5,6,7,8,9,10,11)
1
(11)
8
(1,2,6,7,8,9,10,11)
Bus-
5
3
(7,8,10)
3
(7,8,10)
3
(7,8,10)
3
(7,8,10)
Bus-
60 0 0 0
Bus-
70 0 0 0
Bus-
8
1
(10)
1
(10)
1
(10)
1
(10)
Bus-
90 0 0 0
Bus-
10 0 0 0 0
Bus-
11
6
(2,6,7,8,9,10)
6
(2,6,7,8,9,10)
07
(2,5,6,7,8,9,10)
Table 4.14 Voltage and current measurements for Bus-4 when Rfault = 1e−3 and f =
1000Hz
56
Msr
Inj
Bus-4
Voltase Current
Bus-4 Bus-4-Line-1 Bus-4-Line-2 Bus-4-Line-3
Bus-
1
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
Bus-
2
2
(6,9)
2
(6,9)
2
(6,9)
2
(6,9)
Bus-
3
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
Bus-
4
10
(1,2,3,5,6,7,8,9,10,11)
7
(2,5,6,7,8,9,10)
8
(2,5,6,7,8,9,10,11)
9
(1,2,3,5,6,7,8,9,10)
Bus-
5
3
(7,8,10)
3
(7,8,10)
3
(7,8,10)
3
(7,8,10)
Bus-
60 0 0 0
Bus-
70 0 0 0
Bus-
8
1
(10)
1
(10)
1
(10)
1
(10)
Bus-
90 0 0 0
Bus-
10 0 0 0 0
Bus-
11
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
Table 4.15 Voltage and current measurements for Bus-5 when Rfault = 1e−3 and f =
1000Hz
57
Msr
Inj
Bus-5
Voltase Current
Bus-5 Bus-5-Line-1 Bus-5-Line-2 Bus-5-Line-3
Bus-
1
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
Bus-
2
4
(4,6,9,11)
4
(4,6,9,11)
4
(4,6,9,11)
4
(4,6,9,11)
Bus-
3
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
4
1
(11)
1
(11)
1
(11)
1
(11)
Bus-
5
10
(1,2,3,4,6,7,8,9,10,
11)
7
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
Bus-
6
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
7
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
8
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
Bus-
9
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
10
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
11 0 0 0 0
Table 4.16 Voltage and current measurements for Bus-6, Bus-7, and Bus-8 when Rfault =
1e−3
and f=1000Hz
58
Measu
rement
Inj
Bus-6 Bus-7 Bus-8
Voltase Current Voltase Current Voltase Current
Bus-1 7
(3,4,5,7,8,1
0,11)
3
(3,4,11)
6
(2,3,4,6,9,1
1)
6
(2,3,4,6,9,1
1)
6
(2,3,4,6,9,1
1)
6
(2,3,4,6,9,
11)
Bus-2 9
(1,3,4,5,7,8,
9,10,11)
6
(3,4,7,9,10,
11)
4
(4,6,9,11)
4
(4,6,9,11)
4
(4,6,9,11)
4
(4,6,9,11)
Bus-3 2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-4 1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
Bus-5 5
(4,7,8,10,11
)
3
(4,7,11)
9
(1,2,3,4,6,8,
9,10,11)
9
(1,2,3,4,6,8,
9,10,11)
8
(1,2,3,4,6,7,
9,11)
8
(1,2,3,4,6,
7,9,11)
Bus-6 10
(1,2,3,4,5,7,
8,9,10,11)
10
(1,2,3,4,5,7,
8,9,10,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-7 2
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,
8,9,10,11)
10
(1,2,3,4,5,6,
8,9,10,11)
3
(3,4,11)
3
(3,4,11)
Bus-8 3
(4,10,11)
3
(4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
10
(1,2,3,4,5,6,
7,9,10,11)
9
(1,2,3,4,5,
6,7,9,11)
Bus-9 3
(3,4,11)
3
(3,4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-10 2
(4,11)
2
(4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-11 0 0 0 0 0 0
Table 4.17 Voltage and current measurements for Bus-9, Bus-10, and Bus-11 when Rfault
= 1e−3 and f = 1000Hz
59
Measu
rement
Inj
Bus-9 Bus-10 Bus-11
Voltase Current Voltase Current Voltase Current
Bus-1
7
(3,4,5,7,8,1
0,11)
7
(3,4,5,7,8,1
0,11)
6
(2,3,4,6,9,1
1)
6
(2,3,4,6,9,1
1)
7
(2,5,6,7,8,9
,10)
7
(2,5,6,7,8,9
,10)
Bus-2
9
(1,3,4,5,6,7,
8,10,11)
9
(1,3,4,5,6,7,
8,10,11)
4
(4,6,9,11)
4
(4,6,9,11)
2
(6,9)
2
(6,9)
