power systems/ PSCAD/EMTDC/MATLAB/POWER LAB
ECE 43200/53201 Power Systems Fall 2020
1
AC Transmission Lines Components and Electrical Parameters
Transmission lines are used to transfer large amounts of electrical power over long distances. Most
transmission systems use extra-high voltage ac overhead lines for long-distance energy transport, [1],
[2].
There are also few high-voltage dc (HVDC) transmission systems for point-to-point power transport, long
distance bulk energy transfer, which are highly effective (there is no inductive voltage drop). Typical
examples are the HVDC lines which interconnects Los Angeles with Oregon, and the interconnection
between France and England using underwater cables, [1]. High-voltage ac lines are often used to
connect power plants to a city. A typical example is the high-voltage transmission system between
Hoover Dam and Las Vegas, Nevada. Within a city, sub-transmission lines connect the distribution
substations together, and distribution lines, originating from the substations, supply the energy to the
residential and commercial customers. In congested cities, some transmission lines are replaced by
underground cables.
In this chapter we describe the construction and components of the transmission lines. We address the
most important environmental effects of the transmission lines, that is, the electric and magnetic fields.
The chapter derives equations for calculation of transmission line resistance, inductance, and
capacitance; introduces equivalent circuit for the line and present analysis methods to evaluate line
performance.
The transmission lines commonly consist of three-phases and they can be categorized according to their
voltages as follows, [1]:
Extra-high-voltage lines
▪ Voltage: 345 kV, 500 kV, 765 kV ▪ Interconnection between systems
High-voltage lines
▪ Voltage: 115 kV, 230 kV ▪ Interconnection between substations, power plants
Sub-transmission lines
▪ Voltage: 46 kV, 69 kV ▪ Interconnection between substations and large industrial customers
Distribution lines
▪ Voltage: 2.4 kV to 46 kV, with 15 kV being the most commonly used ▪ Supplies residential and commercial customers
High-voltage DC lines
▪ Voltage: ±120 kV to ±600 kV ▪ Interconnection between regions (e.g., Oregon-California)
ECE 43200/53201 Power Systems Fall 2020
2
Fig.1 shows typical extra-high-voltage (EHV) transmission systems, with two different high-voltage
transmission lines [1].
(a) (b)
Fig.1 Transmission line systems with two high-voltage lines using
(a) a more aesthetic steel tube tower; (b) a steel lattice tower.
Fig. 1(b) shows the transmission line with two-conductor bundles per phase, to reduce the corona effect
and generation of (radio and television) noise. The shield conductors at the top of the towers are
grounded to protect each line against lightning.
An EHV transmission line requires towers more than 100 ft. tall and a 200-300-ft-wide corridor. These
lines (see Fig.1) are not an aesthetically pleasing sight, and the general public wants the lines be located
far from their backyard. An additional problem is the people's aversion to electric and magnetic fields
generated by the lines, although any adverse health effects from these fields has been proven.
These considerations have led to the development of transmission line corridors with several lines remote
from populated areas as much as possible.
Sub-transmission lines are used to interconnect substations and to locally distribute energy within a
city or rural area. These lines are supported with a steel tube (on a concrete foundation) or wood tower
(frequently placed in the ground without a foundation). A single conductor is usually used in each phase
because the lower sub-transmission voltage reduces the corona generation, although multiple conductors
per phase may be used to increase the current-carrying capability of the line. The conductors are
supported by post insulators without a cross-arm, or may be supported by suspension insulators attached
to a cross-arm. Lightning protection might be achieved using one grounded shield conductor placed on top
of the tower. The shield conductor is grounded at each tower. A plate or vertical tube electrode (ground
rod) is used for grounding.
ECE 43200/53201 Power Systems Fall 2020
3
Fig.2 shows a typical double-circuit 69 kV sub-transmission line with a wooden pole. This line
carries two three-phase circuits and is located along major city streets and roadways. Note the 12.47
kV distribution line under the 69 kV line and the communication cables under the 12.47 kV circuit.
Fig.2 A typical double circuit sub-transmission line, [1]
Distribution lines supply electricity to the residential and commercial buildings.
(A) In rural areas, there are overhead distribution lines that mostly employ a wood tower with cross-
arm(s). Some utilities use concrete towers. The wood is treated with creosote to protect against rotting.
A simple concrete block foundation or no foundation is used. Small porcelain or plastic post insulators
hold the conductors. The insulator shaft is grounded, to eliminate leakage current from causing the
wood tower to ignite and burn. A simple steel rod is used for grounding. A shield conductor is
seldom used.
Fig.3 shows a distribution line with a 240 V voltage cable connection and pole-mounted transformers
that supplies houses in a neighborhood. The distribution line has four conductors; one of them
(second from the right) is the grounded neutral conductor. A 240/120 V service cable is attached
under the distribution line. The line supplies each transformer through a fuse and a disconnect
switch. The single-phase pole-mounted transformers are installed under the cable connection. The
low voltage 240/120 V line supplies nearby homes. For better utilization of the tower, telephone
and/or cable television lines are often attached to the pole under the transformer.
ECE 43200/53201 Power Systems Fall 2020
4
Fig.3 A distribution line with pole-mounted transformers
and service cable connection, [1]
Figures 1 - 3 illustrate that the conductors are suspended on the poles, and the distance between the
poles is called the span, and it varies between 100 to 1500 ft., depending on the voltage. A
conductor, which is hung between two points, sags (from the horizontal position). The sag varies with
the conductor temperature, wind, and icing conditions. In summer, the sag is significantly larger than in
the winter. The sag determines the distance between the conductors and the ground. The National
Electrical Safety Code (ANSI C2-1997, p.232B1) specifies the minimum distance, depending on the line
voltage and the use of the land below the line. As an example, below a 22 kV line the minimum
distance must be more than 14.5 ft. if the land is used for pedestrian traffic.
