Programable Logic controller questions 1-3
MODULE TITLE: PROGRAMMABLE LOGIC CONTROLLERS
TOPIC TITLE: ADDITIONAL FACILITIES
LESSON 1: DIGITAL TO ANALOGUE CONVERSION
PLC - 7 - 1
© Teesside University 2011
Published by Teesside University Open Learning (Engineering)
School of Science & Engineering
Teesside University
Tees Valley, UK
TS1 3BA
+44 (0)1642 342740
All rights reserved. No part of this publication may be reproduced, stored in a
retrieval system, or transmitted, in any form or by any means, electronic, mechanical,
photocopying, recording or otherwise without the prior permission
of the Copyright owner.
This book is sold subject to the condition that it shall not, by way of trade or
otherwise, be lent, re-sold, hired out or otherwise circulated without the publisher's
prior consent in any form of binding or cover other than that in which it is
published and without a similar condition including this
condition being imposed on the subsequent purchaser.
________________________________________________________________________________________
INTRODUCTION ________________________________________________________________________________________
This lesson deals with the idea of obtaining an analogue output from a machine
which is, itself, operated on purely digital principles. A simple network used for the
production of analogue outputs is examined from the point of view of a network
analysis, to determine the levels of output which could be possible in theory. These
output levels are not often those achieved in actual practice and reasons for non-
theoretical outputs and methods of counteracting them are also discussed.
The lesson continues by looking at the possible need to improve the analogue
output level to make it capable of supplying a greater range of loads.
Finally, the problem of maintaining and updating an output from a PLC is
considered by reference to the ladder diagram function and basic block
diagram circuitry found in analogue output modules.
________________________________________________________________________________________
YOUR AIMS ________________________________________________________________________________________
Upon completion of this lesson you should be able to:
• determine the number of analogue output values expected from
specified D/A circuits
• conduct a full voltage analysis on an R/2R network with a specified
number of inputs
• explain the need for amplification and buffering of the D/A output
• understand the use of a function number specified within a program
to effect control over a conversion update process.
1
Teesside University Open Learning (Engineering)
© Teesside University 2011
________________________________________________________________________________________
ANALOGUE OUTPUTS FROM PLCs ________________________________________________________________________________________
Lesson 1 of Topic 2 introduced analogue and digital signals and the difference
between them. It was stated that a true analogue signal is one which can have
an infinite number of possible values lying between an upper and a lower limit.
In comparison the digital signal on a single conductor can have only one of
two acceptable values, a logic 1 or a logic 0.
If a PLC, which is a digital machine, is to be used to supply a so called
analogue output, then the best that can be achieved from a single conductor is
two levels of voltage – one level obtained when the conductor is logic 1 and
the other when the conductor is logic 0. Two possible values do not constitute
an infinite number of values and so the analogue output would clearly not be
acceptable.
DIGITAL TO ANALOGUE CONVERSION
Whenever a digital machine/system is required to output an analogue signal
level an electrical conversion circuit (or network) is used to produce the change
from digital signals to analogue signals. Understandably, the network/circuit is
referred to as a digital to analogue (D/A) converter.
Unfortunately, the output from such a circuit will never be truly 'analogue', as
defined by the previous statement, because it is impossible to produce an
infinite number of output values from the circuit. The output number is finite
and is defined by the number of digital inputs going into the converter circuit.
Consider the diagram of FIGURE 1. The converter shown by the symbol has
two digital inputs, A and B. Each of these inputs can have one of two possible
logic levels, i.e. A can be logic 0 or 1 and B can be logic 0 or 1.
2
Teesside University Open Learning (Engineering)
© Teesside University 2011
This means that four possibilities of input levels exist (shown by the table of
FIGURE 2). It also means that only four "analogue" output levels are possible.
FIG. 1 FIG. 2
If the D/A converter has three digital input lines, as shown in FIGURE 3, then
as each one has two possible states, eight combinations of input levels exist.
This means that eight ‘analogue’ output levels are possible (FIGURE 4).
FIG. 3 FIG. 4
Digital Inputs Analogue
Output
1
2
3
4
5
6
7
8
C
0
0
0
0
1
1
1
1
B
0
0
1
1
0
0
1
1
A
0
1
0
1
0
1
0
1
A D/A CIRCUIT
Analogue
OutputB C
Digital Inputs
B
0
0
1
1
A
0
1
0
1
Analogue Output
1
2
3
4
A D/A CIRCUIT
Analogue
Output B
Digital Inputs
3
Teesside University Open Learning (Engineering)
© Teesside University 2011
If you have not realised yet, the number of outputs is increasing in a particular
fashion.