Bus-3 2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
8
(1,2,5,6,7,8
,9,10)
8
(1,2,5,6,7,8
,9,10)
Bus-4 1
(11)
1
(11)
1
(11)
1
(11)
9
(1,2,3,5,6,7
,8,9,10)
9
(1,2,3,5,6,7
,8,9,10)
Bus-5
5
(4,7,8,10,11
)
5
(4,7,8,10,11
)
8
(1,2,3,4,6,7
,9,11)
8
(1,2,3,4,6,7
,9,11)
3
(7,8,10)
3
(7,8,10)
Bus-6 3
(3,4,11)
3
(3,4,11)
2
(4,11)
2
(4,11) 0 0
Bus-7 2
(4,11)
2
(4,11)
3
(3,4,11)
3
(3,4,11) 0 0
Bus-8 3
(4,10,11)
3
(4,10,11)
9
(1,2,3,4,5,6
,7,9,11)
9
(1,2,3,4,5,6
,7,9,11)
1
(10)
1
(10)
Bus-9
10
(1,2,3,4,5,6,
7,8,10,11)
10
(1,2,3,4,5,6,
7,8,10,11)
2
(4,11)
2
(4,11) 0 0
Bus-10 2
(4,11)
2
(4,11)
10
(1,2,3,4,5,6
,7,8,9,11)
10
(1,2,3,4,5,6
,7,8,9,11)
0 0
Bus-11 0 0 0 0
10
(1,2,3,4,5,6
,7,8,9,10)
10
(1,2,3,4,5,6
,7,8,9,10)
60
4.6 Current Measurement Results for Rfault = 1 and f = 1000Hz
Table 4.18 Voltage and current measurements for Bus-1 when Rfault = 1 and f = 1000Hz
Msr
Inj
Bus-1
Voltase Current
Bus-1 Bus-1-Line-1 Bus-1-Line-2 Bus-1-Line-3 Bus-1-Line-
4
Bus-
1
11
(1,2,3,4,5,6,7,8
,9,10,11)
4
(1,3,4,11)
10
(1,2,4,5,6,7,8,9,
10,11)
7
(1,2,3,4,6,9,11
)
8
(1,3,4,5,7,8,1
0,11)
Bus-
2
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
5
(2,4,6,9,11)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
Bus-
3
3
(3,4,11)
3
(3,4,11)
11
(1,2,3,4,5,6,7,8,
9,10,11)
3
(3,4,11)
3
(3,4,11)
Bus-
4
2
(4,11)
2
(4,11)
7
(1,6,7,8,9,10,11
)
2
(4,11)
2
(4,11)
Bus-
5
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,
11)
6
(4,5,7,8,10,11)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,
11)
Bus-
6
4
(3,4,6,11)
4
(3,4,6,11)
3
(4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
Bus-
7
4
(3,4,7,11) 4
(3,4,7,11)
3
(4,7,11)
7
(2,3,4,6,7,9,11
)
4
(3,4,7,11)
Bus-
8
5
(3,4,8,10,11) 5
(3,4,8,10,11)
4
(4,8,10,11)
8
(2,3,4,6,8,9,10
,11)
5
(3,4,8,10,11)
Bus-
9
4
(3,4,9,11)
4
(3,4,9,11)
3
(4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
Bus-
10
4
(3,4,10,11) 4
(3,4,10,11)
3
(4,10,11)
7
(2,3,4,6,9,10,1
1)
4
(3,4,10,11)
Bus-
11
1
(11)
1
(11)
7
(1,2,5,6,7,9,11)
1
(11)
1
(11)
Table 4.19 Voltage and current measurements for Bus-2 when Rfault = 1 and f =
1000Hz
61
Msr
Inj
Bus-2
Voltase Current
Bus-2 Bus-2-Line-1 Bus-2-Line-2 Bus-2-Line-3 Bus-2-Line-4
Bus-
1
8
(1,3,4,5,7,8,
10,11)
8
(1,3,4,5,7,8,10
,11)
8
(1,3,4,5,7,8,10
,11)
8
(1,3,4,5,7,8,10
,11)
8
(1,3,4,5,7,8,10,1
1)
Bus-
2
11
(1,2,3,4,5,6,
7,8,9,10,11)
4
(2,3,4,11)
6
(2,3,4,6,9,11)
10
(1,2,3,4,5,7,8,
9,10,11)
10
(1,2,3,4,5,6,7,8,
10,11)
Bus-
3
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
4
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
5
7
(3,4,5,7,8,10
,11)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,11)
Bus-
6
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
9
(1,3,4,5,6,7,8,
10,11)
4
(3,4,6,11)
Bus-
7
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
Bus-
8
5
(3,4,8,10,11)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
Bus-
9
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
9
(1,3,4,5,7,8,9,10
,11)
Bus-
10
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
Bus-
11
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
Table 4.20 Voltage and current measurements for Bus-3 when Rfault = 1 and f =
1000Hz
62
Msr
Inj
Bus-3
Voltase Current
Bus-3 Bus-3-Line-1 Bus-3-Line-2 Bus-3-Line-3
Bus-
1
8
(1,2,5,6,7,8,9,
10)
8
(1,2,5,6,7,8,9,10)
10
