Sprinklers Made Simple B Y R O N K A N T E R M A N
W HETHER YOU’VE BEEN ON THE
line for one year or 25 years
and have not had the time to
understand sprinkler systems basics,
this article is for you.
Frederick Grinnell, a graduate of Rens-
selaer Polytechnic Institute, worked in
railroad engineering until he retired as chief
mechanical engineer and general man-
ager of the Jersey City Locomotive Works.
Soon after his retirement, he purchased a
controlling interest in the Providence Steam
and Gas Pipe Company. Grinnell already
knew Henry S. Parmalee, who patented the
first automatic fire sprinkler head in 1874.
Providence Steam & Gas partnered with
Parmalee and manufactured the Parmalee
sprinkler. Grinnell also designed and
erected the piping installations into which
the Parmalee sprinkler heads were fitted.
Grinnell improved Parmalee’s first practical
automatic sprinkler and patented his own
Grinnell sprinkler in 1882.
Continual improvements resulted in the
glass disc sprinkler in 1890. With slight
modifications, this sprinkler head is still
used in modern fire sprinkler systems;
sprinklers are even called le Grinnells in
France. In 1892, Grinnell organized the
General Fire Extinguisher Company,
which was renamed the Grinnell Fire Pro-
tection Company after his death in 1919.
So, sprinklers have been around and
effective in fire control for about 140 years.
Yes, those little brass and chrome-plated
beauties have been the front line of de-
fense against fire in commercial buildings
for quite some time and, more recently,
in people’s homes. For many years, it was
the insurance industry that advocated
for sprinklers in commercial buildings.
Sprinklers minimized the loss, minimiz-
ing insurance payouts and enhancing
their profits at the same time. Although
the insurance industry still avidly sup-
ports sprinkler system installations, the
National Fallen Firefighters Foundation
(NFFF) is the current advocate for resi-
dential sprinklers, according to Initiative
15 of the NFFF’s 16 Life Safety Initiatives:
“Advocacy must be strengthened for the
enforcement of codes and the installation
of home fire sprinklers.”
Basics
There are two common types of
systems, wet and dry pipe systems. In
addition, there are two other less common
systems, preaction and deluge, used for
special hazards and applications. Foam
may be used in some systems, particu-
larly when dealing with flammable liquid
hazards. All of these systems simply send
water or foam (foam is just water with its
specific gravity rearranged so it floats on
top of hydrocarbons instead of sinking
in them) to the fire’s location to control;
confine; and, in some cases, extinguish
it. Very effective! You still need people to
rescue victims and pull them out of harm’s
way, so sprinklers only support staffing—
they do not replace it. They are a tool to
protect property and, in some cases, life
(residential) and to assist the fire service
with effective, efficient, and safe opera-
tions. Sprinklers save firefighters lives, too!
Wet Systems
As implied, they are wet, and the
system pipes are full of water up to the
sprinkler heads. Because of this, wet
systems are the quickest, most reliable
sprinklers around. The fire actuates the
individual sprinkler heads—this is the
only way that water gets on the fire.
Sprinkler heads use either a fusible link
with a predetermined melting point or a
glass bulb filled with a liquid designed
to boil, expand, and shatter the bulb.
Others use a chemical pellet to retain
the water cap, which is released after
(1, 3) Photos by Paul Dansbach. (2) Photo by Bill
Gustin. (4-15) Photos courtesy of the United
States Fire Administration.