Two possibilities per line gives us a base of two, and the number of lines
produces a power index to which the base is raised, to produce the output
number. So we have:
one line – 21 = 2 values (i.e. 1 change 0 → 1) two lines – 22 = 4 values (i.e. 3 changes)
three lines – 23 = 8 values (i.e. 7 changes)
four lines – 24 = 16 values (i.e. 15 changes)
five lines – 25 = 32 values, etc. (i.e. 31 changes)
The diagram of FIGURE 5 shows a D/A circuit having 12 input lines. How many
output value levels are possible?
FIG. 5
________________________________________________________________________________________
A
B
C
D
E
F
G
H
I
J
K
L
D/A CIRCUIT
0 volt line
Digital Input Lines
Analogue Output
4
Teesside University Open Learning (Engineering)
© Teesside University 2011
A D/A circuit with 12 input lines will have 212 = 4096 possible output values.
A sixteen input D/A circuit produces a possible 65 536 output values. This is
still not truly analogue but the incremental change from value to value may be
small enough for it to be acceptable as an analogue equivalent. If, for example,
the output voltage ranged from 0 volts to 4 volts then the smallest change
possible in the output value would be 1/65 535 of 4 volts = 4/65535 volts
= 0.000061 volts. If the output voltage were being monitored by a 0 to 4 volt
analogue voltmeter then this small change in value would produce such a small
change in pointer deflection that it could not be detected by the human eye. If
this is the case, then a sixteen input D/A circuit would not be necessary, and
perhaps a twelve input or even an eight input D/A would suffice.
This example serves to show that a true analogue output is seldom required and
hence a D/A circuit can be chosen to have the number of inputs to match the
requirements of the device which is detecting or receiving the analogue output
signal. Hence D/A circuits have become acceptable within industry.
5
Teesside University Open Learning (Engineering)
© Teesside University 2011
________________________________________________________________________________________
D/A CIRCUIT ________________________________________________________________________________________
The process of drawing little boxes with lines going in and coming out is all
very easy but is it just as easy to understand what the manufacturer will put
inside the box to effect the conversion?
Different circuits exist as D/As and, as you might expect, modern practice is to
use integrated circuit packages because they are small, relatively cheap,
reliable and easy to install. We shall examine one circuit network method of
effecting a D/A conversion. The chosen circuit is simple because it contains
nothing other than resistors and so elementary circuit theory can be employed
to conduct an analysis.
R/2R RESISTOR CIRCUIT
To make the analysis as simple as possible a two input circuit will be used.
The theory of this circuit relies upon the use of only two values of resistor.
One we will call R ohms and the other 2R ohms, 2R being exactly twice the
resistance value of R. The actual values of resistance are not important to the
theory as long as the 1 : 2 ratio is maintained. However, the resistance values
used in practice do need some consideration.
FIGURE 6 shows the two input circuit. Only five resistors are needed and
these are identified as R1, R2, R3, R4 and R5.
Two test point nodes (TP1 and TP2) are also shown for text reference. Notice
that this purely resistive circuit does not have a positive power supply because
it draws its current from the digital circuit which feeds its inputs. To determine
a value of output voltage for each input combination of digital levels we will
need to carry out a circuit analysis.
6
Teesside University Open Learning (Engineering)
© Teesside University 2011
FIG. 6
If A = 0 and B = 0 (assumed here to be 0 volts)
If 0 volts is applied to each input then no current will flow in the circuit and no
voltage will be developed across any of the resistors. The output voltage will
therefore be 0 volts. This is the lower limit.
If A = 1 and B = 0
We don't need to specify a value of voltage to represent a logic 1 level, we
could just use V as a symbol. However, if you are not happy with this then
assume that the logic level is 9 volts which is common for CMOS circuits.
If input B is at logic 0 then a 0 volt connection has been made to this input.
The circuit network can now be considered as being that of FIGURE 7. R4 in
parallel with R5 is equivalent to a resistance value of:
R R
R R
R R
R R
R
R R4 5
4 5
22 2 2 2
4 4
×( ) +( ) =
× +
= = ohms
High impedance instrument
0 volt line
R5
R4R1
R2
Analogue output
V
A B
2R
TP2
2R2R
2R
TP1 R3
R
Inputs
7
Teesside University Open Learning (Engineering)
© Teesside University 2011
An equivalent circuit (FIGURE 8) can be drawn using this value.