(1,2,4,5,6,7,8,9,10,11)
8
(1,2,5,6,7,8,9,10)
Bus-
2
3
(2,6,9)
3
(2,6,9)
5
(2,4,6,9,11)
3
(2,6,9)
Bus-
3
11
(1,2,3,4,5,6,7,
8,9,10,11)
9
(1,2,3,5,6,7,8,9,1
0)
11
(1,2,3,4,5,6,7,8,9,10,1
1)
9
(1,2,3,5,6,7,8,9,10
)
Bus-
4
10
(1,2,4,5,6,7,8,
9,10,11)
10
(1,2,4,5,6,7,8,9,1
0,11)
10
(1,2,4,5,6,7,8,9,10,11)
10
(1,2,4,5,6,7,8,9,10
,11)
Bus-
5
4
(5,7,8,10)
4
(5,7,8,10)
6
(4,5,7,8,10,11)
4
(5,7,8,10)
Bus-
6
1
(6)
1
(6)
3
(4,6,11)
1
(6)
Bus-
7
1
(7)
1
(7)
3
(4,7,11)
1
(7)
Bus-
8
2
(8,10)
2
(8,10)
4
(4,8,10,11)
2
(8,10)
Bus-
9
1
(9)
1
(9)
3
(4,9,11)
1
(9)
Bus-
10
1
(10)
1
(10)
3
(4,10,11)
1
(10)
Bus-
11
9
(1,2,5,6,7,8,9,
10,11)
9
(1,2,5,6,7,8,9,10,
11)
9
(1,2,5,6,7,8,9,10,11)
9
(1,2,5,6,7,8,9,10,1
1)
Table 4.21 Voltage and current measurements for Bus-4 when Rfault = 1 and f =
1000Hz
63
Msr
Inj
Bus-4
Voltase Current
Bus-4 Bus-4-Line-1 Bus-4-Line-2 Bus-4-Line-3
Bus-
1
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10
)
Bus-
2
3
(2,6,9)
3
(2,6,9)
3
(2,6,9)
3
(2,6,9)
Bus-
3
9
(1,2,3,5,6,7,8,9,10)
9
(1,2,3,5,6,7,8,9,1
0)
9
(1,2,3,5,6,7,8,9,10
)
9
(1,2,3,5,6,7,8,9,
10)
Bus-
4
11
(1,2,3,4,5,6,7,8,9,10
,11)
9
(1,2,4,5,6,7,8,9,1
0)
10
(1,2,4,5,6,7,8,9,10
,11)
10
(1,2,3,4,5,6,7,8,
9,10)
Bus-
5
4
(5,7,8,10)
4
(5,7,8,10)
4
(5,7,8,10)
4
(5,7,8,10)
Bus-
6
1
(6)
1
(6)
1
(6)
1
(6)
Bus-
7
1
(7)
1
(7)
1
(7)
1
(7)
Bus-
8
2
(8,10)
2
(8,10)
2
(8,10)
2
(8,10)
Bus-
9
1
(9)
1
(9)
1
(9)
1
(9)
Bus-
10
1
(10)
1
(10)
1
(10)
1
(10)
Bus-
11
9
(1,2,5,6,7,8,9,10,11)
9
(1,2,5,6,7,8,9,10,
11)
9
(1,2,5,6,7,8,9,10,1
1)
9
(1,2,5,6,7,8,9,10
,11)
Table 4.22 Voltage and current measurements for Bus-5 when Rfault = 1 and f =
1000Hz
64
Msr
Inj
Bus-5
Voltase Current
Bus-5 Bus-5-Line-1 Bus-5-Line-2 Bus-5-Line-3
Bus-
1
7
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
Bus-
2
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
Bus-
3
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
4
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
5
11
(1,2,3,4,5,6,7,8,9,
10,11)
8
(1,2,3,4,5,6,9,11)
8
(1,2,3,4,5,6,9,11)
8
(1,2,3,4,5,6,9,11)
Bus-
6
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
Bus-
7
7
(2,3,4,6,7,9,11)
7
(2,3,4,6,7,9,11)
7
(2,3,4,6,7,9,11)
7
(2,3,4,6,7,9,11)
Bus-
8
8
(2,3,4,6,8,9,10,11
)
8
(2,3,4,6,8,9,10,1
1)
8
(2,3,4,6,8,9,10,1
1)
8
(2,3,4,6,8,9,10,1
1)
Bus-
9
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
Bus-
10
7
(2,3,4,6,9,10,11)
7
(2,3,4,6,9,10,11)
7
(2,3,4,6,9,10,11)
7
(2,3,4,6,9,10,11)
Bus-
11
1
(11)
1
(11)
1
(11)
1
(11)
Table 4.23 Voltage and current measurements for Bus-6, Bus-7, and Bus-8 when Rfault = 1
and
f = 1000Hz
65
Measu
remen
t
Inj
Bus-6 Bus-7 Bus-8
Voltase Current Voltase Current Voltase Current
Bus-1 8
(1,3,4,5,7,8,
10,11)
8
(1,3,4,5,7,8,
10,11)
7
(1,2,3,4,6,9,
11)
7
(1,2,3,4,6,9,
11)
7
(1,2,3,4,6,9,
11)
7
(1,2,3,4,6,
9,11)
Bus-2 10
(1,2,3,4,5,7,
8,9,10,11)
10
(1,2,3,4,5,7,
8,9,10,11)
6
(2,3,4,6,9,1
1)
6
(2,3,4,6,9,1
1)
6
(2,3,4,6,9,1
1)
6
(2,3,4,6,9,
11)
Bus-3 3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-4 2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-5 7
(3,4,5,7,8,1
0,11)
7
(3,4,5,7,8,1
0,11)
10
(1,2,3,4,5,6,
8,9,10,11)
10
(1,2,3,4,5,6,
8,9,10,11)
9
(1,2,3,4,5,6,
8,9,11)
9
(1,2,3,4,5,
6,8,9,11)
Bus-6 11
(1,2,3,4,5,6,
7,8,9,10,11)
11
(1,2,3,4,5,6,