1 2
3
1501fe_69 69 1/2/15 4:54 PM
To request information go to fireeng.hotims.com
(800)682-3626 or (909) 983-0772
www.phos-chek.com
(8(8(8(8(8(8(8(88(8(8(8(8(8(8(8(8(8(8(8(8(8(8(8(8(8(8(8(8(8(88(8(8(8(888(8(8(8(8(888(8(88(8(8(8(8(8(88(8(8(8888888(8(8(8(888(88(8((8(((8(8(8(8(8(8(8(8(88888(8((( 00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000)6)6)6)6)6)6)6)6)6)6)6)6)6)6)6)6)6)6)6)66)6)6)6)6)6)6)6)6)6)6)6)6)6)66)6)6)6))666666)6)6)))66))6)6)6)6))6)6)6)) 828282828282828282828282828282828282828282828282828282828282828282828282822822-3-3-3-3-3-3-3-33-3-33-3-3-3-33-3-3-362626262626262626262626262666262262626226622626666666 66 66 66 6 ororororororororororororororororororoo (((((((( (( ( (((9090909090909090909090090909000999909)9)9)9)9)9)9)9)9)9)9)9)9)9)9)99) 9 9 9 9 9 9 9 9 9 9 999 9983838383838383838388838383838338 -0-0-0-0-0-0-0-0-0-0-0-0-0-077777777777777777777777777777777777777772222222222222222222222
wwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwww.w.w.w.w.w.w.w.w.w.w.w.w.w.w.w.ww.wwww phphphphphphphphphphphphphpphphphphososososososososososososo -c-c-c-c-c-c-c-c-c-c-c-chehehehehehehehehehehehehehek.k.k.k.k.k.k.k.k.k.k.k.k..cococococococococococoococooococococommmmmmmmmmmmmmmmmmmmmmmmm
MAKE WATER
MORE EFFECTIVE Phos-Chek Class A Foam concentrates are specifically formulated to make
water more effective. The unique combination of surfactants significantly
reduces water’s surface tension, creates a superior foam blanket when mixed
with air that surrounds fuels with a thick layer of water, creates a barrier
between the fuel and the fire, allows fire fighters to see application areas,
and knocks down fire faster than water alone.
e e e e e ee e e e e e ee apapapapapapapapapapapapapapapapapapapapapapapapapapa plplplplplplplplplplplplplplplplplplplplplplplpplplplp iciciciciciciciciciciciciciciciciciciccciciciciccciciciciciciccicccatatatatatatatatatatatatatatatatatatatatatatattatatataaataaaataata ioioioioioioioioioioioioioioioioioioioioioioioioion n n n n n n n n n n n nnn n n nnnn nnnnn nn nn n arararararararararararararrararararararararraraaareaeaeaeaeaeaeaeaeaeaeaeaeaeaeaeaeaeaaeaeaeaeaaeaeaeaaeaaeaeaeeaeeaeaeaeeeeeaeeaeaeaeaeaeaeeaeaeeaee s,s,s,s,s,s,s,s,s,s,s,s,s,s,s,s,s,s,ss,s,s,s,s
((((((( ))))))))) ((((((( ))))))
Sprinklers Made Simple
the pellet melts or bursts, and the water
is there immediately. The main riser and
related equipment (known as “trim” in
the sprinkler business) is where it all
starts. The riser is connected to a water
supply with a main control valve, a main
drain, an alarm check, a retard chamber,
a couple of gauges, a fire department
connection (FDC), and a water motor
gong (photo 1).
When one or several
sprinkler heads open, water
flows though the alarm
check, which sends an alarm
(that’s why they called it
that) possibly to a central
station and to the local water
motor gong on the outside of
the building. That’s the bell
that’s ringing when you pull
up at 0300 hours and there’s
water pouring out from
under the door. The exterior
gong is there to notify people
walking or driving by to call
the fire department. The re-
tard chamber is there to take
surges in the main. The surge enters the
retard chamber so it won’t lift the alarm
check clapper, it won’t send a water
flow alarm, and you can stay in bed on a
10°F night. It retards the alarm and then
automatically drains.
You will find wet systems in areas that
are heated at all times and not subject
to freezing conditions, such as malls,
hotels, schools, office buildings, ware-
houses, factories, hospitals, and industri-
al processing sites. Wet systems are also
found in private homes. Unless there is a
reason you shouldn’t have a wet system
(e.g., no heat, water-reactive chemical
storage) then most codes and standards
(and insurance companies) require wet
systems.