FIG. 7
The equivalent circuit becomes:
FIG. 8
0 volt line
R1
R2
A = 1
R
TP2
2R
2R
TP1 R3
R
V
(Equivalent to R4 and R5)
0 volt line
R5
R1
R2
Analogue output
A
B
TP2
2R
2R
2R
TP1 R3
R
R4 2R V
8
Teesside University Open Learning (Engineering)
© Teesside University 2011
Note now that R3 is shown in series with R4 and R5 in parallel. The resistance
values both being R ohms gives a combined resistance of R + R = 2R ohms.
This 2R value is connected across R2 and so the next stage of equivalence can
be shown as FIGURE 9.
FIG. 9
R2 (2R ohms) in parallel with the equivalent resistance of R3, R4 and R5 (2R ohms) again gives a resistance of R ohms.
The circuit is finally reduced to the one shown in FIGURE 10.
R1
R2
A = 1
2R
2R
TP1
(Equivalent to R3, R4 and R5)
2R
9
Teesside University Open Learning (Engineering)
© Teesside University 2011
FIG. 10
This last equivalence diagram is that of a simple potential divide network of
two resistors connected in series. The potential at the node between the two
resistors (TP1) will be:
The diagrams of FIGURE 8, FIGURE 9 and FIGURE 10 can all be redrawn
showing this potential.
R
R R
R
R+( ) = =2 3 1 3
of the voltage applied at the input AA.
( 1 3
of 9 volts is 3 volts.)
R1
A = 1
R
2R
TP1
(Equivalent to R2, R3, R4 and R5)
10
Teesside University Open Learning (Engineering)
© Teesside University 2011
FIG. 11
The output voltage displayed on the voltmeter will be half the value available
at test point 1 because R3 is in series with the R4/R5 combination of R. The
actual value will therefore be 1/2 × 1/3 = 1/6 of the voltage applied as a logic 1 at the A input. (1/6 of 9 volts = 1.5 volts.)
If A = 0 and B = 1
The circuit analysis is very similar to that already conducted for the 1, 0 input.
This time the potential at test point 2 is 1/3 of the voltage applied at B (if you
doubt this then work through the equivalent circuits yourself). This is also the
value of voltage indicated at the output. (1/3 of 9 volts = 3 volts.)
R1
R2
A
2R
2R
TP1
2R
R1
A
R
2R
TP1 1/3 V
Equivalent to
1/3 V
Equivalent to
R1
R2
A
2R
2R
TP1
R3
R
R
1/3 V 1/6 V (Output voltage)
11
Teesside University Open Learning (Engineering)
© Teesside University 2011
If A = 1 and B = 1
To determine the output voltage with this input combination you will need to
consider the potentials that would exist if the R3 resistor were removed from
the circuit. The circuit would then be two potential dividers providing 1/2 of
the voltage at TP1 and 1/2 of the voltage at TP2 i.e. the same potentials. If the
same potentials exist then connecting R3 back into circuit will make no
difference because no current will flow through R3 (there being no potential
difference across it). This means that the output voltage will be 1/2 of the
input voltage (1/2 of 9 volts = 4.5 volts).
FIG. 12
When these output values are tabulated the output trend will appear.
R1
R2
A = 1
2R
2R
TP1 = 1/ 2V R3
R
V
B = 1
R4
TP2 = 1/ 2V
R5 2R
2R
12
Teesside University Open Learning (Engineering)
© Teesside University 2011
FIG. 13
The input/output graph of FIGURE 14 shows the possible incremental steps at
the D/A output. Steps of equal change in voltage are clearly indicated, no
other output values would be possible.
FIG. 14
A
D/A CIRCUIT
0 volt line
B
Analogue
Output
A = 0
B = 0
A = 1
B = 0
A = 0
B = 1
A = 1
B = 1
Input Combinations
1/6 V
2/6 V
3/6 V
Digital Inputs
Digital Inputs
Analogue Output
B
0
0
1
1
A
0
1
0
1
Output
0 volts = 0 volts
1 of VDIG = 2 VDIG3 6
1 of VDIG = 3 VDIG2 6
1 of VDIG = 1 VDIG6 6
1 VDIG DIFFERENCE6
1 VDIG DIFFERENCE6
1 VDIG DIFFERENCE6
} } }
Lower limit
Upper limit
Note: VDIG is whatever digital voltage value is being used (positive logic assumed).