7,8,9,10,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
Bus-7 4
(3,4,7,11)
4
(3,4,7,11)
11
(1,2,3,4,5,6,
7,8,9,10,11)
11
(1,2,3,4,5,6,
7,8,9,10,11)
7
(2,3,4,6,7,9,
11)
7
(2,3,4,6,7,
9,11)
Bus-8 5
(3,4,8,10,11
)
5
(3,4,8,10,11
)
8
(2,3,4,6,8,9,
10,11)
8
(2,3,4,6,8,9,
10,11)
11
(1,2,3,4,5,6,
7,8,9,10,11)
10
(1,2,3,4,5,
6,7,8,9,11
)
Bus-9 4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
Bus-10 4
(3,4,10,11)
4
(3,4,10,11)
7
(2,3,4,6,9,1
0,11)
7
(2,3,4,6,9,1
0,11)
8
(1,2,3,4,6,9,
10,11)
7
(2,3,4,6,9,
10,11)
Bus-11 1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
Table 4.24 Voltage and current measurements for Bus-9, Bus-10, and Bus-11 when Rfault
= 1
and f=1000Hz
66
Measu
remen
t
Injecti
abov
e
Bus-9 Bus-10 Bus-11
Voltase Current Voltase Current Voltase Current
Bus-1
8
(1,3,4,5,7,8,
10,11)
8
(1,3,4,5,7,
8,10,11)
7
(1,2,3,4,6,9,
11)
7
(1,2,3,4,6,9,
11)
8
(1,2,5,6,7,8,
9,10)
8
(1,2,5,6,7,8,
9,10)
Bus-2
10
(1,2,3,4,5,6,
7,8,10,11)
9
(1,2,3,4,5,
6,7,10,11)
5
(2,3,4,6,11)
5
(2,3,4,6,11)
3
(2,6,9)
3
(2,6,9)
Bus-3 3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
9
(1,2,3,5,6,7,
8,9,10)
9
(1,2,3,5,6,7,
8,9,10)
Bus-4 2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
6
(4,5,6,7,8,9)
6
(1,5,6,7,8,9)
Bus-5 4
(7,8,10,11)
3
(7,10,11)
5
(5,6,7,9,11)
5
(5,6,7,9,11)
4
(5,7,8,10)
4
(5,7,8,10)
Bus-6 4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
1
(6)
1
(6)
Bus-7 4
(3,4,7,11)
4
(3,4,7,11)
5
(2,6,7,9,11)
5
(2,6,7,9,11)
1
(7)
1
(7)
Bus-8
5
(3,4,8,10,11
)
5
(3,4,8,10,
11)
10
(1,2,3,4,5,6,
7,8,9,11)
10
(1,2,3,4,5,6,
7,8,9,11)
2
(8,11)
2
(8,11)
Bus-9
11
(1,2,3,4,5,6,
7,8,9,10,11)
10
(1,2,3,4,5,
6,7,8,9,11
4
(3,4,9,11)
4
(3,4,9,11)
1
(9)
1
(9)
Bus-10 4
(3,4,10,11)
4
(3,4,10,11
)
11
(1,2,3,4,5,6,
7,8,9,10,11)
11
(1,2,3,4,5,6,
7,8,9,10,11)
1
(10)
1
(10)
Bus-11 1
(11)
1
(11)
1
(11)
1
(11)
11
(1,2,3,4,5,6,
7,8,9,10,11)
11
(1,2,3,4,5,6,
7,8,9,10,11)
67
4.7 Current Measurement Results for Rfault = 1e−3 and f = 7000Hz
Table 4.25 Voltage and current measurements for Bus-1 when Rfault = 1e−3 and f =
7000Hz
Msr
Inj
Bus-1
Voltase Current
Bus-1 Bus-1-Line-1 Bus-1-Line-2 Bus-1-Line-3 Bus-1-Line-4
Until
-1
10
(2,3,4,5,6,7,8,9,1
0,11)
1
(11)
7
(2,5,6,7,8,9,10
)
6
(2,3,4,6,9,11)
7
(3,4,5,7,8,10,
11)
Until
-2
4
(4,6,9,11)
4
(4,6,9,11)
2
(6,9)
4
(4,6,9,11)
4
(4,6,9,11)
Until
-3
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Until
-4
1
(11)
1
(11)
2
(9,11)
1
(11)
1
(11)
Until
-5
5
(4,7,8,10,11)
5
(4,7,8,10,11)
3
(7,8,10)
5
(4,7,8,10,11)
5
(4,7,8,10,11)
Until
-6
2
(4,11)
2
(4,11)
02
(4,11)
2
(4,11)
Until
-7
2
(4,11)
2
(4,11)
03
(3,4,11)
2
(4,11)
Until
-8
3
(4,10,11)
3
(4,10,11)
1
(10)
4
(3,4,10,11)
3
(4,10,11)
Until
-9
2
(4,11)
2
(4,11)
02
(4,11)
2
(4,11)
Until
-10
2
(4,11)
2
(4,11)
03
(3,4,11)
2
(4,11)
Until
-11 0 0 1
(9) 0 0
Table 4.26 Voltage and current measurements for Bus-2 when Rfault = 1e−3 and f =
7000Hz
68
Msr
Inj
Bus-2
Voltase Current
Bus-2 Bus-2-Line-1 Bus-2-Line-2 Bus-2-Line-3 Bus-2-Line-4
Bus-
1
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,
11)
Bus-
2
10
(1,3,4,5,6,7,8,9
,10,11)
2
(4,11)
4
(4,6,9,11)
9
(1,3,4,5,7,8,9,
10,11)
9
(1,3,4,5,6,7,8,
10,11)
Bus-
3
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
4
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
Bus-
5
5
(4,7,8,10,11)
5
(4,7,8,10,11)