High wind and icing can damage the conductors, and the lines may clap in stormy weather. In order to
limit line damage, tension towers are used to carry tangential, transverse and vertical loads. The
supporting tower (carrying the conductors) carries only transverse and vertical loads. The advantage of
this construction is that any storm damage may be limited to one section that is terminated with
tension towers at each end.
The tension in the conductor depends on the conductor weight, the ambient temperature, wind, ice,
and the sag at the time of installation. During operation, the maximum tension occurs at wintertime.
The sag calculation must consider the ambient temperature, conductor tensile strength, wind, and ice
loading on the line.
(B) In urban areas most new construction uses underground cables placed in concrete ducts, which protect
the cables, and simplify maintenance and replacement of faulty cable sections.
Fig.4 shows a typical section of an urban distribution cable system installation. The figure shows the
concrete duct banks with low-voltage cables. Manholes, placed in the street or easement (e.g., front or
back yard), divide the cable system into sections. In the case of a cable fault, the faulty cable is cut,
pulled out, and replaced. The figure shows the transformer and related switchgear placed in a sidewalk
vault.
ECE 43200/53201 Power Systems Fall 2020
5
Fig.4 Underground grid network - cutaway view, [1]
High-voltage 230 kV-69 kV cables are used in large municipalities, such as Chicago and New York,
to supply urban substations located in the middle of the city. These cables carry several hundred
megawatts of power to supply skyscrapers and other urban loads.
1. Components of the AC Transmission Lines
The major components of the transmission line are: the three-phase conductors, the insulators, which
support and electrically isolate the conductors, the tower, which holds the insulators and conductors,
the foundation and grounding, and optional shield conductors, which protect against lightning.
Towers and Foundations
The most frequently used tower types are, [1]:
▪ Lattice tower, used for 220 kV and above ▪ Guyed lattice tower, 345 kV and above ▪ Tapered steel tube with cross-arm, 230 kV and below ▪ Concrete tower, for distribution and sub-transmission, and ▪ Wood tower, for distribution.
Most of the metal towers are stabilized by a concrete foundation and grounded. Buried copper rods or
plates are used for grounding. The grounding resistance determines the lightning strike caused
overvoltage. Overvoltage occurs when the voltage is more than 10%-20% greater than the rated voltage.
Good grounding will limit overvoltage.
Conductors for Overhead Lines
Aluminum has replaced copper as the most common conductor metal for overhead transmission.
Although a larger aluminum cross-sectional area is required to obtain the same loss as in a copper
conductor, aluminum has a lower cost and lighter weight. Also, the supply of aluminum is abundant,
whereas that of copper is limited, [3].
Typical phase conductors are, [1]:
ECE 43200/53201 Power Systems Fall 2020
6
▪ Aluminum Conductor Steel Reinforced (ACSR) ▪ All Aluminum Conductor (AAC), and ▪ All Aluminum Alloy Conductor (AAAC) ▪ Aluminum Conductor Alloy-Reinforced (ACAR)
Typical shield conductors are:
▪ Aluminum-Clad Steel (Alumoweld), and ▪ Extra-High-Strength Steel.
Fig.5 Typical ACSR conductor (54/7 Cardinal), [3]
One of the most common conductor types is aluminum conductor steel-reinforced (ACSR), [2], [3],
which consists of layers of aluminum strands surrounding a central core of steel strands, as shown in
Fig.5. Stranded conductors are easier to manufacture, since larger conductor sizes can be obtained by
simply adding successive layers of strands. Stranded conductors are also easier to handle and more
flexible than solid conductors, especially in larger sizes. The use of steel strands gives ACSR conductors
a high strength-to-weight ratio. For purposes of heat dissipation, overhead transmission-line conductors
are bare (no insulating cover).Most frequently used is ACSR, which has a stranded steel center core and
one to four outside layers of aluminum strands.
(a) (b)
Fig.6 (a) Typical bundled conductors’ arrangements [1];
(b) three-conductor bundle, 500 KV line [2]
Bundled conductors are used for lines above 220 kV to minimize the electric field strength at the
conductor surface to reduce the corona effect and to increase current-carrying capacity. The bundled
conductor contains 2, 3, or 4 conductors in each phase (Fig.6(a)). The distance (d) between the
conductors is 12-18 inches, which is maintained by aluminum bars (spacers) placed at 20-50 ft.
distances along a span.
Rough estimates of the cost of such lines are available for different transmission voltages.
For example, a 345 kV line costs range from 500,000 dollars per mile (1.6km) in rural areas to over
2 million dollars per mile in urban areas of the state of Minnesota (in 2006, [2]).
ECE 43200/53201 Power Systems Fall 2020
7
Underground Cables
In many cities and residential areas, transmission lines are opposed because of environmental and
aesthetical concerns in addition to lack of space for large towers. In these areas, the electrical energy
is transported and distributed by underground cables. The underground cables are insulated
conductors that are buried in the ground or placed in underground concrete cable ducts. Most cables
are placed in concrete ducts, although older installations use directly buried cables. This has been
found to be undesirable because cable life is significantly reduced.
