Assignment
CHAPTER 3
OCCUPANCY CLASSIFICATIONS AND LOADS The occupancy classification
of a building or space is generally determined by the way that building or space is
to be used. Occupancy classifications have been developed by the codes to address
the different hazardous situations, often referred to as risk factors, associated with
each type of use. These risk factors consider the typical characteristics of the
environment, the activity that will occur in the space, and the occupants using the
space. Risk factors may include spatial characteristics (low light levels, fixed
seating, and high sound levels), fuel loads (amount of finish materials, upholstered
furniture, and other flammable contents), concentration of occupants,
characteristics of the occupants (mobility, age, alertness), and sometimes the
familiarity of the occupants with the building. In some cases, these unique
characteristics call for additional code requirements so that buildings are safe. For
example, more exits are required in auditoriums (Assembly) due to the large
number of people using the space, and alternate exiting methods are required in
hospitals (Institutional), where occupants often are not mobile due to age, health,
or security reasons. The different occupancy classifications in the codes are based
on these various characteristics. The codes address these conditions for each
occupancy classification so that people can be considered equally safe at work, at a
crowded concert, or with any other type of use. In some cases, the projected
occupant load (OL) will be the most influential component in determining the
occupancy classification. The occupant load is the number of people that is
assumed to safely occupy a space or building. Since occupancy classifications and
occupant loads are, in a sense, dependent on each other, both should be considered
at the beginning of a project. Once the occupancy classification has been
determined, the projected occupant load, or expected number of people, is used to
determine a number of other code requirements. The first part of this chapter
concentrates on occupancy classifications and their relationships; occupant loads
are discussed in the last part of the chapter. UNDERSTANDING OCCUPANCY
CLASSIFICATIONS An occupancy classification must be assigned to every
building or space within a building. Determining the occupancy classification is
one of the most important steps in the code process. It should be the first thing
determined when designing the interior of a building, since almost every interior
code and regulation is based on the
Kennon, Katherine E.; Harmon, Sharon K.. The Codes Guidebook for Interiors
(pp. 131-132). Wiley. Kindle Edition.
building's occupancy. Many examples are listed in Figure 3.1. The occupancy of a
space must also be known in order to effectively use most of the remaining
chapters in this book. Once the occupancy is known, it will guide the remaining
code research. Accessibility Requirements Fire Extinguishing Systems Alarm
Systems Furniture Selection/Placement Egress Capacities Means of Egress
Electrical Devices Mechanical Loads Emergency Lighting Occupant Loads Finish
Selection/Placement Plumbing Fixtures Fire Barriers/Partitions Smoke Barriers
Fire/Smoke Detection Systems Smoke Detection Systems Figure 3.1 Interior codes
affected by occupancy. For existing buildings that are occupied, the occupancy
classification is already determined. But for a new or existing building that is
intended to have new tenants, the occupancy classification for each proposed
tenant must be determined separately. These different tenants may, in turn, affect
the way the shared public spaces are classified. The occupancy classification must
be reexamined whenever changes are made in the use of a building or space. If the
intended use of an existing building is changing significantly, determining the new
occupancy classification may be particularly important. Some of these changes are
obvious, such as an old warehouse building being renovated into apartments. Other
changes may be less noticeable but still require reclassification. It may also be
important to understand how the occupants will actually be using the space or plan
to use it in the future. For example, if a space will be used temporarily as an open
office plan but in the future will be used as a training room, both Assembly and
Business requirements may have to be considered so that the design will address
the most stringent code requirements. If not, significant renovations may be
required when the change in use actually occurs. The ICC codes and the NFPA
codes divide the occupancy classifications slightly differently. However, the 10
most common occupancy classifications used throughout the various building and
life safety codes are listed here. Some of them also have subclassifications. The
occupancy classifications and their subcategories are discussed in the first part of
this chapter. Assembly occupancies
Kennon, Katherine E.; Harmon, Sharon K.. The Codes Guidebook for Interiors
(pp. 132-133). Wiley. Kindle Edition.
Business occupancies Educational occupancies Factory or Industrial occupancies
Hazardous occupancies Institutional occupancies Mercantile occupancies
Residential occupancies Storage occupancies Utility or Miscellaneous occupancies
Many of these classifications seem self‐explanatory, especially if a building type is
straightforward, but remember that three things must be known before the
occupancy classification can be accurately determined: (1) the type of activity
occurring, (2) the expected number of occupants, and (3) whether any unusual
hazards or risk factors are present. These factors can affect the appropriate
classification of a building type or spaces within a building. A boutique that sells
clothing, for example, has an activity that is straightforward. It is a Mercantile
occupancy. However, in some cases, small differences in use can change the
occupancy classification. For example, a television studio is a Business occupancy,
but if the studio allows audience viewing, it will typically be considered an
Assembly occupancy. Knowing the specific type(s) of activities that are occurring
is important. Many of the classifications allow for a specific number of people. For
example, a space may appear to be an Assembly use, but if a small number of
people will be using the space, it may be allowed to be classified as Business.
When using the IBC, if a day care center serves fewer than five children, it may be
considered Residential, but if it has more than five attendees, it may be considered
Institutional or Educational. So, if the number of occupants increase or decrease,
the occupancy classification may have to be reexamined. Hazards to occupants can
include harmful substances and/or potentially harmful situations. (See the inset
titled “Risk Factors and Hazards in Occupancies” in this chapter.) When either is
present, different types of requirements apply. The storage or use of flammable,
explosive, or toxic materials is considered to be hazardous and can either change
the occupancy to a stricter classification or require all or part of a building to be
classified as a Hazardous occupancy and be subject to tougher codes. Small levels
of certain hazardous materials, however, are allowed in almost every occupancy
classification. For example, a small amount of paint can be stored
Kennon, Katherine E.; Harmon, Sharon K.. The Codes Guidebook for Interiors
(pp. 133-134). Wiley. Kindle Edition.
in any occupancy. However, in large amounts paint storage would be considered a
Hazardous use. Certain situations within a building or the condition of the
occupants themselves can create potential risk factors or hazards as well. Low light
levels, low awareness or mental capacity, restricted movement due to security, and
similar characteristics can create potentially unsafe situations. If hazardous
materials or situations are expected to be present in the building or space, it may
affect the appropriate choice of occupancy classification. Consult the local code
official early in a project whenever there is uncertainty as to the correct occupancy
classification. It is always a good idea to have a code official confirm the choice of
occupancy. If it is determined later that the choice is incorrect, or if the choice is
not approved by the code official, the rest of the research may be incorrect and the
design may not meet the appropriate code requirements. COMPARING THE
CODES The building codes, such as the International Building Code (IBC) and the
Life Safety Code (LSC), are used to assign an occupancy classification to the uses
of a space or building. Knowing the appropriate occupancy classification and/or
subclassification is the most important step in understanding what code and
standard requirements apply to a space or building. Most of the requirements and a
majority of the exceptions are based on occupancy. Also, since the NFPA codes
are organized largely by individual occupancy chapters, the correct occupancy
classification is necessary to determine the appropriate chapter to apply to the
project. Other codes also use the occupancy classifications to call out particular
code requirements. This includes the fire codes, such as the International Fire Code
(IFC), which provides specific fire‐related requirements for each occupancy type
within its various chapters. The fire codes provide additional requirements for
other special uses as well. This includes unusual buildings and rooms that might
not be covered in the building codes. Because these uses have unique activities or
hazards associated with them, special requirements are called out by separate
chapters or sections within the fire codes. For example, the fire codes typically
have chapters on airports, clean rooms in laboratories, and rooms used for dry
cleaning. If there is a special use in a particular design, research both the building
code and the fire code when it is required by a jurisdiction.
Kennon, Katherine E.; Harmon, Sharon K.. The Codes Guidebook for Interiors
(pp. 134-135). Wiley. Kindle Edition.