5
(4,7,8,10,11)
4
(4,7,10,11)
5
(4,7,8,10,11)
Bus-
6
3
(3,4,11)
3
(3,4,11)
2
(4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
7
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
8
3
(4,10,11)
3
(4,10,11)
3
(4,10,11)
3
(4,10,11)
3
(4,10,11)
Bus-
9
3
(3,4,11)
3
(3,4,11)
2
(4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
10
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
11 0 0 0 0 0
Table 4.27 Voltage and current measurements for Bus-3 when Rfault = 1e−3 and f =
7000Hz
69
Msr
Inj
Bus-3
Voltase Current
Bus-3 Bus-3-Line-1 Bus-3-Line-2 Bus-3-Line-3
Bus-
1
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
Bus-
2
2
(6,9)
2
(6,9)
2
(6,9)
2
(6,9)
Bus-
3
10
(1,2,4,5,6,7,8,9,10,11)
2
(6,9)
2
(4,11)
8
(1,2,5,6,7,8,9,10)
Bus-
4
8
(2,5,6,7,8,9,10,11)
8
(2,5,6,7,8,9,10,11)
1
(11)
8
(1,2,6,7,8,9,10,11)
Bus-
5
3
(7,8,10)
3
(7,8,10)
3
(7,8,10)
3
(7,8,10)
Bus-
60 0 0 0
Bus-
70 0 0 0
Bus-
8
1
(10)
1
(10)
1
(10)
1
(10)
Bus-
90 0 0 0
Bus-
10 0 0 0 0
Bus-
11
6
(2,6,7,8,9,10)
6
(2,6,7,8,9,10)
07
(2,5,6,7,8,9,10)
Table 4.28 Voltage and current measurements for Bus-4 when Rfault = 1e−3 and f =
7000Hz
70
Msr
Inj
Bus-4
Voltase Current
Bus-4 Bus-4-Line-1 Bus-4-Line-2 Bus-4-Line-3
Bus-
1
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
Bus-
2
2
(6,9)
2
(6,9)
2
(6,9)
2
(6,9)
Bus-
3
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
Bus-
4
10
(1,2,3,5,6,7,8,9,10,11)
7
(2,5,6,7,8,9,10)
8
(2,5,6,7,8,9,10,11)
9
(1,2,3,5,6,7,8,9,10)
Bus-
5
3
(7,8,10)
3
(7,8,10)
3
(7,8,10)
3
(7,8,10)
Bus-
60 0 0 0
Bus-
70 0 0 0
Bus-
8
1
(10)
1
(10)
1
(10)
1
(10)
Bus-
90 0 0 0
Bus-
10 0 0 0 0
Bus-
11
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
7
(2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
Table 4.29 Voltage and current measurements for Bus-5 when Rfault = 1e−3 and f =
7000Hz
71
Msr
Inj
Bus-5
Voltase Current
Bus-5 Bus-5-Line-1 Bus-5-Line-2 Bus-5-Line-3
Bus-
1
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
Bus-
2
4
(4,6,9,11)
4
(4,6,9,11)
4
(4,6,9,11)
4
(4,6,9,11)
Bus-
3
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
4
1
(11)
1
(11)
1
(11)
1
(11)
Bus-
5
10
(1,2,3,4,6,7,8,9,10,11)
7
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
Bus-
6
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
7
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
8
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
Bus-
9
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
10
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
11 0 0 0 0
Table 4.30 Voltage and current measurements for Bus-6, Bus-7, and Bus-8 when Rfault =
1e−3
and f=7000Hz
72
Msr
Inj
Bus-6 Bus-7 Bus-8
Voltase Current Voltase Current Voltase Current
Bus-
1
7
(3,4,5,7,8,
10,11)
7
(3,4,5,7,8,1
0,11)
6
(2,3,4,6,9,11
)
6
(2,3,4,6,9,11
)
6
(2,3,4,6,9,1
1)
6
(2,3,4,6,9,1
1)
Bus-
2
9
(1,3,4,5,7,
8,9,10,11)
9
(1,3,4,5,7,8,
9,10,11)
4
(4,6,9,11)
4
(4,6,9,11)
4
(4,6,9,11)
4
(4,6,9,11)
Bus-
3
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
4
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
Bus-
5
5
(4,7,8,10,1
1)
4
(4,7,10,11)
9
(1,2,3,4,6,8,
9,10,11)
9
(1,2,3,4,6,8,
9,10,11)
8
(1,2,3,4,6,7
,9,11)
8
(1,2,3,4,6,7
,9,11)
Bus-
6
10
(1,2,3,4,5,
7,8,9,10,1
1)
10
(1,2,3,4,5,7,
8,9,10,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