Fig.7 Three-phase distribution cable with solid dielectric
Fig. 7 shows a typical, three-phase distribution cable, with a solid dielectric, that is used in
residential areas. The cable uses three stranded aluminum conductors, which are surrounded by a
semiconducting shield layer that produces a smooth surface and reduces the stranding-caused
electrical field concentration. Solid PEX dielectric provides insulation for each conductor. A
grounded semiconducting layer covers the conductor insulation to assure a cylindrical field
distribution. Fillers are placed between the phases to assure a cylindrical cross-section. A grounded
copper wire surrounding the insulated phase conductors forms the outside shield. Finally, the
weather and water-resistant PVC sheet protects the cable from the environment.
Insulators [1]
Ball-and-socket type insulators composed of porcelain or toughened glass are used for most high-
voltage lines. These are also referred to as "cap-and-pin" insulators. The cross-section of a ball-and-
socket type insulator is shown in Fig.8.
Fig.8 Porcelain insulator (cap-and -pin)
ECE 43200/53201 Power Systems Fall 2020
8
The porcelain skirt provides insulation between the iron cap and steel pin. The upper part of the
porcelain is smooth, to promote rain washing and cleaning of the surface. The bottom part is corrugated,
which prevents wetting and provides a longer protected leakage path. Portland cement is used to attach
the cap and pin.
The ball-and-socket insulators are attached to each other by inserting the ball in the socket and securing
the connection by a locking key. Several insulators are connected together to form an insulator string.
Strings of insulators are frequently used for transmission lines. Insulators strings are arranged vertically
on support towers (see Fig.1), and near horizontally on dead-end (tension) towers.
Porcelain post insulators are often used to support sub-transmission lines. These insulators replace the
cross-arm of the towers, as shown in Fig.2. The post insulator consists of a porcelain column, with
weather skirts or corrugation on the outside surface to increase leakage distance. For indoor use, the
outer surface is corrugated. For outdoor use, a deeper weather shed is used. The end fitting seals the
inner part of the tube, to prevent water penetration.
Growing industrial pollution increased the number of flashovers on porcelain insulator strings.
Flashover occurs when an arc bridges an insulator, thereby providing a conduction path between the line
and ground. This motivated the development of pollution-resistant non-ceramic (composite) insulators.
Composite insulators are built with mechanical load-bearing fiberglass rods, which are covered by
rubber weather sheds to assure high electrical strength. End fittings connect the insulator to a tower or
conductor.
All high-voltage composite insulators use rubber weather sheds installed on fiberglass rods. The interface
between the weather-shed, fiberglass rod, and the end fittings is carefully sealed to prevent water
penetration. The most serious insulator failure is caused by water penetration to the interface. The most
frequently used materials are silicon rubber, EPDM (ethylene propylene diene monomer) rubber, and the
alloy of the two. The direct molding of the sheds to the fiberglass rod produces high-quality insulators
and is the best approach, although other methods are used successfully. The rubber contains fillers and
additive agents to prevent discharge-caused tracking and erosion.
Post composite insulators are frequently used on medium- and low-voltage lines. This type of
insulator has a fiberglass core covered by a silicon or EPDM rubber weather-shed.
2. Transmission Line Electrical Parameters
The equivalent transmission line circuits for a balanced system are presented at the end of this section.
These circuits are usually referred to as the positive sequence transmission line equivalent circuits.
The transmission line parameters are the resistance R and the inductance L of the conductors, and the
capacitance C to neutral. These parameters are calculated per unit line length and per phase.
The line carries balanced current and is transposed (see Fig.15). This permits the representation of the
line by a single-phase circuit, which corresponds to phase A. The currents and voltages in phases B
and C are shifted by 120° and 240°, respectively. The single-phase equivalent circuit carries one-third
of the line power and is supplied by the line-to-neutral voltage.
The conductors of transmission lines have temperature and frequency dependent electric resistance (R). In
addition, when the transmission lines are energized and carry current, the current produces a magnetic
ECE 43200/53201 Power Systems Fall 2020
9
field, and the electric charge creates an electric field around the line. The results of the generated fields
are the line inductance (L), and line capacitance (C), which are distributed parameters all through the
length of the line.
Next, the conductance, G, parameter is discussed briefly which is usually neglected in the analysis.
2.1 Conductance G
Conductance accounts for real power loss between conductors or between conductors and ground, [3].
For overhead lines, this power loss is due to leakage currents at insulators and to corona effect where
the surrounding air is ionized and a hissing sound can be heard in misty, foggy weather [2] .
Insulator leakage current depends on the amount of dirt, salt, and other contaminants that have
accumulated on insulators, as well as on meteorological factors, particularly the presence of moisture.
Corona occurs when a high value of electric field strength at a conductor surface causes the air to
become electrically ionized and to conduct. The real power loss due to corona, called corona loss,
depends on meteorological conditions, particularly rain, and on conductor surface irregularities. Losses
due to insulator leakage and corona are usually small compared to conductor I2R loss. Conductance is
usually neglected in power system studies because it is a very small component of the shunt
admittance, and thus in our future analysis the presence of conductance G will be neglected also.
Fig.9 Transmission line distributed parameter model per-phase [2]
Assuming the three phases of the transmission line to be balanced, the line parameters on a per-phase basis
can be easily be calculated, as shown in Fig.9, where the bottom conductor is neutral (in general,
hypothetical) that carries no current in an ideally balanced three-phase arrangement and under a
balanced sinusoidal steady state operation.
For unbalanced arrangements including the effect of the ground plane and the shield wires, computer
programs such as PSCAD/EMTDC and EMTP are available that can also include frequency dependence of
the transmission line parameters, [2].
2.2 Line Resistance, R
The resistance of a transmission line in per unit length of the line (in units Ω/m) is designed to be small to
minimize I2R power losses. These losses go down as the conductor size is increased but the costs of
conductors and towers go up. In the U.S., the Department of Energy estimates that approximately 9% of
the generated electricity is lost in transmission and distribution. Therefore, it is important to keep the
transmission line resistance small.