RISK FACTORS AND HAZARDS IN OCCUPANCIES The types of risk factors
or hazards found in a building help to determine its occupancy classification. They
can vary dramatically from one building type to the next. Each occupancy type was
created to handle different types of hazards. Some of the risk factors that are
typically considered when determining an occupancy classification are: Number of
occupants (a large group versus a small gathering) If occupants are at rest or
sleeping Alertness of the occupants (considers mental capabilities and inherent
distractions caused by the activities going on in the space) Mobility of the
occupants (considers physical abilities, age, and security measures) Familiarity of
occupants with the space or building Typical characteristics of the space used for a
particular activity (includes fixed seating and aisles, light levels, noise levels, etc.)
Potential for spread of fire (due to airborne flammable particles, storage of
hazardous materials, combustible finishes, decoration or contents, etc.) These risk
factors were considered by the code organizations in the development of each
occupancy classification, the various subcategories, and the appropriate code
requirements. It may also be necessary to consider if any of these factors are
specifically known to exist within the proposed space. Both the occupants in the
space and the use of the space must be considered to correctly determine the
occupancy classification. Similar risk factors must also be considered when
working with performance codes. The assigning of occupancy classifications by
the codes allows some assumptions to be made as to how people will react and
move within a space or building in case of a fire or emergency. The prescriptive
requirements then define specifically how safety can be achieved. By contrast,
when using performance codes, only general parameters for what should be
considered about the activities and the occupants are given by the codes. The
design must then describe and/or prove how safety is provided. Therefore, if there
is an unusual building type or an occupancy with multiple uses, use of performance
criteria may have to be considered (if allowed by the jurisdiction). Note Most code
jurisdictions require the use of a fire code in addition to a building code. Typically,
the fire code will be either the International Fire Code or the NFPA Fire Code
(NFPA 1). The ICC Performance Code (ICCPC) has a section titled “Use and
Occupancy Classification” within the “Design Performance Levels” chapter.
Instead of grouping types of activities into occupancy classifications, it states that
the objective is to identify the primary use of a space or building and the risk
factors associated with that use. The risk factors that must be considered include
the type of activity, hazards, number of occupants, length of occupancy, alertness
(sleeping or awake), familiarity with the space, vulnerability (lack of mobility or
cognitive awareness), and whether occupants are related. The NFPA codes discuss
similar issues that should be considered by discussing occupant characteristics and
assumptions within the “Performance‐based Option” chapter in each code. The
design must then take into account the unique characteristics of the use and
occupants. Because accessibility requirements apply to almost every occupancy
classification or building use, the necessary accessibility documents must be
referenced. The building codes include an accessibility chapter and refer to the
accessibility standard ICC A117.1. Depending on the building type, the Americans
with Disabilities Act (ADA) standards or the FHA Accessibility Guidelines
(FHAG) may be required as well. In some cases, specific building types will be
subject to additional requirements. For example, the ADA Standards have
requirements that must be met for certain occupancies, such as Mercantile,
Residential, and Health Care. Other building uses may be exempt. (See the section
“Accessibility Requirements” later in this chapter and Chapter 2 for more
information.) DESCRIPTION OF OCCUPANCIES Use the following description
of each occupancy to help determine the occupancy classification of a space or
building. In addition, an occupancy may be subdivided into smaller, more specific
categories. For example, the IBC divides its Assembly occupancy into five
different subclassifications. These subclassifications are explained as well. A wide
range of common building types has been provided as examples. The list is not all‐
inclusive, and it does not replace the applicable code publications. These must be
referenced as well. Each code also classifies its occupancies a little differently. For
example, the classifications used in this chapter are based on the ICC's I‐Codes.
Although many are similar to those used in the NFPA codes, the NFPA may use a
different name for a classification or subdivide them differently. Refer to Figure
3.2 for a comparison of how each occupancy classification differs in the IBC and
the NFPA codes. OccupancyClassification ICCInternational Building Code
NFPALife Safety Code and NFPA 5000 ASSEMBLY A‐1 Assembly, Theaters
(Fixed Seats) A Assembly (variations noted by occupant load) A‐2 Assembly,
Food and/or Drink Consumption A‐3 Assembly, Worship, Recreation, Amusement
A‐4 Assembly, Indoor Sporting Events A‐5 Assembly, Outdoor Activities
BUSINESS B Business B Business AHC Ambulatory Health Care
EDUCATIONAL E Educational (includes some day care) E Educational
FACTORY/INDUSTRIAL F‐1 Factory Industrial, Moderate Hazard I Industrial,
General F‐2 Factory Industrial, Low Hazard Industrial, Special Purpose Industrial,
High Hazard HAZARDOUS H‐1 Hazardous, Detonation Hazard (included in
Group I) H‐2 Hazardous, Deflagration Hazard or Accelerated Burning H‐3
Hazardous, Physical or Combustible Hazard H‐4 Hazardous, Health Hazard H‐5
Hazardous, Hazardous Production Materials (HPM) INSTITUTIONAL I‐1
Institutional, Custodial Care OL* >16 D‐I Detentional/Correctional (includes
various subconditions IV) I‐2 Institutional, Medical Care H Health Care I‐3
Institutional, Restrained (includes various subconditions I5) DC Day Care I‐4
Institutional, Day Care Facilities MERCANTILE M Mercantile M‐A Mercantile, >
3 levels or > 30,000 SF (2800 SM) M‐B Mercantile, ≤ 3 stories or > 3000 SF (280
SM) and ≤ 30,000 SF (2800 SM) M‐C Mercantile, 1 story ≤ 3000 SF (280 SM)
RESIDENTIAL R‐1 Residential, Transient R Residential, Hotels and Dormitories
R‐2 Residential, Multi‐Dwelling Unit Residential, Apartment Buildings R‐3
Residential, One and Two Dwelling Units Residential, Lodging or Rooming
Houses Residential, One‐ and Two‐Family Dwellings R‐4 Residential, Care and
Assisted Living Facilities OL > 5 ≤16 Residential, Board and Care STORAGE S‐1
Storage, Moderate Hazard S Storage S‐2 Storage, Low Hazard UTILITY/
MISCELLANEOUS U Utility and Miscellaneous Special Structures and High‐
Rise Buildings Figure 3.2 Comparison of occupancy classifications. (This chart is a
summary of information contained in the 2015 editions of the International
Building Code®, the NFPA 5000®, and the Life Safety Code®. Neither the ICC
nor the NFPA assumes responsibility for the accuracy or completeness of this
chart.) Note Letters are often used to designate an occupancy classification. For
example, “A” stands for Assembly and “E” stands for Educational. (See Figure
3.2.) Assembly (A) Occupancy A building or part of a building is classified as an
Assembly occupancy if people gather for civic, social, or religious functions,
recreation, entertainment, eating, drinking, or awaiting transportation. The most
common characteristic of an Assembly occupancy is that it holds a large number of
people (usually more than 50) who are unfamiliar with the space. Other common
characteristics include such aspects as low light levels, the occupants' lack of
awareness of surroundings, and the potential for panic because of the number of
occupants. Because of these multiple risk factors, there are a number of additional
codes that apply strictly to Assembly occupancies. Note A restaurant can be
classified as a Business or Mercantile occupancy (if the number of occupants is
small enough), as an Assembly, or as an accessory to a larger adjacent occupancy.
The NFPA codes rely primarily on the number of people to determine the
classification of an Assembly. The IBC bases its classifications more on the type of
activity than on the density of occupants. As a result, NFPA codes have fewer
Assembly subclassifications. (See Figure 3.2.) Each code also provides specific
requirements for unique uses such as malls, theaters with stages, and other building
types that may seem to fit the Assembly use. In the IBC this information is in a
separate special‐use chapter; in the NFPA codes it is included in the Assembly
occupancy chapters. The IBC has five subclassifications of Assembly based on the
type of activity occurring. They are designated as A‐1 through A‐5. A‐1 This type
is for the viewing of performing arts or movies. The space often includes a stage.