7
2
(4,11)
2
(4,11)
10
(1,2,3,4,5,6,
8,9,10,11)
10
(1,2,3,4,5,6,
8,9,10,11)
3
(3,4,11)
3
(3,4,11)
Bus-
8
3
(4,10,11)
3
(4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
10
(1,2,3,4,5,6
,7,9,10,11)
9
(1,2,3,4,5,6
,7,9,11)
Bus-
9
3
(3,4,11)
3
(3,4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
10
2
(4,11)
2
(4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
11 0 0 0 0 0 0
Table 4.31 Voltage and current measurements for Bus-9, Bus-10, and Bus-11 when Rfault
= 1e−3 and f = 7000Hz
73
Msr
Instr
uctio
ns
Bus-9 Bus-10 Bus-11
Voltase Current Voltase Current Voltase Current
Bus-
1
7
(3,4,5,7,8,1
0,11)
7
(3,4,5,7,8,10
,11)
6
(2,3,4,6,9,
11)
6
(2,3,4,6,9,11)
7
(2,5,6,7,8,
9,10)
7
(2,5,6,7,8,
9,10)
Bus-
2
9
(1,3,4,5,6,7
,8,10,11)
9
(1,3,4,5,6,7,
8,10,11)
4
(4,6,9,11)
4
(4,6,9,11)
2
(6,9)
2
(6,9)
Bus-
3
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
8
(1,2,5,6,7,
8,9,10)
8
(1,2,5,6,7,
8,9,10)
Bus-
4
1
(11)
1
(11)
1
(11)
1
(11)
9
(1,2,3,5,6,
7,8,9,10)
9
(1,2,3,5,6,
7,8,9,10)
Bus-
5
5
(4,7,8,10,1
1)
5
(4,7,8,10,11)
8
(1,2,3,4,6,
7,9,11)
8
(1,2,3,4,6,7,9
,11)
3
(7,8,10)
3
(7,8,10)
Bus-
6
3
(3,4,11)
3
(3,4,11)
2
(4,11)
2
(4,11) 0 0
Bus-
7
2
(4,11)
2
(4,11)
3
(3,4,11)
3
(3,4,11) 0 0
Bus-
8
3
(4,10,11)
3
(4,10,11)
9
(1,2,3,4,5,
6,7,9,11)
9
(1,2,3,4,5,6,7
,9,11)
1
(10)
1
(10)
Bus-
9
10
(1,2,3,4,5,6
,7,8,10,11)
10
(1,2,3,4,5,6,
7,8,10,11)
2
(4,11)
2
(4,11) 0 0
Bus-
10
2
(4,11)
2
(4,11)
10
(1,2,3,4,5,
6,7,8,9,11)
10
(1,2,3,4,5,6,7
,8,9,11)
0 0
Bus-
11 0 0 0 0
10
(1,2,3,4,5,
6,7,8,9,10)
10
(1,2,3,4,5,
6,7,8,9,10)
74
4.8 Current Measurement Results for Rfault = 1 and f = 7000Hz
Table 4.32 Voltage and current measurements for Bus-1 when Rfault = 1 and f = 7000Hz
Mr
s.
R
Inj
Bus-1
Voltase Current
Bus-1 Bus-1-Line-1 Bus-1-Line-2 Bus-1-Line-3 Bus-1-Line-4
Until
-1
11
(1,2,3,4,5,6,7,
8,9,10,11)
4
(1,3,4,11)
8
(1,2,5,6,7,8,9,
10)
7
(1,2,3,4,6,9,11
)
8
(1,3,4,5,7,8,10
,11)
Until
-2
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
3
(2,6,9)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
Until
-3
3
(3,4,11)
3
(3,4,11)
6
(2,3,4,6,9,11)
3
(3,4,11)
3
(3,4,11)
Until
-4
2
(4,11)
2
(4,11)
5
(2,4,6,9,11)
2
(4,11)
2
(4,11)
Until
-5
7
(3,4,5,7,8,10,
11)
7
(3,4,5,7,8,10,1
1)
4
(5,7,8,10)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,1
1)
Until
-6
4
(3,4,6,11)
4
(3,4,6,11)
1
(6)
4
(3,4,6,11)
4
(3,4,6,11)
Until
-7
4
(3,4,7,11)
4
(3,4,7,11)
1
(7)
4
(3,4,7,11)
4
(3,4,7,11)
Until
-8
5
(3,4,8,10,11)
5
(3,4,8,10,11)
2
(8,10)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
Until
-9
4
(3,4,9,11)
4
(3,4,9,11)
1
(9)
4
(3,4,9,11)
4
(3,4,9,11)
Until
-10
4
(3,4,10,11)
4
(3,4,10,11)
1
(10)
4
(3,4,10,11)
4
(3,4,10,11)
Until
-11
1
(11)
1
(11)
4
(2,6,9,11)
1
(11)
1
(11)
Table 4.33 Voltage and current measurements for Bus-2 when Rfault = 1 and f =
7000Hz
75
Msr
Inj
Bus-2
Voltase Current
Bus-2 Bus-2-Line-
1Bus-2-Line-2 Bus-2-Line-3 Bus-2-Line-4
Bus-
1
8
(1,3,4,5,7,8,
10,11)
8
(1,3,4,5,7,8,1
0,11)
8
(1,3,4,5,7,8,10
,11)
8
(1,3,4,5,7,8,10
,11)
8
(1,3,4,5,7,8,10,
11)
Bus-
2
11
(1,2,3,4,5,6,
7,8,9,10,11)
4
(2,3,4,11)
6
(2,3,4,6,9,11)
10
(1,2,3,4,5,7,8,
9,10,11)
10
(1,2,3,4,5,6,7,8
,10,11)
Bus-
3
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
4
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