In a bundled arrangement, it is the parallel resistance of the bundled conductors that is of consideration. The
calculation of the stranded conductor ac resistance is complicated and the results are inaccurate. The
practical method is the use of conductor tables that give the resistance at dc and 60 Hz frequency at various
temperatures.
ECE 43200/53201 Power Systems Fall 2020
10
The Table 1 below, [5], shows the technical data of ACSR (aluminum conductor steel reinforced)
conductors.
Table1 Technical Data for ACSR (aluminum conductor steel reinforced) Conductors(*)
Cross-Section
Diameter
Layers
Weight
(Ibs per
1000 ft)
Resistance (ohms/mile)
Code Al (kcmil)
Al (mm2)
Total
(mm2)
Stranding Cond. (in.)
Core (in.)
Strength
(kips)
dc 25°C
ac at 60 Hz 60 Hz
GMR
(ft)
Aluminum Steel 25°C 50° C 75°C 100°C _ 2776. 1407. 1521. 84 x .1818 19 x .1091 2.000 .546 4 3219 81.6 .0338 .0395 .0421 .0452 .0482 .0667
Joree 2515. 1274. 1344. 76 x .1819 19 x .0849 1.880 .425 4 2749 61.7 .0365 .0418 .0450 .0482 .0516 .0621
Thrasher 2312. 1171. 1235. 76 x .1744 19 x .0814 1.802 .407 4 2526 57.3 .0397 .0446 .0482 .0518 .0554 .0595
Kiwi 2167. 1098. 1146. 72 x .1735 7 x .1157 1.735 .347 4 2303 49.8 .0424 .0473 .0511 .0550 .0589 .0570
Bluebird 2156. 1092. 1181. 84 x .1602 19 x .0961 1.762 .480 4 2511 60.3 .0426 .0466 .0505 .0544 .0584 .0588
Chukar 1781. 902. 976. 84 x .1456 19 x .0874 1.602 .437 4 2074 51.0 .0516 .0549 .0598 .0646 .0695 .0534
Falcon 1590. 806. 908. 54 x .1716 19 x .1030 1.545 .515 3 2044 54.5 .0578 .0602 .0657 .0712 .0767 .0521
Lapwing 1590. 806. 862. 45 x .1880 7 x .1253 1.504 .376 3 1792 42.2 .0590 .0622 .0678 .0734 .0790 .0497
Parrot 1510. 765. 862. 54 x .1672 19 x .1003 1.505 .502 3 1942 51.7 .0608 .0631 .0689 .0748 .0806 .0508 Nuthatch 1510. 765. 818. 45 x .1832 7 x .1221 1.465 .366 3 1702 40.1 .0622 .0652 .0711 .0770 .0830 .0485
Plover 1431. 725. 817. 54 x .1628 19 x .0977 1.465 .489 3 1840 49.1 .0642 .0663 .0725 .0787 .0849 .0494
Bobolink 1431. 725. 775. 45 x .1783 7 x .1189 1.427 .357 3 1613 38.3 .0656 .0685 .0747 .0810 .0873 .0472
Martin 1351. 685. 772. 54 x .1582 19 x .0949 1.424 .475 3 1737 46.3 .0680 .0700 .0765 .0831 .0897 .0480
Dipper 1351. 685. 732. 45 x .1733 7 x .1155 1.386 .347 3 1522 36.2 .0695 .0722 .0788 .0855 .0922 .0459
Pheasant 1272. 645. 726. 54 x .1535 19 x .0921 1.382 .461 3 1635 43.6 .0722 .0741 .0811 .0881 .0951 .0466 Bittern 1272. 644. 689. 45 x .1681 7 x .1121 1.345 .336 3 1434 34.1 .0738 .0764 .0835 .0906 .0977 .0445
Crackle 1192. 604. 681. 54 x .1486 19 x .0892 1.338 .446 3 1533 41.9 .0770 .0788 .0863 .0938 .1013 .0451
Bunting 1193. 604. 646. 45 x .1628 7 x .1085 1.302 .326 3 1344 32.0 .0787 .0811 .0887 .0963 .1039 .0431
Finch 1114. 564. 636. 54 x .1436 19 x .0862 1.293 .431 3 1431 39.1 .0825 .0842 .0922 .1002 .1082 .0436
Bluejay 1113. 564. 603. 45 x .1573 7 x .1049 1.258 .315 3 1255 29.8 .0843 .0866 .0947 .1029 .1111 .0416
Curfew 1033. 523. 591. 54 x .1383 7 x .1383 1.245 .415 3 1331 36.6 .0909 .0924 .1013 .1101 .1190 .0420 Ortolan 1033. 523. 560. 45 x .1515 7 x .1010 1.212 .303 3 1165 27.7 .0909 .0930 .1018 .1106 .1195 .0401
Merganser 954. 483. 596. 30 x .1785 7 x. 1783 1.248 .535 2 1493 46.0 .0987 .0995 .1092 .1189 .1286 .0430
Cardinal 954. 483. 546. 54 x .1329 7 x .1329 1.196 .399 3 1229 33.8 .0984 .0998 .1094 .1191 .1287 .0404 Rail 954. 483. 517. 45 x .1456 7 x .0971 1.165 .291 3 1075 25.9 .0984 .1004 .1099 .1195 .1291 .0385
Baldpate 900. 456. 562. 30 x .1732 7 x .1732 1.212 .520 2 1410 43.3 .1046 .1054 .1156 .1259 .1362 .0417
(*) Electric Power Research Institute (EPRI). Transmission Line Reference Book 345 kV and Above, 2nd Ed., J.J. LaForest, Ed., Palo Alto, CA, 1982, p. 110.