Dry Systems
A dry pipe sprinkler system has no
water in the pipes. A compressor or other
source of air or nitrogen holds back the
dry pipe valve (a clapper) until the heat
of the fire melts the link or bursts the
bulb on the sprinkler heads. The air then
rushes out of the heads, releasing the
pressure on the dry pipe valve, and the
water starts to flow. These systems are
used in buildings and areas of buildings
where there is no heat (e.g., refrigerated
warehouses, outdoor sheds, loading
docks, multilevel parking structures, and
structure attic areas). To reduce response
time, some systems use “accelerators”
or “exhausters,” also known as quick
4
1501fe_70 70 1/2/15 4:54 PM
Sprinklers Made Simple
www.FireEngineering.com To request information go to fireeng.hotims.com
Fire Victim in Need of Help? Call a Retired Local Firefighter
Americaís Largest Employer of Retired Fire Officers
Proud to be a 5 Bugle Partner of the IAFC
24/7 Fast Professional 1 Hour Response Board Up ï Roof Cover ï Structural Stabilization
1-800BOARDUP.COM FIRECHIEFRECRUITERS.COM
Simplify Your Fire Truck’s Operation
Hatboro, PA 215-293-0700 Fax: 215-293-0701 © 2015 Trident Emergency Products, LLC. All rights reserved.
We design and manufacture advanced versions of the typical plumbing and hardware products so you receive improved function, easier installation, longer service life, and lower costs.
AirPrime™ Pump Primer
For example, our premier invention is our AirPrime™ Pump Primer, a patented water pump priming system powered by the truck’s air brake system. It operates manually or in AUTO PRIME mode to automatically engage the primer when no discharge pressure is sensed. Available with both single and multi-location priming points, it quickly installs on new apparatus or as a retrofi t.
E-Commerce Website... TridentDirect.com
Visit our website to buy online and for in-depth information on all our products, including… air-operated intake relief valves… Wildland products for plumbing suction and discharge mani- folds… Class A Foam proportioners… hand-wheels with unique valve position indicator… and more!
To request information go to fireeng.hotims.com
opening devices (QODs), which help release the air out of the
system and more quickly open the dry pipe valve (photo 2).
As with the wet system, the riser is connected to a water
supply, but there is a dry pipe valve in place of the alarm
check. It will also send a water flow signal after it trips. It
has a main control valve, a main drain, a couple of gauges,
an FDC, and a water motor gong. This system also has a
compressor or a nitrogen supply, and an air gauge is on the
upstream side of the dry pipe. If it starts to bleed down, a sig-
nal will go to the fire alarm panel, reporting a “low air alarm.”
Pre-Action
A pre-action system is also dry, but two distinct actions
must occur for water to enter the occupancy. Pre-action sprin-
kler systems are used in places (e.g., computer rooms, hospital
operating rooms, and museums) in which any accidental wa-
ter discharge is to be avoided. Because two distinct actions
must take place to put water in the room, merely snapping off
a sprinkler head by accident will not activate the system. Un-
like the dry pipe, an opening caused by an accidental break in
the piping or a head will not trip the valve. Pre-action valves
are electronically tripped through heat or smoke detection
(photo 3).
Note the following sequence of actuation of a typical pre-
action system in a computer room:
1. A smoke condition occurs in the room.
2. A smoke detector picks up the smoke and signals a small
pre-action panel (similar to a fire alarm panel) or the main
fire alarm panel for the entire building. In either event,
the signal goes to a panel. The smoke detector indicates,
“Smoke has been detected in the room. Open the pre-
action valve.”
3. The panel signals the pre-action valve at the riser, “A
smoke condition has been detected in the computer room.
Trip and open to flood the piping system and stand by for
fire.”
4. An electronic solenoid switch on the pre-action valve at the
riser activates and electronically “pulls a pin,” which trips
the valve. Water flows into the system. At this point, we
now have a wet system.
5. When the fire grows and reaches the set temperatures of
the sprinkler heads (usually 165-175°F in a computer room),
the heads will start to open over the fire.