5
7
(3,4,5,7,8,10
,11)
7
(3,4,5,7,8,10,
11)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,1
1)
7
(3,4,5,7,8,10,1
1)
Bus-
6
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
Bus-
7
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
Bus-
8
5
(3,4,8,10,11)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
Bus-
9
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
Bus-
10
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
Bus-
11
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
Table 4.34 Voltage and current measurements for Bus-3 when Rfault = 1 and f =
7000Hz
76
Msr
Inj
Bus-3
Voltase Current
Bus-3 Bus-3-Line-1 Bus-3-Line-2 Bus-3-Line-3
Until
-1
8
(1,2,5,6,7,8,9,10
)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
Until
-2
3
(2,6,9)
3
(2,6,9)
3
(2,6,9)
3
(2,6,9)
Until
-3
11
(1,2,3,4,5,6,7,8,9
,10,11)
9
(1,2,3,5,6,7,8,9,10
)
5
(3,4,6,9,11)
9
(1,2,3,5,6,7,8,9,10
)
Until
-4
10
(1,2,4,5,6,7,8,9,1
0,11)
10
(1,2,4,5,6,7,8,9,10
,11)
5
(2,4,6,9,11)
10
(1,2,4,5,6,7,8,9,10
,11)
Until
-5
4
(5,7,8,10)
4
(5,7,8,10)
4
(5,7,8,10)
4
(5,7,8,10)
Until
-6
1
(6)
1
(6)
1
(6)
1
(6)
Until
-7
1
(7)
1
(7)
1
(7)
1
(7)
Until
-8
2
(8,10)
2
(8,10)
2
(8,10)
2
(8,10)
Until
-9
1
(9)
1
(9)
1
(9)
1
(9)
Until
-10
1
(10)
1
(10)
1
(10)
1
(10)
Until
-11
9
(1,2,5,6,7,8,9,10,
11)
9
(1,2,5,6,7,8,9,10,1
1)
4
(2,6,9,11)
9
(1,2,5,6,7,8,9,10,1
1)
Table 4.35 Voltage and current measurements for Bus-4 when Rfault = 1 and f =
7000Hz
77
Msr
Inj
Bus-4
Voltase Current
Bus-4 Bus-4-Line-1 Bus-4-Line-2 Bus-4-Line-3
Until
-1
8
(1,2,5,6,7,8,9,10
)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
8
(1,2,5,6,7,8,9,10)
Until
-2
3
(2,6,9)
3
(2,6,9)
3
(2,6,9)
3
(2,6,9)
Until
-3
9
(1,2,3,5,6,7,8,9,1
0)
9
(1,2,3,5,6,7,8,9,10)
9
(1,2,3,5,6,7,8,9,10)
9
(1,2,3,5,6,7,8,9,10)
Until
-4
11
(1,2,3,4,5,6,7,8,9
,10,11)
9
(1,2,4,5,6,7,8,9,10)
10
(1,2,4,5,6,7,8,9,10,
11)
10
(1,2,3,4,5,6,7,8,9,1
0)
Until
-5
4
(5,7,8,10)
4
(5,7,8,10)
4
(5,7,8,10)
4
(5,7,8,10)
Until
-6
1
(6)
1
(6)
1
(6)
1
(6)
Until
-7
1
(7)
1
(7)
1
(7)
1
(7)
Until
-8
2
(8,10)
2
(8,10)
2
(8,10)
2
(8,10)
Until
-9
1
(9)
1
(9)
1
(9)
1
(9)
Until
-10
1
(10)
1
(10)
1
(10)
1
(10)
Until
-11
9
(1,2,5,6,7,8,9,10,
11)
9
(1,2,5,6,7,8,9,10,1
1)
9
(1,2,5,6,7,8,9,10,1
1)
9
(1,2,5,6,7,8,9,10,1
1)
Table 4.36 Voltage and current measurements for Bus-5 when Rfault = 1 and f =
7000Hz
78
Msr
Inj
Bus-5
Voltase Current
Bus-5 Bus-5-Line-1 Bus-5-Line-2 Bus-5-Line-3
Bus-
1
7
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
7
(1,2,3,4,6,9,11)
Bus-
2
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
Bus-
3
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Bus-
4
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Bus-
5
11
(1,2,3,4,5,6,7,8,9,10,11)
8
(1,2,3,4,5,6,9,11)
8
(1,2,3,4,5,6,9,11)
8
(1,2,3,4,5,6,9,11)
Bus-
6
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
Bus-
7
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
Bus-
8
5
(3,4,8,10,11)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
5
(3,4,8,10,11)
Bus-
9
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
Bus-
10
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
Bus-
11
1
(11)
1
(11)
1
(11)
1
(11)
Table 4.37 Voltage and current measurements for Bus-6, Bus-7, and Bus-8 when Rfault = 1
and
f=7000Hz
79
M
rs.