As seen in the first column of the table, the conductors are named after birds. The table gives the geometry
of each conductor, including the cross-sections, number of layers, size of the wires, and so forth. These data
are followed by the weight and mechanical strength of the conductors. The dc resistance is given at 25°C
and the ac resistance is given at several different temperatures. These data are used to determine the
transmission line resistance. From the last column, the geometric mean radius (GMR) is used for the line
inductance calculation (see next section).
For the calculation of the line electrical parameters the conductor diameter, the GMR and the conductor ac
resistance at the appropriate ambient temperature are needed. The temperature dependence of the resistance
has a minor effect on the voltage drop calculation, but significantly affects the line loss. The "Cardinal"
conductors are frequently used on high-voltage lines (see Fig.5). As an example of using the table above, the
line parameters for the Cardinal conductor are extracted. The diameter of this conductor is d = 1.196 in., the
GMR is 0.0404 ft., and the conductor 60 Hz ac resistance at 25°C is 0.0998 ohm/mile and at 75°C is 0.1191
ECE 43200/53201 Power Systems Fall 2020
11
ohm/mile. Considering the desert climate in Arizona, the resistance at 25°C corresponds to winter
conditions, if the heating effect of the current is included. The 75°C value represents summer conditions,
including the current and direct sunshine-caused radiation heating.
ACSR conductors such as that shown in Fig.5 are considered hollow, as shown in Fig. 10, because of the
following reasons: the electrical resistance of the steel core is much higher than the outer aluminum
strands, and the skin-effect phenomenon is present at 60-Hz (or 50-Hz) frequency (see details in Appendix
A).
Fig. 10 Cross-section of ACSR conductors, (b) skin-effect in a solid conductor
The line resistance R depends on the length of the conductor l (not accurate for stranded conductors),
the resistivity of the material ρ (that increases with temperature), and inversely on the effective cross-
sectional area A of the conductor through which the current flows:
𝑅 = 𝜌𝑙
𝐴 (1)
The effective area A in Eq. (1) depends on the frequency due to the skin effect, where the current at
60-Hz frequency is not uniformly distributed throughout the cross-section; rather it crowds towards
the periphery of the conductor with a higher current-density J as shown in Fig. 10b for a solid good
conductor (it will be more uniform in a hollow conductor), and decreases exponentially such that at
the skin-depth, δ, the current density is decreasing to e-1=0.368 from the conductor's surface.
The skin depth of a material at a frequency f is [4]:
𝛿 = 1
√𝜋𝑓𝜇𝜎 (2)
where, 𝜇 = 𝜇𝑟𝜇0 = 𝜇𝑟(4𝜋 × 10 −7) H/m, and the conductivity, 𝜎 =
1
𝜌 , is the reciprocal of the
conductor's resistivity.
The average power loss in a conductor with skin effect present may be calculated by assuming that the
total current is distributed uniformly in one skin depth. We may apply this to a conductor of circular
cross section with little error, provided that the conductor’s radius a is much greater than the skin
depth.
❖ The resistance at a high frequency where there is a well-developed skin effect is therefore found by considering a slab of width equal to the circumference 2𝜋a and thickness 𝛿. Hence
ECE 43200/53201 Power Systems Fall 2020
12
𝑅 = 𝜌𝑙
𝐴 =
𝑙
𝜎𝐴 =
𝑙
2πaσδ [Ω] (3)
Example 2-1:
Skin-depth and Conductor's Resistance Calculation
In Fig.10a, for the aluminum conductor , calculate the skin-depth, 𝛿, at 60-Hz frequency, and the resistance for a large conductor diameter, D=30 mm, and a line length l=100 km, at 60Hz.
Solution: The permeability of aluminum can be consider to be that of free space, that is, 𝜇 = 𝜇0 = 4𝜋 × 10−7𝐻/𝑚, and the resistivity is specified as ρ = 2.65× 10−8𝛺𝑚. Substituting these values in Eq. (2), for a frequency f = 60 Hz, the skin depth is calculated as
𝛿 = 1
√𝜋𝑓𝜇𝜎 =
1
√𝜋60(4𝜋10−7)( 108
2.65 )
= 0.018747𝑚 ≅ 18.75𝑚𝑚.
The conductor resistance at 60 Hz, substituting the conductor radius a = D/2 = 15mm in Eq.(3)
𝑅60𝐻𝑧 = 𝜌𝑙
𝐴 =
𝜌𝑙
2πaδ =
(2.65×10−8)×105
2π(15×10−3)×(18.75×10−3) = 1.5Ω.
Due to the skin effect, in ACSR conductors, the aluminum thickness T, as shown in Fig.10a, is kept at the order of
the skin depth and any further thickness of aluminum will essentially be a waste that will not result in decreasing the
overall resistance to ac currents, [2]. In case of a type of the ACSR conductor called the Bunting conductor,
the ratio T/D = 0.37, where D = 1.302 inches as listed in the previous Table 1, [5]. Therefore, the skin effect results in a resistance only slightly higher at 60 Hz compared to at dc in such a "hollow" conductor, where the resistance at dc
is listed as 0.0787 ohms/mile versus 0.0811 ohms/mile at 60 Hz, both at the temperature of 25°C.