Deluge
The main difference between the deluge system and a dry
5
1501fe_71 71 1/2/15 4:54 PM
To request information go to fireeng.hotims.com
REGISTER BY 2/17 TO SAVE | NSCA.COM/TSAC2015
TSAC ANNUAL TRAINING
APRIL 6 – 9, 2015 | WYNDHAM RESORT | ORLANDO, FL | CEUs: NSCA 2.0 BOC 20
FITNESS TO SERVE, STRENGTH TO PERFORM2015
Sprinklers Made Simple
system is that all sprinkler heads are
open with no fusible elements or glass
bulbs. It discharges lots of water every-
where and all at once. These systems
are usually actuated by heat detection
and are mainly found in heavy industrial
applications (e.g., around transformers,
processing tanks, processing pads with
large vessels, small flammable liquid
storage tanks). Since the heads are
always open, using compressed air to
hold a dry pipe valve back won’t work.
Activation is similar to that of a pre-
action system.
1. A heat detector detects fire around a
transformer and signals the panel.
2. The panel signals the deluge valve at the
riser, “A fire condition has been detected.
Trip and open to deliver water to all
heads and all sides of the transformer.”
3. An electronic solenoid switch on the
deluge valve at the riser activates and
electronically “pulls a pin,” which al-
lows the valve to trip. Water flows into
the system and all heads. At this point,
we now have a deluge of water sur-
rounding the subject equipment on fire.
4. Deluge systems sometimes require an
immediate activation pull station at the
hazard (in this case, the transformer)
and in the riser room, so a person can
intervene and manually activate the
system even before the detection kicks
in (photos 4, 5).
Valves
All fire service control valves must be
indicating valves—i.e., just by looking at
them you can see whether they are open
or closed.
Outside stem and yoke (OS&Y). The
amount of stem showing should be the
same as the depth of the valve body—
6 7
1501fe_72 72 1/2/15 4:54 PM
Sprinklers Made Simple
DEMAND
QUALITY
USA – CANADA – SOUTH AMERICA
EUROPE – ASIA / MIDDLE EAST
Tel: 1-800-567-2719 Fax: 1-800-434-2613 [email protected]
www.fire-pump.com
PORTABLE
PUMP
FOAM
TRAILER
CAFS SKID UNIT
BRUSH
TRUCK
ATV SKID UNIT
SKEETER
SPACE PACK
A C E N T U R Y O F E N G I N E E R I N G
F O R T H E B R AV E S T
www.FireEngineering.com To request information go to fireeng.hotims.com
i.e., six inches of valve,
six inches of stem.
When the stem is out,
it’s open. The red box
is a tamper switch that
will send a signal to
the panel if someone
tries to maliciously shut
the valve. The lock and
chain shown here are an
insurance requirement,
not code (photo 6).
Post indicator valve
(PIV). This valve is
found outside buildings and has a win-
dow that will indicate OPEN or SHUT.
A wrench sits on the operating nut as
it does on a hydrant and can be locked
on the side. Both PIVs shown are also
electronically supervised with tamper
switches (photo 7).
Wall PIV. Found on the outside wall
of a commercial building, similar to the
PIV, it has a window indicating OPEN or
SHUT. On the inside of the wall attached
to this valve is a large fork that spears
the operating valve on the riser so you
can operate the riser valve from the out-
side of the building. The valve shown has
a tamper switch on it as well (photo 8).
Indicating butterfly valve (IBV). This
valve is found on the riser usually for
smaller piped systems. Larger risers
require larger valves and operating
handles. The indicator is the yellow bar
in the center of the valve. As it opens and
closes, the bar rotates. Since sprinkler
valves must be indicator valves, an open
valve will show the bar in line with the
pipe. This one is open (photo 9).
Sprinkler Heads
Sprinkler heads come in various sizes,
configurations, and temperatures. All
have a specific purpose and use. One
size does not fit all!