(There are many code requirements specifically for stages.) The common
characteristics of these types of spaces are low light levels and above‐normal
sound levels. Seating usually consists of fixed seating with well‐defined aisles.
Occupants are alert but distracted and generally unfamiliar with the building.
Sample Building Types Motion picture theaters Radio and television studios with
audiences Symphony and concert halls Theaters for stage production A‐2 This type
is for the consumption of food and drink. Often these spaces have low light levels,
loud music, late operating hours, and ill‐defined aisles (e.g., movable tables and
chairs). The serving of food and drink is the most defining characteristic. Sample
Building Types Banquet halls Casino gaming areas Dance halls (serving food and
drink) Drinking establishments Fast‐food restaurants Fellowship halls (serving
food and drink) Nightclubs Restaurants (including kitchen; may also be classified
as Business) Taverns and bars (may also be classified as Business) Commercial
kitchens (associated with a dining area) A‐3 This type is for the gathering of
people for worship, recreation, or amusement. Types of activities that are not
classified by other types of Assembly are typically included in this
subclassification. The common characteristics of this subclassification are clear or
defined egress patterns and moderate to low fuel loads. For example, in a church or
an auditorium, aisles used for egress are defined by the placement of pews or
chairs. Occupants in an A‐3 subclassification are also usually alert and are often
more familiar with the space than in other assembly uses. Sample Building Types
Amusement arcades Armories Art galleries Assembly halls Auditoriums Bowling
lanes Churches and religious structures Community halls Courtrooms Dance halls
(not including food or drink consumption) Exhibition halls Fellowship halls
Funeral homes Galleries Gymnasiums (without spectator seating) Lecture halls
(may also be Business) Libraries Mortuary chapels Museums Passenger stations,
terminals, or depots (waiting areas) Pool and billiard rooms Public assembly halls
Recreation halls and piers Tents for assembly A‐4 This type is for the viewing of
indoor sporting events and other activities with spectator seating. The spectator
seating can consist of a defined area for seating or fixed seats such as bleachers.
Although A‐3 and A‐4 can have similar activities, if a defined area for viewing the
activities is provided, then it is an A‐4. For example, an indoor pool can be
classified as an A‐3 Assembly, but if the pool area also includes seating for
viewing swim competitions, it is considered an A‐4. (Similar activities can also
occur in A‐4 and A‐5 Assemblies.) Sample Building Types Arenas Gymnasiums
Indoor skating rinks Indoor swimming pools Indoor tennis courts A‐5 This type is
for the participation in or viewing of outdoor activities. This subclassification is
similar to A‐4, except that it is outdoors or in a structure with no roof. Sample
Building Types Amusement park structures Bleachers Grandstands Stadiums Note
A good rule of thumb is that when the occupant load is 50 or more, the
requirements for an Assembly occupancy should be researched. Typically in
Assembly occupancies, there are a large number of occupants. Examples include a
theater or large restaurant. However, when a space is used for a small group of
people to gather—such as a college classroom, an office conference room, or a
small restaurant—the codes often allow these uses to be classified under another
occupancy type. The IBC and the NFPA codes use an occupancy of 50 people or
more as the cutoff point. (Some jurisdictions may use a different limit.) For
example, if the IBC is used, a small restaurant can be classified as a Business
occupancy if its occupant load is less than 50. The NFPA codes would reclassify
this as a Mercantile occupancy. In many cases, the codes also allow an assembly‐
type use that is part of another occupancy classification to be considered the same
occupancy that it serves. It may depend on the size or the occupant load. For
example, the IBC allows rooms used for assembly purposes that are less than 750
square feet (70 square meters [sm]) or have an occupancy less than 50 to be
classified either as a Business occupancy or as part of the main occupancy
classification. Assembly occupancies that are related to Educational or are
accessory to a religious educational facility can also be classified with the
occupancy that they serve, according to the IBC. These clarifications can have
critical impact on the various code requirements that will apply. Business (B)
Occupancy Note A wide variety of building types can fall under the Business
occupancy classification. For example, a small Assembly, such as a restaurant that
has an occupant load fewer than 50 people, as well as college classrooms and
outpatient clinics, can be classified as a Business occupancy. A building or part of
a building is classified as a Business occupancy if it is used for the transaction of
business such as office, professional, or service‐type trades and other similar
functions. Limited areas that are a natural part of a business setting, such as small
storage, recordkeeping, supply areas, and break rooms, are included as well. The
risk factors in a Business occupancy are considered to be relatively low. This is
because there is typically a low concentration of occupants, and they are usually
alert and generally familiar with their environment. It is considered one of the
lowest‐risk occupancies. This classification can become very broad. For example, a
smaller Assembly‐like occupancy that has fewer occupants can sometimes be
classified as a Business occupancy, such as a small restaurant. Conversely, when
the function or size of any of the Business building types expands beyond a typical
business, the occupancy must be reexamined. Examples might include city halls
that include assembly areas or college facilities that include an auditorium
classroom. These areas may be classified separately as an Assembly occupancy or
a mixed occupancy. (See the section “Mixed Occupancies” later in this chapter.) In
addition, for an occupancy that offers health care services similar to a doctor's
office, but where procedures are performed that cause four or more patients to be
under sedation or conditions that would prevent them from being able to exit the
facility without assistance, the facility may have to be classified as an ambulatory
care facility. Under the IBC, this type of use is still considered a Business
occupancy, but will have specific code requirements that differ from those for a
typical Business occupancy. The NFPA codes have a separate occupancy
classification of Ambulatory Health Care. However, in both cases additional
requirements will apply. Educational‐type occupancies can also be confusing.
Colleges and universities (educational facilities after the twelfth grade) are
considered Business occupancies. Yet, business and vocational schools are often
considered as the same occupancy as the trade or vocation that is being taught. For
instance, general classrooms for a college would be classified as Business, but the
areas for instruction in automotive repair may be considered Factory/Industrial. In
addition, places that offer various types of training or skill‐development classes
can be classified as Business instead of Educational, regardless of the age of the
participants. Examples include places that offer music, dance, or tutoring. Sample
Building Types Airport traffic control towers Ambulatory care facilities Animal
hospitals, kennels, and pounds (part of the building could be considered Storage)
Automobile and other motor vehicle showrooms Automobile service stations (can
also be classified as Hazardous) Banks Barber shops Beauty shops Car washes
City halls Civic administration buildings Clinics (outpatient) College and
university classrooms Dentist's offices Doctor's offices Dry‐cleaning facilities (can
also be classified as Hazardous) Educational facilities (above twelfth grade)
Electronic data processing facilities Fire stations Florists and nurseries
Government offices Greenhouses Laboratories (nonhazardous) Laboratories
(testing and research) Laundromats Libraries (can also be classified as Assembly
or Business) Medical offices (separate from Institutional occupancies) Motor
vehicle showrooms Office buildings Outpatient clinics, ambulatory Police stations
Post offices Print shops Professional offices (architect, attorney, dentist, physician,
etc.) Radio and television stations (without audiences) Repair garages (small,
nonhazardous) Telecommunication equipment buildings Telephone exchanges
Travel agencies Educational (E) Occupancy A building or part of a building is
classified as an Educational occupancy if it is used for educational purposes by a
specified number of persons at any one time through the twelfth grade. Depending
on the code publication, the specified number of persons range from six to the
minimum number of people required for an Assembly occupancy. (For colleges
and universities, see Assembly and Business occupancies.) The NFPA codes also
specify a minimum amount of time that a space is used for educational purposes.