13
Teesside University Open Learning (Engineering)
© Teesside University 2011
With a 2 input R/2R network the best theoretical analogue output would be 1/2
of the voltage level being used as a digital logic 1. On the basis of the current
work, theory suggests a 2.5 volt output if a 5 volt logic 1 is assumed.
However, even though the theory may seem acceptable, there are some factors
which have not been taken into consideration. These factors are due to circuit
loading effects.
Firstly, the D/A network has been considered as a stand alone circuit when, in
fact, it is actually connected to and supplied from another circuit, which feeds
it the logic levels. If the resistances within the network have relatively low
ohmic values then the D/A could draw a relatively large current which would
upset the logic levels at the input and, therefore, have an effect upon the
analogue value at the output. To minimise this effect the R/2R values would
need to be relatively high.
Secondly, the D/A network will be used to supply a circuit at its output
terminal. In our analysis the output load was a voltmeter which was being
used to sense the analogue voltage. If the load connected to the analogue
output needs to draw a relatively large current then its input resistance will be
relatively low. This low resistance will upset the output voltage value expected
because, in our analysis, we did not take this into account. This is indicated by
FIGURE 15. The only way to avoid this loading effect is to make the load a
high resistance or make it appear as a high resistance by the use of an
impedance matching device.
14
Teesside University Open Learning (Engineering)
© Teesside University 2011
FIG. 15
Consider the limitations of this network.
1. The R/2R values should ideally be high to prevent overloading or altering
the logic levels of the circuit supplying the D/A.
2. The load connected to the analogue output should be of high resistance in
relation to the R/2R resistance values. This will impose limits on the
output current.
3. The best possible analogue output voltage is fairly low at only 1/2 of the
input digital value.
To overcome some of the loading problems and to boost the output voltage to a
more useful value, the D/A circuit is likely to be followed by a fixed gain or
variable gain voltage amplifier (an integrated circuit operational amplifier).
No longer 2R Ω across TP2 to 0 volt line due to low
resistance load.
A B
2R
2R2R
2R
R
Low Ω Load
15
Teesside University Open Learning (Engineering)
© Teesside University 2011
Such an amplifier will present a high enough resistance to the D/A output and
provide a greater analogue voltage and current driving capacity to be able to
feed the load. FIGURE 16 shows the basic arrangement.
FIG. 16
The analogue output from the amplifier will be an amplification of the output
from the D/A circuit. The diagram indicates a times by four amplifier. If the
voltage gain is four and the logic level is +5 volts then 4 × 1/2 of 5 volts = 10 volts will be the new upper limit of analogue voltage.
Note that the analogue output has been amplified but it still only has four
possible output values, i.e.
1. 0 volts × 4 = 0 volts 2. (1/6 × 5 volts) × 4 = 3.33 volts 3. (2/6 × 5 volts) × 4 = 6.66 volts 4. (3/6 × 5 volts) × 4 = 10 volts
Remember, to increase the number of output values the number of digital
inputs must be increased. However, a 3, 4, 5, etc. input R/2R network does not
produce the same levels of analogue voltages as the 2 input circuit! Each
would require its own circuit analysis to determine the output upper and lower
range limits.
A D/A
CIRCUIT
B
Amplified
analogue output
High input
impedance ×4
Voltage amplifier
16
Teesside University Open Learning (Engineering)
© Teesside University 2011
________________________________________________________________________________________
PLC D/A CONVERTERS ________________________________________________________________________________________
Analogue outputs are not normally supplied as standard facilities on smaller
PLCs. It is possible to obtain them in separate units which may be fitted as
expansion modules for some machines and they certainly should be available
for use on larger and rack mounted types. Large PLCs are often supplied as an
almost empty backplane into which the user plugs the combination of modules
required for a particular application. One or more of these modules may be
analogue output units. The module plugged into the backplane would be
allocated an identification according to its position. The identification is often
by a channel number which represents a group of individual digital relays.
Any use of the module is made by making reference to its channel number
when programming the ladder diagram.
When the program is run and the point in the ladder diagram is reached where
an analogue output update is required the typical operation would be:
• obtain the logic status levels of a specified group of memory cells
• send the logic levels, as channel data, to the input terminals of the
D/A output module.
An analogue output value, determined by the current logic levels in the
specified memory locations, would then appear at the output of the specified
channel. The D/A inputs are, as in the case of the 2 input circuit, taken as true
binary (or hexadecimal) code.