Upright. This sits on top of the pipe
and is usually found in dry systems so
that when the system drains down after
tripping, the water doesn’t remain in the
heads and pipe nipples. In an unheated
area, if the temperature were to drop
below freezing, water remaining in the
system could damage it. This head has a
chemical pellet fusible element that melts
and allows the water to flow (photo 10).
Pendant. This sprinkler head hangs
8 9
1501fe_73 73 1/2/15 4:54 PM
12
10 13
11
74 | January 2015 FIRE ENGINEERING www.FireEngineering.com
Sprinklers Made Simple
from under the piping. In some cases,
it’s placed on a long “drop” and pokes
through a dropped ceiling. The oblong
device is a lead link holding the two le-
vers together under tension. It’s designed
to melt at a given temperature, releas-
ing the arms and allowing water to flow
(photo 11).
Sidewall. These were designed primar-
ily for retrofitting hotels and motels. A
pipe is placed along the upper corner
of the corridor and a sprinkler head is
inserted into each room and into the cor-
ridor itself. It operates like other standard
sprinklers and will have a link, a glass
bulb, or a chemical pellet (photo 12).
Early suppression fast response (ESFR).
The insurance industry designed this
head for high-piled storage warehouses
(e.g., big-box stores and other places
with high racks of combustible storage).
Because of the large water demand, you
need larger pipes than usual and, in most
cases, a fire pump. If ever you’ve noticed
sprinklers inside the racks in your
favorite home supply store, they can be
eliminated if an ESFR system in installed
at the ceiling. It puts out lots of water
really fast. Compare the difference in size
between an ESFR and a standard head
(photo 13). The “fast response” comes
from a pencil-thin glass bulb that will
burst a lot more quickly than a standard-
size sprinkler bulb (photo 14).
High-pressure water mist sprinkler
head. Developed by and for the cruise
ship industry, these sprinkler heads can
provide extinguishment into a compart-
ment without necessarily flooding it. The
water is discharged as a high mist fog
and cools the atmosphere and the burn-
ing materials. Other applications include
computer rooms instead of gas systems
using halon and laboratory fume hoods
where the scientists do their experi-
ments. The water output from
these heads is negligible, and
they are also the only heads
that have a filter screen on the
nipple where it connects to the
piping to eliminate any pipe
scale, sludge, or other foreign
matter that would be detrimen-
tal to the operation of this type
of head. Note the quartzite
bulb for activation (photo 15).
Tactical Tips
1. Always send personnel with a radio to
the riser room on arrival to check the
status of the sprinkler system.
2. Place a dry line from the first-due
engine to the FDC, and prepare to
augment pressure in the system. Know
the local pressure demands for the
systems in your district; also know
that the rule of thumb for FDCs for
sprinklers is 150 psi.
3. Shut sprinkler control valves only on
the express order of the incident com-
mander (IC). Let the system do what it
was designed for, which is to confine,
contain, and possibly extinguish the
fire. ESFRs are designed to extin-
guish. Sprinklers will buy you some
time to set up and get going.
4. Carry sprinkler head clamps to help
minimize water damage. Sometimes
two wood chocks work, but they
would have to be cut to the right
size.
5. Be ready to deploy salvage tarps for
water traveling down to the floors
below.
6. It’s extremely difficult and danger-
ous to fight a fire when sprinklers are
operating. It is recommended that you
don’t. The water from the heads is
pushing the heat and steam down on
top of you, and visibility is worse than
usual. Coordinate your actions. Vent,
shut the valve (by the IC’s order), and
move in with a line as simultaneously
as you can.