For example, if there are fewer than 12 hours of instruction per week, the building
type could be governed by a different occupancy classification, according to the
LSC. Note Although it may seem normal for college and university classrooms to
fall under the Educational occupancy, these building types are typically classified
as Business. However, they may also have spaces that are considered Assembly. It
is common for a typical school to have spaces that might be considered a different
occupancy, such as auditoriums, cafeterias, and gymnasiums. As of the 2012 IBC,
in most cases, these additional uses are not required to be classified separately
under an Assembly occupancy, but are allowed to be considered Educational as
well. Vocational shops, laboratories, and similar areas within a school will usually
be considered Educational, even though they may require additional fire
protection. As mentioned in a previous section, if the entire school is considered
vocational, some codes may require that it fall into the same classification as the
trade or vocation being taught. If an Educational occupancy also provides care and
sleeping accommodations, it could be classified as an Institutional occupancy or a
mixed occupancy. For example, the sleeping area of a boarding school or an
extended‐stay rehabilitation program may be classified as Residential. Day care
centers can also be classified as Institutional, depending on the number of children
and their age. Verify the proper designation with the local code official when
necessary. Sample Building Types Academies Day care centers (can also be
considered Institutional) Elementary schools High schools Junior high schools
Kindergartens Nursery schools Preschools Secondary schools Note Areas
providing day care during religious functions are allowed to be considered part of
the primary occupancy; this will affect many code requirements. Factory (F)
Occupancy A building or part of a building is designated as a Factory or Industrial
occupancy if it is used for assembling, disassembling, fabricating, finishing,
manufacturing, packaging, processing, or repairing. This designation generally
refers to a building in which a certain type of product is made. The product that is
made or the materials used to make the product must typically be considered a low
or moderate hazard. If it is a more hazardous material or product, the building or
space where it is made may be considered a Hazardous occupancy. The sample
product types listed here are typically considered low to moderate types of hazards
by the building codes. However, each code groups them a little differently under
the Factory/Industrial occupancy, and there may be different code requirements,
depending on which hazardous group the product is in. For example, the IBC
divides its Factory occupancy into F‐1 and F‐2. The NFPA uses the term Industrial
occupancy and has three subclassifications of that category. (See Figure 3.2. Also
see the section “Hazardous Occupancy” later in this chapter.) These
subclassifications are made for the different levels of hazardous materials or
activities that are part of the manufacturing process. Refer to the specific code to
determine if a manufactured product is considered moderate or low hazard; if more
hazardous materials are used or created in the space or building, it may have to be
classified as a Hazardous occupancy. Sample Building Types Assembly plants
Factories Manufacturing plants Mills Processing plants Low and Moderate
Hazardous Products Aircrafts Appliances Athletic equipment Automobiles and
other motor vehicles Bakeries Beverages (alcoholic) Beverages (nonalcoholic)
Bicycles Boats (building) Boiler works Brick and masonry Brooms or brushes
Business machines Cameras and photo equipment Canneries Canvas or similar
fabrics Carpets and rugs (includes cleaning) Ceramic products Clothing Condensed
powdered milk manufacturing Construction and agricultural machinery Creameries
Disinfectants Dry cleaning and dyeing Electric light plants and power houses
Electrolytic reducing works Electronics Engines (includes rebuilding) Film
(photographic) Food processing and commercial kitchens (not associated with a
restaurant, cafeteria, or similar dining facility) Foundries Furniture Glass products
Gypsum products Hemp products Ice Jute products Laboratories (can also be
classified as Business) Laundries Leather products Machinery Metal products
(fabrication and assembly) Millwork (sash and door) Motion pictures and
television filming Musical instruments Optical goods Paper mills or products
Plastic products Printing or publishing Recreational vehicles Refineries Refuse
incineration Sawmills Shoes Smokehouses Soaps and detergents Sugar refineries
Textiles Tobacco Trailers Upholstering Water pumping plants Wood (distillation
of) Woodworking (cabinetry) Hazardous (H) Occupancy A building or part of a
building that involves the generation, manufacturing, processing, storage, or other
use of hazardous materials is typically classified as a Hazardous occupancy. These
materials can include flammable dust, fibers or liquids, combustible liquids,
poisonous gases, explosive agents, corrosive liquids, oxidizing materials,
radioactive materials, and carcinogens, among others. In general, this classification
is categorized by an unusually high degree of explosive, fire, physical, and/or
health hazards. Note The NFPA codes do not have a separate Hazardous
occupancy. Instead, it is a subclassification under the Industrial occupancy and
addresses hazardous uses in each occupancy type. Hazardous building types
require additional precautions. Each code sets different standards and has special
sections dedicated to hazardous uses, which list very specific materials. In most
cases, a Hazardous occupancy can be subclassified as a low, medium, or high
hazard. Each building code categorizes the hazards a little differently. Often the
lower hazards are made part of the Factory/Industrial or Storage occupancy
classification. Each code also has a different number of subclassifications. The IBC
has five Hazardous classifications (H‐1 through H‐5). The NFPA codes, however,
include high hazard building types as a subclassification under Industrial. (See
Figure 3.2.) They do not have a separate Hazardous occupancy. When using the
NFPA codes, be careful to identify how that specific code or standard defines the
term hazardous, as they may vary slightly per code publication and the purpose of
the regulation. For example, in the LSC, the term hazardous is used to describe the
level of hazardous content of the space, whereas in the NFPA 13, Installation of
Sprinkler Systems, the term is used to define the ability of the sprinkler system to
control the fire. Note Sometimes two different buildings with the same building
type may have different occupancy classifications if hazardous materials are
present in one but not the other. For example, some auto repair shops are
considered a Hazardous occupancy. Others are considered a Business occupancy.
An important factor to consider is the amount of hazardous materials. If the
amount is small enough, the space or building may not be considered Hazardous
by the codes. A common example is a chemistry lab in a high school. As more
performance‐type requirements are introduced into code publications, more
emphasis will be placed on the types of products or materials used in a space rather
than on the type of building. If a space or building may contain hazardous
materials or conditions, consult the specific codes and work closely with the local
code officials. Some buildings may require only part of the building to be
classified as Hazardous. (Hazardous buildings and materials are beyond the scope
of this book.) Sample Building Types Airport hangars or airport repair hangars
Dry‐cleaning plants Explosives manufacturers Film storage, combustible
Firearm/ammunition warehouses Gas plants Laboratories with hazardous
chemicals Paint and solvent manufacturers Paint shops and spray painting rooms
Pesticide warehouses Power plants Pumping/service stations Tank farms
Warehouses with hazardous materials Institutional (I) Occupancy A building or
part of a building is classified as an Institutional occupancy if it includes care or
supervision of the occupants, including medical care. The primary distinction of
this classification is that the occupants are either limited in their mobility,
immobile, or incapable of mobility due to physical or security restraints. In most
cases, the occupants must depend on others to help them evacuate the building in
case of an emergency. The IBC has four Institutional subclassifications (I‐I
through I‐4). The NFPA, on the other hand, separates these uses into different
occupancy classifications. The NFPA codes refer to them as
Detentional/Correctional, Health Care, and Day Care occupancies. (See Figure
3.2.) Using the IBC designations, each subclassification is described in the
following subsections; the similar NFPA classification is given as well. Note,
however, that the specific definition for each NFPA occupancy may vary from
those in the IBC. The minimum and maximum number of occupants can vary as
well. For example, the minimum number for an I‐4 classification in the IBC is 6
and the minimum number for a Day Care occupancy in the LSC is 4. Refer to the
applicable code to determine the correct occupancy classification. (Also see the
inset titled “Rooms and Spaces” later in this chapter.) Note The IBC has four
Institutional subclassifications. The NFPA codes divide these into separate Health
Care, Detentional/Correctional, and Day Care occupancies. Because some uses can
be determined by subtle differences, a discussion with a code official may be
required to confirm whether the jurisdiction will consider the facility Institutional,
Residential, or one of the other specific NFPA classifications. The applicable code
requirements can vary significantly between these occupancies. Note Custodial
care describes when assistance with day‐to‐day living tasks is given but the
occupant can evacuate independently at a slow rate. Depending on additional
factors, these occupancies can be Institutional or Residential. I‐1 This type is for
the housing and custodial care of a certain number of occupants on a 24‐hour basis.