➢ The tables with parameters given in English units (different from SI units) are using conductor cross-sectional area expressed in circular mil (cmil). One inch = 1000 mils, and 1cmil = π/4 sq
mil, [3]
➢ For stranded conductors, alternate layers of strands are spiraled in opposite directions to hold the strands together. Spiraling makes the strands up to 1% or 2% longer than the actual
conductor (line) length.
➢ Resistivity of metal conductors varies over normal operating temperatures according to 𝜌𝑇2 =
𝜌𝑇1 ( T2+T
T1+T ), where 𝜌𝑇2 and 𝜌𝑇1 are resistivities at temperatures T2 and T1 in Celsius degrees,
respectively. T is a temperature constant that depends on the conductor material, and is listed in
tables such as the Table 2 given below [3]
Table 2 Resistivity and temperature constant of conductor metals
ECE 43200/53201 Power Systems Fall 2020
13
2.3 Line Series Inductance, L
Magnetic Field Generated by Transmission Lines [1]
The current in a conductor produces a magnetic field inside and around the conductor as shown in Fig.11.
The magnetic flux lines produced by current flowing in an isolated, long straight, round conductor are
concentric circles, and the right-hand rule gives the field direction.
Fig.11 magnetic field produced by the current in an conductor
Both ac and dc lines generate magnetic fields. The intensity of the field is proportional with the current.
The dc current generated magnetic field is constant. The dc line generated magnetic field has not been seen
as a health concern because it is constant and is much less than the Earth's magnetic field, which is about
half of a gauss. However, ac generated magnetic fields, which vary in time according to the system
frequency, have received concern, although their magnitude is also much less than the Earth's magnetic
field.
The calculation of the line inductance requires the calculation of the magnetic flux inside and outside the
conductor, [1].
External Magnetic Flux
The relation between the magnetic field and the current that generates the field is described by Ampere's
Law :
∮�⃗⃗� 𝑑𝑙⃗⃗ ⃗ = ∑ 𝐼𝑘 (4)
where, �⃗⃗� is the magnetic field intensity vector measured in amp-turn/m; 𝐼𝑘 are the currents within the closed path that generates the field, in amp.
The magnetic field is constant along a flux line, which simplifies the integration. This case is shown in
Fig.12.
Fig.12 Ampere's law for a magnetic field generated by a
conductor's current (flowing out of page), [1]
ECE 43200/53201 Power Systems Fall 2020
14
In this case, the magnetic field intensity H, produced by the current I flowing through conductor, can be
calculated as 𝐻 = 𝐼
2𝜋𝑟 , and the magnetic flux density is 𝐵 = 𝜇0𝐻 = 𝜇0
𝐼
2𝜋𝑟 .
The magnetic flux is the integral of the flux density on a surface S.
Φ = ∫ �⃗� × 𝑑𝑆⃗⃗⃗⃗ 𝑆
(5)
As an example, the flux between the conductor surface at rc and point R in Fig.12 is
Φ = ∫ �⃗� × 𝑑𝑆⃗⃗⃗⃗ 𝑆
= 𝜇0 ∫ 𝐼
2𝜋𝑟 𝑙dr
R
rc = 𝜇0
𝐼𝑙
2𝜋 ln (
R
rc ) (6)
where, l is the length of the conductor.
Fig.13 External magnetic flux calculation (current into page), [1]
Consider the conductor shown in Fig.13 with a radius rc and carrying current Ic. To calculate the
external flux we select a magnetic flux line at a radius of x. The flux passing through the plane
placed between P1 and P2 is calculated by integrating the flux density between D1 and D2. The
magnetic flux is calculated in a similar manner as shown in Eqs.(5) and (6) and is finally given
by
𝛷12 = 𝜇0 𝐼𝑐𝑙
2𝜋 ln (
D2
D1 ) (7)
This equation will be used to calculate the phase-conductor generated flux and inductance.
The calculation of the magnetic field inside the conductor is based on the magnetic energy stored
in the conductor (beyond the goal of this course) and is finally calculated as
𝛷𝑖𝑛𝑡 = 𝜇0 𝐼𝑐𝑙
2𝜋
1
4 .
The interesting conclusion is that the internal flux in a conductor carrying a current is independent of
the radius.
Total Magnetic Flux of the Conductor
The total conductor generated magnetic flux is the sum of the internal and external fluxes. Equation
(7) gives the conductor generated flux passing through the plane placed between two points P1 and P2 as
shown in Fig.14, [1].
ECE 43200/53201 Power Systems Fall 2020
15
Fig.14 Magnetic flux calculation between the
conductor and an external point
In this case, D1 is equal to the conductor radius, rc. The substitution of D1= rc in Eq.(7) and replacement
of D2 with D gives a general equation for the external magnetic flux:
𝜱𝒆𝒙𝒕 = 𝜇0 𝑰𝒄𝑙
2𝜋 ln (
D
r𝑐 ) (8)
where, D is the distance from the center of the conductor; rc is the conductor radius; Ic is the
conductor current; and l is the conductor length.
The total conductor generated flux, which is the sum of the internal and external fluxes, is [1]:
𝜱𝒄 = 𝜇0 𝑰𝒄𝑙
2𝜋 ln (
D
r𝑐 ) + 𝜇0
𝑰𝒄𝑙
2𝜋
1
4 (9)
Although this formula is suitable for calculations, the equation is modified by substituting 1
4 = 𝑙𝑛 (
1
𝑒 −
1 4
)
into the above expression. The two natural logarithms are combined together, which results in a
simplified formula. A further simplification is the assumption of an l unit length which gives the flux
in weber per unit length. In the United States Wb/mile is the preferred unit, whereas in Europe Wb/km
is used.