r
Inj
Bus-6 Bus-7 Bus-8
Voltase Current Voltase Current Voltase Current
Until
-1
8
(1,3,4,5,7,8
,10,11)
8
(1,3,4,5,7,8,
10,11)
7
(1,2,3,4,6,9
,11)
7
(1,2,3,4,6,9
,11)
7
(1,2,3,4,6,9,1
1)
7
(1,2,3,4,6,
9,11)
Until
-2
10
(1,2,3,4,5,7
,8,9,10,11)
10
(1,2,3,4,5,7,
8,9,10,11)
6
(2,3,4,6,9,1
1)
6
(2,3,4,6,9,1
1)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,
11)
Until
-3
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
Until
-4
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
Until
-5
7
(3,4,5,7,8,1
0,11)
7
(3,4,5,7,8,1
0,11)
10
(1,2,3,4,5,6
,8,9,10,11)
10
(1,2,3,4,5,6
,8,9,10,11)
9
(1,2,3,4,5,6,8
,9,11)
9
(1,2,3,4,5,
6,8,9,11)
Until
-6
11
(1,2,3,4,5,6
,7,8,9,10,1
1)
11
(1,2,3,4,5,6,
7,8,9,10,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
Until
-7
4
(3,4,7,11)
4
(3,4,7,11)
11
(1,2,3,4,5,6
,7,8,9,10,11
)
11
(1,2,3,4,5,6
,7,8,9,10,11
)
4
(3,4,7,11)
4
(3,4,7,11)
Until
-8
5
(3,4,8,10,1
1)
5
(3,4,8,10,11
)
5
(3,4,8,10,1
1)
5
(3,4,8,10,1
1)
11
(1,2,3,4,5,6,7
,8,9,10,11)
10
(1,2,3,4,5,
6,7,8,9,11)
Until
-9
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
4
(3,4,9,11)
Until
-10
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
4
(3,4,10,11)
Until
-11
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
1
(11)
Table 4.38 Voltage and current measurements for Bus-9, Bus-10, and Bus-11 when Rfault
= 1
and f=7000Hz
80
Mr
s. r
Inj
Bus-9 Bus-10 Bus-11
Voltase Current Voltase Current Voltase Current
Until
-1
8
(1,3,4,5,7,8,
10,11)
8
(1,3,4,5,7,8,1
0,11)
7
(1,2,3,4,6,9,1
1)
7
(1,2,3,4,6,9,1
1)
8
(1,2,5,6,7,
8,9,10)
8
(1,2,5,6,7,
8,9,10)
Until
-2
10
(1,2,3,4,5,6,
7,8,10,11)
10
(1,2,3,4,5,6,7
,8,10,11)
6
(2,3,4,6,9,11)
6
(2,3,4,6,9,11)
3
(2,6,9)
3
(2,6,9)
Until
-3
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
3
(3,4,11)
4
(1,2,3,10)
9
(1,2,3,10)
Until
-4
2
(4,11)
2
(4,11)
2
(4,11)
2
(4,11)
10
(1,2,3,4,5,
6,7,8,9)
10
(1,2,3,4,5,
6,7,8,9)
Until
-5
7
(3,4,5,7,8,1
0,11)
7
(3,4,5,7,8,10,
11)
9
(1,2,3,4,5,6,7
,9,11)
9
(1,2,3,4,5,6,7
,9,11)
4
(5,7,8,10)
4
(5,7,8,10)
Until
-6
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
4
(3,4,6,11)
1
(6)
1
(6)
Until
-7
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
4
(3,4,7,11)
1
(7)
1
(7)
Until
-8
5
(3,4,8,10,11
5
(3,4,8,10,11
5
(5,7,8,9,11)
5
(5,7,8,9,11)
2
(8,11)
2
(8,11)
Until
-9
11
(1,2,3,4,5,6,
7,8,9,10,11)
11
(1,2,3,4,5,6,7
,8,9,10,11)
4
(3,4,9,11)
4
(3,4,9,11)
1
(9)
1
(9)
Until
-10
4
(3,4,10,11)
4
(3,4,10,11)
11
(1,2,3,4,5,6,7
,8,9,10,11)
11
(1,2,3,4,5,6,7
,8,9,10,11)
1
(10)
1
(10)
Until
-11
1
(11)
1
(11)
1
(11)
1
(11)
9
(1,3,5,6,7,
8,9,10,11
9
(1,3,5,6,7,
8,9,10,11
As shown in the table, current measurements can provide better results with fewer undetected
buses and less multi-estimation over voltage measurements.
81
CHAPTER 5
CONCLUSION
Conclusion
In this thesis, a new method for locating faults in the ship's power system is proposed
using the applied voltage and the voltage/current measured when a fault occurs in the system.
The system is tested for all possible buses for injection and measurement and the optimal point
leading to the minimum number of injections and measurements in the system is found. The
proposed approach generalizes the Active Impedance Estimation (AIE) error location method
where the injection and measurement do not have to be in the same location. Also, it was shown
that by increasing the frequency of multi-estimation injections was significantly reduced. The
proposed approach is a reliable and economical method that can find fault locations in the ship's
power system with a minimum number of injections and measurements.
82
LIFE
Pedram Jahanmard was born in 1990 in Iran. He received his BS in Electrical
Engineering from Azad Islamic University, Najafabad, Esfahan, Iran in 2013. His current
research interests include Fault Location, Ship Power Systems, Protection, Intelligent Networks,
and Micronetworks.
Students also viewed