The codes often use 16 occupants as the limit. (This number does not include
staff.) These occupants, because of age or mental disability, require supervision.
However, they can typically respond to an emergency without physical assistance
from staff. If fewer than 16 people with the same characteristics were being cared
for, the occupancy would be reclassified as Residential. The NFPA considers this
building type a Residential occupancy (Board and Care), which includes a section
for larger and smaller types of facilities. Sample Building Types Alcohol and drug
centers Assisted living facilities (can also be classified as Residential) Congregate
care facilities (16 or fewer occupants) Convalescent facilities Group homes
Halfway houses Residential board and custodial care facilities Social rehabilitation
facilities I‐2 This type is for medical, surgical, psychiatric, nursing, or other type of
care on a 24‐hour basis for more than five persons. These occupants are not
capable of self‐preservation. If fewer than five people are being cared for, the
occupancy would typically be reclassified as Residential. The similar NFPA
category is under a separate occupancy classification called Health Care. Sample
Building Types Day care centers (24‐hour) Detoxification facilities Foster care
Hospitals Infirmaries Limited care facilities Mental hospitals Nursing homes
(intermediate care and skilled nursing) Psychiatric hospitals Treatment or
rehabilitation centers I‐3 This type is for the detention of more than five persons.
These occupants are incapable of self‐preservation due to security measures.
Additional “conditions” based on the level of security provided and the amount of
free movement allowed within the building must be considered to accurately
determine the specific code requirements for this use. (This topic is beyond the
scope of this book.) The similar NFPA category is the Detention/Correction
occupancy classification, which is divided into five separate subclassifications (see
Figure 3.2), depending on the level of security. The LSC has special conditions for
lock‐up areas in facilities other than Detentional/Correctional. These areas are
similar to those in typical I‐3 facilities, as the occupants are incapable of self‐
preservation due to security measures. However, only one person has to be held in
this condition for these requirements to apply. A lock‐up area is most typically
located in facilities such as immigration centers at border crossings; customs
facilities in international airports; prisoner holding at police departments; or
security areas at parks, sports stadia, and similar uses. Sample Building Types
Correctional institutions Detention centers Jails Prerelease centers Prisons
Reformatories Work camps I‐4 This type is for the care of more than five persons
for less than 24 hours a day. This includes adults and children under 2 years of age.
One typical exception is that if adults in this type of facility are capable of self‐
preservation without help from staff, it would be reclassified as an R‐3. (See
Residential occupancy R‐3.) Another is when the area where children are cared for
opens directly to the exterior; it can then be reclassified as Educational. This is
considered a Day Care occupancy in the NFPA codes. Sample Building Types
Adult day cares Day care centers—caring for infants (can also be classified as
Educational) Mercantile (M) Occupancy Note According to the NFPA codes, a
small use that would normally be classified as a type of Assembly occupancy, such
as a small diner, can sometimes be classified as Mercantile. (In the IBC, this may
be reclassified as Business.) A building or part of a building is classified as a
Mercantile occupancy if it is open to the public and used for the display, sale, or
rental of merchandise. This classification includes most stores and showrooms, and
in some codes includes large malls. The IBC groups these into one main
occupancy. Mercantile in the NFPA codes has three subclassifications based on the
type and size of the building. (See Figure 3.2.) A group of retail stores may have
additional code requirements. Each store would be considered a separate
Mercantile occupancy. However, as a group, the stores may also be considered a
covered mall. The codes have special requirements for malls because, in addition
to the large anchor retail stores and the multiple smaller retail tenants, there can be
other uses within the same building. Most typically, these include restaurants and
entertainment areas. In some cases, the general Mercantile requirements apply; in
other cases, the requirements for a covered mall may apply to the project. (Usually
one or the other will be used.) These mall requirements can be found in the
“special occupancy” chapter of the IBC. In the NFPA codes, special requirements
for malls are called out within the Mercantile chapter. When necessary, review
these requirements with the local code official. Sample Building Types Auction
rooms Automotive service stations Bakeries Department stores Drug stores
Grocery stores Markets Paint stores (without bulk handling) Rental stores Retail
stores Salesrooms Shopping centers Showrooms Specialty stores Supermarkets
Wholesale stores (other than warehouses) Residential (R) Occupancy A building or
part of a building that acts as a dwelling and provides sleeping accommodations for
normal residential purposes is designated a Residential occupancy. Most of the
codes further categorize this classification based on the probable number of
occupants and how familiar they are with their surroundings. For example, a
person in a hotel would probably not be familiar with the escape routes, making it
more hazardous. Such an occupancy will be subject to stricter codes than an
apartment complex, where tenants should be more familiar with their surroundings.
In some cases, the number of units in the building may also make a difference. (For
other occupancies that provide sleeping accommodations but with additional care,
see Institutional occupancy.) Note Certain Residential building types may have to
be reclassified as Institutional, depending on the number of occupants and their
length of stay. Examples include day care centers and nursing homes. The IBC has
four Residential subclassifications: R‐1 through R‐4. The NFPA codes separate
these into five separate classifications: Apartment Buildings, Hotels and
Dormitories, Lodging or Rooming Houses, One‐ and Two‐Family Dwellings, and
Board and Care. (See Figure 3.2.) Although these categories are similar to those in
the IBC, there are differences. Refer to the applicable code to determine the correct
occupancy or subclassification. (Also see the inset titled “Rooms and Spaces” later
in this chapter.) Note The term dwelling unit is often associated with Residential
and Institutional occupancies. (See the inset titled “Rooms and Spaces” in this
chapter for more information.) R‐1 This type is for occupants who are transient—
in other words, those who do not stay for an extended period of time. If occupants
typically stay more than 30 days, a building type may be required to be reclassified
as R‐2 or another use. In the NFPA codes, transient residential building types are
addressed separately as hotels in the Hotels and Dormitories subclassification or
the Lodging or Rooming Houses subclassification. Sample Building Types
Boarding houses (transient with more than 10 occupants) Congregate living
facilities (transient with more than 10 occupants) Hotels Inns Lodging and rooming
houses Motels Rooming houses Note Congregate living facilities are most often
classified as an R‐2. This building type contains sleeping units but shared
bathroom and/or kitchen facilities (e.g., a small boarding house). If it is a large
facility, it may be classified as R‐1 or I‐2. R‐2 This type is for buildings that
contain more than two dwelling units with occupants who are somewhat permanent
(less transient). The similar NFPA categories include Apartment Buildings,
Lodging or Rooming Houses, and Hotels and Dormitories. CUSTODIAL CARE
VERSUS MEDICAL CARE Determining the correct occupancy classification
when care is being provided for occupants often is determined by the number of
persons receiving care. However, in some cases the type or level of care should be
considered. The codes specify two basic types of care: custodial and medical.
Custodial care includes assistance with typical daily tasks such as cooking, taking
medications, bathing, and other personal care. This level of care assumes that the
person receiving care is capable of responding to an emergency situation but
potentially at a slower rate. Their conditions may include physical or mental
impairments. Medical care includes care or treatment involving medical or surgical
procedures, nursing care, or psychiatric care. These occupants are often considered
not to be able to respond in the event of an emergency because of their current
physical or mental condition. Residential occupancies often assume that only
custodial care is being provided. Institutional occupancies and ambulatory care
facilities assume that some level of medical care is being provided. Sample
Building Types Apartments Boarding houses (nontransient with more than 16
occupants) Congregate care facilities (nontransient with more than 16 occupants)
Convents Dormitories Fraternities/sororities Hotels (nontransient) Live/work units
Monasteries Motels (nontransient) Multiple single‐family dwellings Vacation
timeshare properties R‐3 This type is for more permanent residences but, unlike R‐
2, is most often used for single or duplex units. The typical single‐family home
falls into this category. Some residential care facilities (see R‐4) may also be
allowed under this classification if the number of occupants is limited to less than
10 or the length of stay is less than 24 hours. Congregate living facilities for 16
persons or fewer are typically included in this subclassification as well. If the I‐
Codes are used, a jurisdiction will typically require the use of the International
Residential Code (IRC) for the specific code requirements for single and duplex
residences. Each NFPA code references its chapter on one‐ and two‐family
dwellings as well. (See Appendix C for more information on family residences.)