𝜱𝒄
𝑙 = 𝑰𝒄
𝜇0
2𝜋 [𝑙𝑛 (
D
r𝑐 ) +
1
4 ] = 𝑰𝒄
𝜇0
2𝜋 𝑙𝑛 (
D
e−0.25r𝑐 ) = 𝑰𝒄
𝜇0
2𝜋 𝑙𝑛 (
D
GMR ) (10)
where GMR is called geometric mean radius.
The GMR for a solid conductor is GMR = rce -0.25, but for a stranded conductor the GMR values are
given in conductor tables. As an example, the GMR for the Cardinal conductor is 0.0404 ft. from
Table 1, [5].
Equation (10) is used to calculate the flux generated by a conductor. That equation can be interpreted
that the actual conductor is replaced by an ideal conductor (tube) with a radius of GMR. The magnetic
field inside this ideal conductor tube is zero.
ECE 43200/53201 Power Systems Fall 2020
16
Inductance of a Three Phase Line
In the case of a three-phase line, the current in each phase conductor produces a magnetic field.
The inductance of a three-phase line for a balanced system is usually referred to as positive sequence
inductance. It is assumed that the line is transposed and the line currents are balanced.
Fig.15 shows the concept of line transposition, where each phase occupies each position for one-third of
the line length.
Fig.15 Transposition of a three-phase line
The transposition equalizes the line and permits the calculation of the flux using an average spacing, called
the geometric mean distance (GMD). The GMD is calculated by
𝐺𝑀𝐷 = √𝐷𝐴𝐵𝐷𝐴𝐶𝐷𝐵𝐶 3
(11)
If line transposition is employed, then this implies that DAB, DBC and DAC may be replaced by the GMD.
The approach to compute the line inductance is derived using as example a three-phase line, built
conductors arranged in horizontal position (see Fig. 17). The field lines are concentric circles around
the conductors. Conductor A is exposed to three fluxes: ΦAA, the flux generated by the phase A current, ΦAB, the flux generated by the phase B current, and ΦAC, the flux generated by the phase C current.
(a) (b) (c)
Fig.16 (a) Fluxes produced by currents in phase A (a), phase B (b) and phase C (c)
The current in conductor A produces a flux of ΦAA, as shown in Fig.16a between A and F, that can be calculated with Equation (10):
ΦAA = 𝐼𝐴 𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐴𝐹
𝐺𝑀𝑅𝑐 ) 𝑙 (12)
where 𝐺𝑀𝑅𝑐 is the conductor GMR obtained from the conductor tables.
The current in conductor B produces a flux of ΦAB, as shown in Fig.16b between A and F, that can be calculated with Equation (7):
ECE 43200/53201 Power Systems Fall 2020
17
ΦAB = 𝐼𝐵 𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐵𝐹
𝐷𝐴𝐵 ) 𝑙 (13)
Similarly, the current in conductor C produces a flux of ΦAC, as shown in Fig.16c between A and F, that can be calculated as
ΦAC = 𝐼𝐶 𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐶𝐹
𝐷𝐴𝐶 ) 𝑙 (14)
The total flux linkage with conductor A is the sum of the fluxes generated by the phase currents,
that is, the addition of Equations (12), (13), and (14):
𝚽𝐀 = 𝑰𝑨 𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐴𝐹
𝐺𝑀𝑅𝑐 ) 𝑙+𝑰𝑩
𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐵𝐹
𝐷𝐴𝐵 ) 𝑙 + 𝑰𝑪
𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐶𝐹
𝐷𝐴𝐶 ) 𝑙 (15)
Similar equations describe the flux linkage with conductors B and C.
For balanced conditions, the sum of the three currents is zero, which permits the elimination of Ic
from Equation (15). The substitution of Ic = -IA - IB results in:
𝚽𝐀 = 𝑰𝑨 𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐴𝐹DAC
𝐷𝐶𝐹𝐺𝑀𝑅𝑐 ) 𝑙 + 𝑰𝑩
𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐵𝐹DAC
𝐷𝐶𝐹DAB ) 𝑙 (16)
This equation gives the flux linking phase A by calculation of the flux paths through the plane
between conductor A and an arbitrarily selected distant point F. Moving point F to infinity results
in DAF = DBF = DCF. Substitution of these values yields:
𝚽𝐀 = 𝑰𝑨 𝜇0
2𝜋 𝑙𝑛 (
DAC
𝐺𝑀𝑅𝑐 ) 𝑙 + 𝑰𝑩
𝜇0
2𝜋 𝑙𝑛 (
DAC
DAB ) 𝑙 (17)
Similar equations can be derived for phases B and C. Equation (17) shows that if the line is built
with unequal conductor spacing, the voltage drop along the line will be unbalanced even if the
currents are balanced. In other words, if the line is supplied by balanced three-phase voltage,
the phase voltages at the opposite end of the line will be different. That is why utilities commonly
transpose the conductors to avoid these unbalanced voltages. Fig. 15 shows this concept.
If line transposition is employed, then this implies that DAB, DBC and DAC may be replaced by the GMD
given in Equation (11). The substitution of Equation (11) into (17) eliminates the second term on
the right-hand side of Equation (17).
Thus, the simplified flux equation is: ΦA = 𝐼𝐴 𝜇0
2𝜋 𝑙𝑛 (
GMD
𝐺𝑀𝑅𝑐 ) 𝑙 (18)
❖ Finally, the line series inductance L of a phase, per unit length, calculated from (18), is
L = ΦA
𝐼𝐴𝑙 =
𝜇0
2𝜋 𝑙𝑛 (
GMD
𝐺𝑀𝑅𝑐 ), [H/m] (19)
ECE 43200/53201 Power Systems Fall 2020
18
Many high-voltage transmission lines are built with bundled conductors. The application of bundled
conductors reduces the line inductance. The bundled conductors are replaced by an equivalent conductor.