The output analogue value will only be available until the program progresses
to the next part of the ladder diagram. It will then be lost unless the digital
values are captured (or latched) at the input to the D/A network. The module
would, therefore, require a small quantity of latching memory to retain the
17
Teesside University Open Learning (Engineering)
© Teesside University 2011
level of each bit. The latching memory device(s) must be controlled by the
CPU and enabled when an update is requested. This will be once in every
program scan if the analogue output rung is complete. Changes in the logic
levels of the specified memory locations which take place during the scan time
are then reflected by the next update scan.
The section of ladder diagram shown as FIGURE 17 indicates that the D/A
conversion output will be updated only if contacts 004 and 012 are closed. The
PLC instruction representing the control action for the D/A update is specified
by a function number (indicated by FUN ** on the diagram). The source of
the data is specified next. Remember that this implies a "group of" individual
locations. The last item of information is the destination channel (here channel
07).
FIG. 17
FIGURE 18 is a simplified version of the analogue output circuitry. Only eight
input lines are shown, giving 256 possible output values, but ten and twelve
line D/As should be recognised as being more common in practice.
004 012
FUN **
DM015
07
Analogue Output Function No. Source of Data. Destination Channel.
18
Teesside University Open Learning (Engineering)
© Teesside University 2011
FIG. 18
The D/A facility, as previously stated, would probably be provided in a larger
PLC. However, large PLCs are also likely to be capable of carrying out other
functions, such as some level of mathematics. In such cases, the machine may
view data held in certain groupings of memor y locations as being
representative of decimal values i.e. the data may be held in Binary Coded
Decimal (BCD) format. If data were regarded as being in BCD then it would
be nonsense to present it at the input of the D/A because the network would be
expected to have an input of true binary.
To cater for this, the set of instruction words which act as ladder diagram
functions, should also provide a means of converting the data from BCD
format to true binary format before the data is sent to the D/A circuit. This
will be discussed further in the next lesson.
You should now attempt the Self-Assessment Questions on pages 20 and 21.
D/A CIRCUIT
Analogue output
terminals
Data latch
memory
Latch control
0 volt line
Output amplifier (with fixed or variable gain)
⎧ ⎪ ⎪ ⎪⎪ ⎨ ⎪ ⎪ ⎪ ⎪⎩
Analogue output module
Data from PLC (possibly
via photo couplers)
AMP
19
Teesside University Open Learning (Engineering)
© Teesside University 2011
________________________________________________________________________________________
SELF-ASSESSMENT QUESTIONS ________________________________________________________________________________________
1. How many different output values are possible from a D/A circuit having:
(a) 8 inputs?
(b) 10 inputs?
(c) 12 inputs?
(d) 14 inputs?
(e) 16 inputs?
2. The network diagram of FIGURE 19 shows a 3 input R/2R network.
Determine the analogue value of output voltage for each of the input
combinations given in the table of FIGURE 20. Assume any suitable
value to represent a logic 1.
FIG. 19
V Analogue
output value
A
2R
2R
R
B
2R 2R
C
2R
R
0 volt line
Inputs
20
Teesside University Open Learning (Engineering)
© Teesside University 2011
FIG. 20
3. Explain why the output of a D/A circuit might be fed to the input of an
operational amplifier within a PLC D/A module.
C
0
0
0
1
B
0
0
1
0
A
0
1
0
0
Output value
21
Teesside University Open Learning (Engineering)
© Teesside University 2011
________________________________________________________________________________________
ANSWERS TO SELF-ASSESSMENT QUESTIONS ________________________________________________________________________________________
1. (a) 256 outputs.
(b) 1024 outputs.
(c) 4096 outputs.
(d) 16 384 outputs.
(e) 65 536 outputs.
2. C = 0, B = 0, A = 0 gives 0 volts output
C = 0, B = 0, A = 1 gives 1/12 of V output
C = 0, B = 1, A = 0 gives 2/12 of V output
C = 1, B = 0, A = 0 gives 4/12 of V output
where V is the value you assumed to represent a logic 1.
3. The output of a D/A network (certainly the R/2R type) is dependent
partially upon the loading applied to its output terminals. To reduce this
loading effect the output should be presented with a high resistance load
which does not vary. The output of the operational amplifier can be
scaled to produce a voltage range to match the load transducer
requirements and will also possess a current drive capability which a D/A
network will not have.