Verify with the local code official which code is applicable to residential projects.
Note The accessibility chapter of the IBC requires that the work area and the
residential area of a live/work unit be evaluated separately. Sample Building Types
Facilities that do not contain more than two dwelling usages Boarding houses
(nontransient with 16 or fewer occupants) Boarding houses (transient) with 10 or
fewer occupants Care facilities (5 or fewer persons receiving care) Congregate
living facilities (nontransient with 16 or fewer occupants) Congregate living
facilities (transient with 10 or fewer occupants) Note Single‐family homes and
duplex units are classified as an R‐3 occupancy by the IBC and typically require
use of the International Residential Code (IRC). The NFPA designation is One‐
and Two‐Family Dwellings. (Refer to Appendix C.) R‐4 This type is for small to
medium‐sized residential care facilities. This occupancy is based on the number of
persons receiving custodial care on a 24‐hour basis and does not include staff. The
typical number of residents is between 6 and 16. If fewer people are receiving care,
it may be considered an R‐3. If a larger number of people are receiving care or if
medical care is also being provided, then it may be considered Institutional. These
occupants are capable of self‐preservation. (See I‐1.) The similar NFPA category
would be Residential Board and Care. It could also be considered a Health Care
occupancy by the NFPA, depending on the number of occupants. If these types of
facilities are protected by an automatic sprinkler system, they may be able to
follow the requirements of the IRC instead of the IBC. Sample Building Types
Alcohol and drug abuse centers Assisted living facilities (can also be classified as
Institutional) Convalescent facilities (can also be classified as Institutional) Group
homes Halfway houses Retirement homes Residential board and care facilities
Social rehabilitation facilities Storage (S) Occupancy A building or a predominant
part of a building is classified as a Storage occupancy if it is used for storing or
sheltering products, merchandise, vehicles, or animals. Minor storage uses, such as
smaller storage rooms and supply closets, are typically treated as part of the
predominant occupancy. As with Factory/Industrial occupancies, low‐ or
moderate‐hazard contents are typically allowed in the Storage occupancy, although
the storage of high‐hazard contents may cause the building or space to be classified
as Hazardous. The classification depends on the type of hazard and the quantity of
material being stored. It can also be affected by how the products are stored, i.e.,
on pallets or in containers. It is important to check the code to determine the level
of hazard of the material being stored. A list of low‐ and moderate‐hazard items
follows, but remember that each code groups them differently and each level will
have slightly different requirements. The IBC has two storage subclassifications,
one for moderate hazards (S‐1) and another for low hazards (S‐2). The NFPA has
only one main storage classification. If unsure about the types of hazardous
materials being stored, check with the local code official. In addition, within
Storage building types, it is generally understood that relatively few people will
occupy the space. If the number of occupants is large or increases substantially in
the future, the building occupancy may have to be reclassified. Sample Building
Types Aircraft hangars (nonhazardous) Cold storage facilities Creameries Freight
terminals and depots Grain elevators Repair garages (nonhazardous) Truck and
marine terminals Warehouses (nonhazardous) Asbestos Beer or wine up to 12
percent alcohol in metal, glass, or ceramic containers Cement in bags Chalk and
crayons Cold storage Dairy products in non‐wax‐coated paper containers Dry cell
batteries Dry insecticides Electrical coils Electrical insulation Electrical motors
Empty cans Food products Foods in noncombustible containers Fresh fruits and
vegetables in nonplastic trays or containers Frozen foods Glass Glass bottles,
empty or filled with noncombustible liquids Gypsum board Inert pigments Ivory
Meats Metal cabinets Metal desks with plastic tops and trim Metal parts Metals
Mirrors New empty cans Oil‐filled and other types of distribution transformers
Open parking structures Porcelain and pottery Stoves Talc and soapstone Sample
low‐ and moderate‐hazard storage contents Washers and dryers Utility (U)
Occupancy A building or part of a building that is not typical and/or cannot be
properly classified as any of the other occupancy groups is often classified as a
Utility, Special, or Miscellaneous occupancy. The building codes and LSC list
different items in this category, and they are usually covered as a group in a
separate chapter or in multiple chapters within each of the codes. If unsure whether
a building would be considered a Utility or Miscellaneous occupancy, check with
the local code official in the early stages of a project. (Unusual structures are
beyond the scope of this book.) Note The IBC also includes requirements for
children's playground structures. This applies to play areas inside any occupancy if
it is a certain size. The requirements address size, materials, fire protection, and
separation from other elements. Sample Building Types Agricultural buildings
(including barns, stables, livestock shelters) Carports Grain silos Greenhouses
Livestock shelters including stables Open structures Parking garages (can also be
classified as Storage) Private garages Retaining walls Sheds Tall fences (over 6
feet, or 1829 mm) Tanks Temporary structures Towers If one of the typical
occupancies is being housed in an unusual structure, additional codes are usually
required. Examples include high‐rise, underground, and windowless buildings.
And, if special conditions are required in particular space or are a specific use,
such as Ambulatory Care facility, hyperbaric facilities, or storm shelters, additional
codes may be required. These will generally be assigned to one of the occupancies
discussed above, but they need special attention and further research because of the
additional code requirements they must meet. NEW VERSUS EXISTING
OCCUPANCIES Because a majority of code requirements are based on the
occupancy classification of the space or building, it is important to understand their
differences. For many projects, additional occupancy‐related issues must be
considered. In some cases, for example, different code requirements may apply
depending on whether the project is considered a renovation or a new construction.
Whether an occupancy is considered new or existing becomes especially important
when using the Life Safety Code because the LSC separates its regulations into
these two different categories for each occupancy classification. The new or
existing designation for these occupancies will affect how the codes must be
applied. An occupancy is considered new if it falls into one of the following
categories: The occupancy is in a building or space constructed for that occupancy
under the currently enforced code edition. The occupancy is relocated to an
existing building previously not used for that occupancy. The occupancy is in a
new addition to an existing building previously not used for that occupancy. The
occupancy is remaining in the same building but changing its size or use that
affects its subclassification. This last category is important to remember because it
is the least obvious. In some cases a change in size or use will cause the occupancy
classification to be considered new. However, in other cases, if the change does not
result in an increase in hazards or risk factors, the code official may allow it to
change subclassification but still be considered existing. A change in occupancy
classification can affect a number of other code regulations, including those found
in the building codes, the International Existing Building Code (IEBC), and the
LSC. (See Appendix B for more information on changes in occupancies in existing
buildings.) If the occupancy is considered new, then many changes may be
required to the entire space. If the occupancy is considered existing, then many of
the existing conditions may be allowed to remain the same. ROOMS AND
SPACES Each building or space must be assigned an occupancy classification so
that it can be determined which codes apply. In addition, certain rooms within an
occupancy can have specific requirements. This is especially true in Residential
and Institutional occupancies. The codes have very distinct definitions for various
types of spaces, depending on how those spaces are utilized. The following are
commonly referenced in the codes: Occupiable space. A room or enclosed space
designed for human occupancy that is equipped with means of egress, light, and
ventilation, as required by the codes. This can include the spaces and rooms in
most occupancies. It excludes such areas as mechanical and electrical rooms, crawl
spaces, and attics. If a space is not considered occupiable, it usually does not have
to meet typical accessibility requirements as specified in the building codes, the
ICC standard, or the ADA. Dwelling unit. A single unit providing complete
independent living facilities for one or more persons, including permanent
provisions for living, sleeping, eating, cooking, and sanitation. Building types that
fall into this category include single‐family homes, apartment units, townhouses,
and certain assisted living units. However, a hotel guest room or dorm room can
also be considered a dwelling unit if it has a kitchenette, eating area (i.e., table or
bar top), and living area (i.e., upholstered seating area) in addition to the typical
sleeping area and bathroom. (The ICC standard and the IBC divide dwelling units
into Type A and Type B types for accessibility reasons. Type B dwellings have
requirements similar to those of the FHA Accessibility Guidelines (FHAG). Type
A dwellings have additional requirements for accessibility.) Live/Work unit. A
dwelling unit or sleeping unit where a significant portion (greater than 10 percent,
but less than 50 percent) is used for nonresidential use by the tenant. It has a
maximum area of 3000 square feet (279 sm) and must be located on the main floor
of the unit. (A typical home office would not be considered a live/work unit.)