7. For stubborn deep-seated Class
A or Class B fires, consider pump-
ing finished foam solution into the
FDC. Also consider pumping foam
solution into FDCs feeding stand-
pipe systems so you can have a
foam handline if you need one on
the upper f loors of a building. We
1501fe_74 74 1/2/15 4:54 PM
Sprinklers Made Simple
To request information go to fireeng.hotims.com
Portable Water Tanks Firefighters’ #1 choice for
Folding Frame Tanks • Self-Supporting Tanks
Salvage Covers • Cargo Netting
918-333-2000 • 800-260-9950 • www.HuskyPortable.com
• Patented Easy Lift Handles (US Patent No. 8,746,478 and other patents pending)
• Quick Dump (optional feature) US Patent No. 8,733,579
• Registered, exclusive Exlon® material • Pinch-free design
• Lifetime warranty on welds & welded seams
• Superior heavy duty • Laser-cut hinge design
EASY LIFT HANDLES
mounted on the floor
of our tanks
US PATENT NO 8,746,478
and other patents
pending
on tanks and salvage covers!
Our New State-of-the-Art Facility is complete!
14tried this in industry, and it worked! (“New Uses for Foam in Industry,”
Fire Engineering, November 2001,
http://bit.ly/1zHnRoQ). Standard
sprinkler heads, although not neces-
sarily listed for “foam service,” will
effectively discharge foam.
8. Depending on your department’s
policies, you may be expected to
restore the system before you leave.
There should be six spare heads
and a wrench at the riser for this
purpose. It is ultimately the owner’s
responsibility to ensure that the sys-
tem gets restored in a timely manner.
Codes will not allow some occu-
pancies to be occupied unless the
sprinklers are in service (e.g., child
care center), so immediate restora-
tion of the system may be warranted
vs. a “vacate” order.
9. If the swivels on the FDC are frozen,
won’t spin, and won’t allow you to
hook up, pull three feet of the line
between your knees, and lock it
there. Backtwist the line about seven
turns and then place it on the frozen
swivel and let it thread itself. Try
this during a drill. Different thread
types will bring different numbers of
backtwists.
Sprinkler Training Tips
for the Company Officer
One of the many responsibilities of
the company officer is to ensure the
members of his crew are familiar with
active and passive fire protection. This
segment on sprinklers (active fire protec-
tion) is key to understanding the basics
of water-based fire protection systems.
Knowledge of these systems lends itself
to safe and efficient operations. Try these
training tips to get your crew familiar
with sprinklers:
1. Review the basic wet and dry systems
as outlined. Explain the importance
of knowing these systems and how
they will help you fight the fire more
effectively and how they assist with
firefighter safety.
2. Review the tactical tips as outlined.
3. After review, go to the field and find
these systems.
4. At a building in your response district,
have the building engineer or other
responsible party walk you through
the systems.
5. Go to another building and have the
members identify the components on
the systems there. They need to know
and understand the basics so when
you send them to the “main control
valve,” they’ll know what you mean.
6. Take advantage of your fire prevention
1501fe_75 75 1/2/15 4:54 PM
To request information go to fireeng.hotims.com
Sprinklers Made Simple
bureau, fire marshal’s office, or fire
academy. They have expertise in this
area. Drop your pride, and improve
your safety and fireground efficiency.
7. When you think your members know
the basics, do it one more time. Just
like standard tactics, knowledge of
these systems needs to be second
nature.
8. Make this part of your regular train-
ing, and take the time to examine
these systems. Do it on or after runs or
during downtime. If you’re driving by
a building and you spot a water motor
gong, an FDC, or a fire pump manifold,
stop and take a look.
RON KANTERMAN is the chief of the Wilton
(CT) Fire Department and a 40-year fire
service veteran with experience in municipal
and industrial fire protection, volunteer and
career services, emergency management,
and emergency response. He has a bachelor’s
degree in fire administration and master
degrees in fire protection management and
in environmental sciences. Kanterman is
a contributing author to Fire Engineering,
FireEngineering.com, Fire Engineering’s
Handbook for Firefighter I and II, and the
new edition of The Fire Chief’s Handbook.
He co-hosts an FE Blog Talk Radio show
“The Back Step Boys” and lectures around
the country on various fire service topics.
He is an adjunct professor of fire science and
emergency management at the University
of New Haven in Connecticut. Kanterman
is also an advocate for the National Fallen
Firefighters Foundation and its programs
and is the chief of operations for the annual
National Memorial Weekend.