22
Teesside University Open Learning (Engineering)
© Teesside University 2011
________________________________________________________________________________________
SUMMARY ________________________________________________________________________________________
This lesson has concentrated on the possibility of producing an analogue
output from a non-analogue system. The network analysed was that of an
R/2R circuit but it should not be assumed that this is the only way of producing
an analogue output. The lesson also examined the loading effects of the D/A
network upon the circuit which supplies it and the considerations required with
respect to the load which is connected to its output terminals.
A D/A network is not the only circuitry to be expected within a PLC D/A
module and so the lesson continued by providing an indication of what else
may be found and the possible reasons for the additions. Such modules have to
be driven through a sequence of events which, in our case, have been shown to
be initiated by a FUNction number used within the ladder diagram. Carrying
out the function effects a conversion update.
23
Teesside University Open Learning (Engineering)
© Teesside University 2011
<< /ASCII85EncodePages false /AllowTransparency false /AutoPositionEPSFiles true /AutoRotatePages /None /Binding /Left /CalGrayProfile (Dot Gain 20%) /CalRGBProfile (sRGB IEC61966-2.1) /CalCMYKProfile (U.S. Web Coated \050SWOP\051 v2) /sRGBProfile (sRGB IEC61966-2.1) /CannotEmbedFontPolicy /Error /CompatibilityLevel 1.4 /CompressObjects /Tags /CompressPages true /ConvertImagesToIndexed true /PassThroughJPEGImages true /CreateJDFFile false /CreateJobTicket false /DefaultRenderingIntent /Default /DetectBlends true /ColorConversionStrategy /LeaveColorUnchanged /DoThumbnails false /EmbedAllFonts true /EmbedJobOptions true /DSCReportingLevel 0 /SyntheticBoldness 1.00 /EmitDSCWarnings false /EndPage -1 /ImageMemory 1048576 /LockDistillerParams false /MaxSubsetPct 100 /Optimize true /OPM 1 /ParseDSCComments true /ParseDSCCommentsForDocInfo true /PreserveCopyPage true /PreserveEPSInfo true /PreserveHalftoneInfo false /PreserveOPIComments false /PreserveOverprintSettings true /StartPage 1 /SubsetFonts true /TransferFunctionInfo /Apply /UCRandBGInfo /Preserve /UsePrologue false /ColorSettingsFile () /AlwaysEmbed [ true ] /NeverEmbed [ true ] /AntiAliasColorImages false /DownsampleColorImages true /ColorImageDownsampleType /Bicubic /ColorImageResolution 300 /ColorImageDepth -1 /ColorImageDownsampleThreshold 1.50000 /EncodeColorImages true /ColorImageFilter /DCTEncode /AutoFilterColorImages true /ColorImageAutoFilterStrategy /JPEG /ColorACSImageDict << /QFactor 0.15 /HSamples [1 1 1 1] /VSamples [1 1 1 1] >> /ColorImageDict << /QFactor 0.15 /HSamples [1 1 1 1] /VSamples [1 1 1 1] >> /JPEG2000ColorACSImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 >> /JPEG2000ColorImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 >> /AntiAliasGrayImages false /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict << /QFactor 0.15 /HSamples [1 1 1 1] /VSamples [1 1 1 1] >> /GrayImageDict << /QFactor 0.15 /HSamples [1 1 1 1] /VSamples [1 1 1 1] >> /JPEG2000GrayACSImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 >> /JPEG2000GrayImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 >> /AntiAliasMonoImages false /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict << /K -1 >> /AllowPSXObjects false /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputCondition () /PDFXRegistryName (http://www.color.org) /PDFXTrapped /Unknown /Description << /ENU (Use these settings to create PDF documents with higher image resolution for high quality pre-press printing. The PDF documents can be opened with Acrobat and Reader 5.0 and later. These settings require font embedding.) /JPN <FEFF3053306e8a2d5b9a306f30019ad889e350cf5ea6753b50cf3092542b308030d730ea30d730ec30b9537052377528306e00200050004400460020658766f830924f5c62103059308b3068304d306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103057305f00200050004400460020658766f8306f0020004100630072006f0062006100740020304a30883073002000520065006100640065007200200035002e003000204ee5964d30678868793a3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002> /FRA <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> /DEU <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> /PTB <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> /DAN <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> /NLD <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> /ESP <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> /SUO <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> /ITA <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> /NOR <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> /SVE <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> >> >> setdistillerparams << /HWResolution [2400 2400] /PageSize [612.000 792.000] >> setpagedevice