Sleeping unit. A sleeping unit or room is used primarily for sleeping and does not
fit the definition of a dwelling unit. The space often includes a bathroom, but it
would not include a cooking area (or it could include a kitchen area but no
bathroom). Examples include typical guest rooms in hotels and boarding houses,
jail cells, dorm rooms, and patient rooms in nursing homes or hospitals. Guest
room or suite. A guest room (or suite) is for living or sleeping in and may include
sanitation and storage facilities within a compartment or a contiguous group of
rooms. Examples include rooms and/or suites in hotels, motels, and dormitories.
Care suite. A special grouping of treatment rooms or sleeping rooms and their
support rooms and the circulation space to the rooms. The arrangement usually
occurs in Institutional or Health Care occupancies and typically must be under
direct supervision by staff. Examples include an emergency suite or a critical care
suite in a hospital. Living area or room. This is considered any occupiable space in
a Residential occupancy, other than sleeping rooms or rooms that are intended for
a combination of sleeping and living. It includes spaces such as bathrooms (or
toilet compartments), kitchens, closets, halls, and storage/utility spaces, but can
also include other rooms such as living rooms, dining rooms, family rooms, and
dens. Habitable room. A room in a Residential occupancy that is used for living,
sleeping, cooking, and eating, but excludes such things as bathrooms,
storage/utility spaces, and hallways. The designation of new and existing
occupancies in the LSC and other NFPA documents allows the code official to
require existing facilities, not just new occupancies, to maintain safe environments
for their occupants even if the use does not change. Under the typical building
code, including the IBC, new code requirements do not become retroactively
applicable to an existing occupancy. Only when the space is renovated or a major
addition is made can existing space be required to meet the newer codes. Note
When using the LSC, it makes a difference if the project is considered new or
existing. The IEBC may be required instead of the IBC in some jurisdictions.
Remember, a change in occupancy classification or subclassification can be subtle,
yet it can change the requirements for the space. For example, if a restaurant
changes to a nightclub or a restaurant changes the seating arrangements so that
more people can occupy the space, both can result in a change of occupancy
classification. Even these slight modifications can change the sprinklering,
occupant load, exit requirements, and so forth. MORE THAN ONE
OCCUPANCY TYPE Two or more occupancies can occur in the same building. In
fact, it is actually more common to see several different occupancies in the same
building than to see a single‐occupancy building. A common example is a large
hotel. Many large hotels have restaurants, indoor pools, conference areas, and spas.
The hotel itself would be classified as Residential, but the restaurants, pools, and
conference areas would be considered Assembly occupancies, and the spa would
be classified as a Business occupancy. Note When more than one occupancy
exists in the same building or space, it will be considered an accessory, mixed, or
multiple occupancy. A variety of examples are listed here so that different building
types can be analyzed and differences between various uses can be distinguished.
(There are many other possibilities.) Notice how often the Assembly and Business
occupancies occur together. These are common occupancies in mixed building
types. Hotels (Residential) with restaurants, ballrooms, or workout rooms
(Assembly or Business) Elementary, middle, and high schools (Educational) with
gymnasiums, auditoriums, and cafeterias (Assembly) Office buildings (Business)
with day care centers (Educational or Institutional) Hospitals (Institutional) with
cafeterias (Assembly) Reformatories (Institutional) with recreational rooms
(Assembly) and offices (Business) Factories (Industrial) combined with the office
headquarters (Business) Malls (Mercantile) with small restaurants (Business) or
large food courts (Assembly) It is important to determine if more than one
occupancy is occurring in the same building. If so, it can affect a number of other
codes, such as those listed in Figure 3.1. These different occupancies can be
adjacent horizontally, as in the Plan in Figure 3.3, or vertically in the case of a
multi‐story building, as shown in the Section in Figure 3.3. Because each
occupancy type has different safety risks, special measures are necessary to make
the building safe. In general, the codes require that either the occupancies be
separated or all of them be treated as one, using the most stringent requirements.
The codes describe the relationship of more than one occupancy differently. The
International Building Code refers to the relationship as accessory, separated
mixed, or nonseparated mixed. In a similar way, the NFPA codes, including the
Life Safety Code, define different occupancies as either accessory, mixed multiple,
or separated multiple occupancies. The requirements for each type of “mixed”
occupancy are described in the next sections. For all of these, the ultimate goal is
to provide the safest building possible. Figure 3.3 Mixed occupancies: Horizontally
and vertically (1 square foot = 0.0929 square meter). Incidental Use Certain uses
within a building are determined to be more hazardous when they occur in any
occupancy type. Previously referred to as incidental use areas and incidental
accessory occupancies in the IBC, they are now referred to as incidental uses. They
are referred to simply as hazardous areas in the NFPA codes. However, in both sets
of codes, if their size is limited, they are not considered a separate occupancy. For
example, the laundry room within the preschool facility (Educational) shown in
Plan A of Figure 3.4 would be considered an incidental use within the other
primary‐use areas such as classrooms and office areas. Figure 3.4 Incidental use
versus accessory occupancy (1 square foot = 0.0929 square meter). The types of
spaces and rooms that are considered incidental use are indicated within the codes
either in a table (IBC) or in the text (NFPA). These spaces include boiler rooms,
furnace rooms, large laundry rooms, and other spaces containing hazardous items
or machinery. The size of the use is limited by the codes. In the IBC, the use
cannot exceed 10 percent of the building area of the floor on which it is located. In
addition, both the IBC and the NFPA codes provide minimum areas for when the
use will be considered an incidental use. For example, the IBC lists specific
incidental uses in a table, as shown in Chapter 6 in Figure 6.8 . As indicated in this
table, additional fire and smoke protection is required for these areas. (This is
discussed further in Chapter 6.) When this additional protection is provided, all
other code requirements for the incidental accessory occupancies follow the codes
required for the main occupancy. If this protection is not provided, the building
must be classified as a mixed occupancy. (See the section “Mixed Occupancies”
later in this chapter.) The NFPA codes list these areas within the occupancy
chapter in which they are most likely to occur. For example, the requirement for
separation of soiled linen rooms can be found in the Health Care occupancy
chapter. Accessory Occupancies Sometimes two or more occupancies exist in a
building, but one or more of them is much smaller than the main occupancy type.
In this case, the smaller occupancy(ies) may be considered an accessory occupancy
by the codes. In the IBC, for instance, an area can be considered an accessory use
if the smaller occupancy classification(s) is less than 10 percent of the total area of
the floor on which it is located. (The NFPA codes may allow the accessory use to
be a larger percentage of the overall area.) So, using the IBC, an example would be
a furniture store that offers design services, as shown in Plan B of Figure 3.4. The
furniture store is Mercantile (M), but the design center area would be Business (B).