The GMR of this conductor depends on the number of conductors in the bundle and the distance between
the conductors within the bundle.
The equivalent GMRs of the bundles are:
Two-conductor bundle: 𝐺𝑀𝑅 = √𝑑 𝐺𝑀𝑅𝑐 (20)
Three-conductor bundle: 𝐺𝑀𝑅 = √𝑑2𝐺𝑀𝑅𝑐 3
(21)
Four-conductor bundle: 𝐺𝑀𝑅 = √𝑑3𝐺𝑀𝑅𝑐 4
(22)
where d is the distance between the conductors in the bundle, and GMRc is the conductor GMR
obtained from the conductor tables.
Example 2-2
Inductance Calculation of a Three-phase Line:
A three phase line, built with Cardinal conductors arranged as shown in Fig.17, has the following geometrical
data, [1]:
Fig.17Conductor arrangement of the transmission line in Example 2
Phase spacing: DAB = 35 ft; DBC = DAB; DAC = 2DAB.
Conductor height and GMR: H line = 70 ft; GMRC = 0.0404 ft.
The phasor line currents are: 𝐼𝐴 = 1500𝑒 𝑗0°; 𝐼𝐵 = 𝐼𝐴𝑒
−𝑗120°; 𝐼𝐶 = 𝐼𝐴𝑒 +𝑗120°.
The coordinates of a distant point F (see Fig.16) are:
DAF = 1000 ft; DBF = DAF; DCF = DAF.
T he length of the line is: l = 100 mi
The flux linking conductor A is determined by calculation of the flux paths through the plane between conductor A and
an arbitrarily selected distant point F. The current in conductor A produces a flux of 𝚽𝐀𝐀 between A and F, as shown in Fig.16a, that can be calculated with Equation (12) and its absolute value is:
ECE 43200/53201 Power Systems Fall 2020
19
ΦAA = 𝐼𝐴 𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐴𝐹
𝐺𝑀𝑅𝑐 ) 𝑙 = 488.44 𝑊𝑏
The current in conductor B creates a flux of 𝚽𝐀𝐁 between A and F, as shown in Fig.16b, that can be calculated with Equation (13) and its absolute value is:
ΦAB = 𝐼𝐵 𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐵𝐹
𝐷𝐴𝐵 ) 𝑙 = 161.85 𝑊𝑏
Similarly, the current in conductor C produces a flux of 𝚽𝐀𝐂 between A and F, as shown in Fig.16c, that can be calculated with Equation (14) and its absolute value is:
ΦAC = 𝐼𝐶 𝜇0
2𝜋 𝑙𝑛 (
𝐷𝐶𝐹
𝐷𝐴𝐶 ) 𝑙 = 123.89 𝑊𝑏
The total flux linkage with conductor A is the sum of the fluxes generated by the phase currents, that can be calculated
with the Equation (17):
𝚽𝐀 = 𝑰𝑨 𝜇0
2𝜋 𝑙𝑛 (
DAC
𝐺𝑀𝑅𝑐 ) 𝑙 + 𝑰𝑩
𝜇0
2𝜋 𝑙𝑛 (
DAC
DAB ) 𝑙,
and its absolute value is: | 𝚽𝐀| = 344.53 Wb. Similar equations can be derived for phases B and C. The Equation (17) shows that if the line is built with unequal
conductor spacing, the voltage drop along the line will be unbalanced even if the currents are balanced. In other
words, if the line is supplied by balanced three-phase voltage, the phase voltages at the opposite end of the line will
be different. Utilities commonly transpose the conductors to avoid these unbalanced voltages. If line transposition is
employed, then this implies that DAB, DBC and DAC may be replaced by the GMD. In this case the simplified flux
calculation is given by Equation (18):
ΦA = 𝐼𝐴 𝜇0
2𝜋 𝑙𝑛 (
GMD
𝐺𝑀𝑅𝑐 ) 𝑙 = 337.74 𝑊𝑏.
The inductance of phase A is calculated using the flux-inductance relation
𝐿𝐴 = ΦA
𝐼𝐴 = 0.225 H.
The unit length inductance is given by Equation (19):
L = ΦA
𝐼𝐴𝑙 =
𝜇0
2𝜋 𝑙𝑛 (
GMD
𝐺𝑀𝑅𝑐 ) = 2.25
𝑚𝐻
𝑚𝑖
If the per phase reactance of the line per unit length is needed, this is calculated for a frequency of 60 Hz as
𝑋𝐿 = 𝜔L = (2𝜋𝑓) 𝜇0
2𝜋 𝑙𝑛 (
GMD
𝐺𝑀𝑅𝑐 ) = 0.85
Ω
mi
ECE 43200/53201 Power Systems Fall 2020
20
References
1. George G. Karady and Keith E. Holbert, "Electrical Energy Conversion and Transportation - An Interactive Computer-Based Approach", IEEE Press, Wiley-Interscience, 2005
2. N. Mohan, "First Course on Power Systems", MNPERE, Minneapolis, 2006, ISBN 0-9715292-7-2.
3. Duncan J. Glover, Mulukutla S. Sarma, and Thomas J. Overbye, "Power Systems - Analysis and Design", 4th Ed., Thomson, 2008
4. William H. Hayt, Jr., "Engineering Electromagnetics", McGrawHill.
5. Electric Power Research Institute (EPRI), "Transmission Line Reference Book: 345kV and above", 2nd edition.
6. Electric Power Research Institute (EPRI),www.epri.com