However, since the area of the design center is less than 10 percent of the overall
area, it can be considered an accessory to the main Mercantile occupancy. And,
because it can be considered an accessory use, the two areas will not have to be
designed under separate occupancy requirements. Sometimes there are several
smaller uses occurring within a larger occupancy classification, and all are located
in the same building. An example would be a large discount store, like the one
shown in Plan A of Figure 3.5. This particular store has a bakery, photo shop, hair
salon, and snack bar as part of its space. In this case, all the accessory spaces
combined cannot be more than the allowable percentage of the total area. Figure
3.5 Accessory versus occupancy examples (1 square foot = 0.0929 square meter).
Note The NFPA codes allow an accessory occupancy to be a larger percentage of
the overall space or building than does the IBC. In addition to the proportionality
requirement, an accessory occupancy cannot exceed the allowable area for that
occupancy classification in relation to the construction type of the building. For
example, Plan B in Figure 3.5 is an electronics store (Mercantile, or M) with its
warehouse located in the same building. The warehouse is considered a Storage (S‐
1) occupancy. It could be considered an accessory occupancy by the IBC because
it does not exceed 10 percent of the total area of the building. However, because
the area of the S‐1 occupancy exceeds the allowable area for this particular
construction type, the S‐1 occupancy cannot be considered an accessory to the
Mercantile. In this case, the storage area would be considered a separate storage
occupancy and would have to meet the code requirements for an S‐1 occupancy
classification instead of the requirements for a Mercantile occupancy. In some
cases, certain areas are allowed to be accessory regardless of the percentage of
area. For example, Assembly areas with an occupant load less than 50 and areas
with less than 750 square feet (69.7 sm) can be considered accessory to the main
occupancy—a small training room in an office space, for instance. However, in
both the IBC and the NFPA codes, some occupancies cannot be considered
incidental or accessory to any other classification. This includes Day Care
occupancies (except for religious uses) and certain types of Residential and
Educational building types. (Hazardous occupancies can never be considered as
accessory to another occupancy.) It is useful for design purposes to determine if an
area can be considered accessory to the main area, because it simplifies the code
requirements and allows areas to be more open. If the smaller occupancy(ies)
cannot be considered accessory, the space or building would have to be designed
as a separated or nonseparated mixed occupancy regardless of the size. (See the
next section.) When there are approved accessory occupancies within a space or
building, most of the code requirements (including the means of egress
requirements) are based on the main occupancies. The fire protection requirements,
however, are based on the most restrictive use (whether the accessory or main use)
and apply to the entire building or space. Mixed Occupancies When two or more
occupancies in a building or space are about the same size or do not meet the
requirements to be considered an accessory use, it is a mixed occupancy. To
address the specific situation, the IBC further divides mixed occupancies into
separated mixed occupancies and nonseparated mixed occupancies. (The NFPA
codes also use the term separated but only in relation to multiple occupancies. This
is explained later in this chapter.) When the different occupancies are divided by
the required rated assemblies (e.g., walls, floor, and/or ceiling assemblies), these
occupancies are considered by the IBC to be separated mixed occupancies. (The
requirements for rated assemblies are discussed further in Chapter 5.) Once
separated, each occupancy only needs to meet the requirements of its own
occupancy classification. For example, in Plan A in Figure 3.6, the Business (B)
occupancy and the Mercantile (M) occupancy are separated by a rated wall. Thus,
the code requirements for the Business occupancy would apply to the post office
and the Mercantile requirements would apply to the shoe store. Figure 3.6 Mixed
occupancies in the IBC: Separated and nonseparated (1 square foot = 0.0929
square meter). When there is no rated separation between the occupancies, it is
considered by the IBC as a nonseparated mixed occupancy. (This term is not used
by NFPA.) When the occupancies are considered nonseparated, both of the
occupancies must then meet the requirements of the most stringent occupancy
classification, including construction type, allowable area, finishes, fire protection,
and exiting requirements. For example, in Plan B of Figure 3.6, the Mercantile (M)
and Assembly (A‐2) occupancies are separated by a partition only for visual
reasons and so are considered nonseparated. In this case, the more stringent
Assembly requirements for the restaurant would be applied to the entire area of the
building, including the gift shop. In buildings where there are both separated and
nonseparated mixed occupancies,
Kennon, Katherine E.; Harmon, Sharon K.. The Codes Guidebook for Interiors
(pp. 136-184). Wiley. Kindle Edition.
not meet the requirements to be considered an accessory use, it is a mixed
occupancy. To address the specific situation, the IBC further divides mixed
occupancies into separated mixed occupancies and nonseparated mixed
occupancies. (The NFPA codes also use the term separated but only in relation to
multiple occupancies. This is explained later in this chapter.) When the different
occupancies are divided by the required rated assemblies (e.g., walls, floor, and/or
ceiling assemblies), these occupancies are considered by the IBC to be separated
mixed occupancies. (The requirements for rated assemblies are discussed further in
Chapter 5.) Once separated, each occupancy only needs to meet the requirements
of its own occupancy classification. For example, in Plan A in Figure 3.6, the
Business (B) occupancy and the Mercantile (M) occupancy are separated by a
rated wall. Thus, the code requirements for the Business occupancy would apply to
the post office and the Mercantile requirements would apply to the shoe store.
Figure 3.6 Mixed occupancies in the IBC: Separated and nonseparated (1 square
foot = 0.0929 square meter). When there is no rated separation between the
occupancies, it is considered by the IBC as a nonseparated mixed occupancy. (This
term is not used by NFPA.) When the occupancies are considered nonseparated,
both of the occupancies must then meet the requirements of the most stringent
occupancy classification, including construction type, allowable area, finishes, fire
protection, and exiting requirements. For example, in Plan B of Figure 3.6, the
Mercantile (M) and Assembly (A‐2) occupancies are separated by a partition only
for visual reasons and so are considered nonseparated. In this case, the more
stringent Assembly requirements for the restaurant would be applied to the entire
area of the building, including the gift shop. In buildings where there are both
separated and nonseparated mixed occupancies, additional requirements apply. For
instance, the most stringent fire protection requirements will apply to the entire
building. Note Both the IBC and the NFPA codes use the term separated for when
two or more occupancies are divided by rated assemblies—called separated mixed
by the ICC and separated multiple by NFPA. Many factors influence the decision
to treat a mixed occupancy as separated or nonseparated. Constructing rated
assemblies for separation can be expensive or undesirable for the design, but
having to meet the most stringent exiting requirements, construction type, or area
limitations for the whole building or space may limit the design unnecessarily. All
these factors must be considered to determine the better choice for a project.
Multiple Occupancies Multiple occupancies is a term used by the NFPA codes (not
the I‐Codes). It occurs when two or more occupancies exist in a building or space
either horizontally or vertically. Multiple occupancies are designated more
specifically as mixed or separated. The NFPA codes consider a building or space
to be a mixed multiple occupancy when two or more occupancies exist together
and are “intermingled.” This can occur if (1) there is no rated separation(s)
between the occupancies, (2) the different occupancies use the same exiting
components (aisle, corridors, stairs, etc.), or (3) both conditions exist. For example,
refer again to Plan B in Figure 3.6; because there is no rated separation between
the Assembly (A‐2) and Mercantile (M) occupancies, it is considered a mixed
multiple occupancy. In addition, if a portion of the occupants from the restaurant
must exit through the gift store as part of the required exiting, that would also
make it a mixed occupancy. Note The term mixed multiple occupancy is unique to
the NFPA. Although similar to nonseparated mixed occupancies in the IBC, a
mixed multiple occupancy includes a wider variety of building scenarios. A
different type of mixed multiple occupancy is shown in Plan A of Figure 3.7.
These occupancies are separated by rated walls and may seem to be separated
occupancies. However, because the tenants share the corridor when exiting from
each space, it would be considered a mixed multiple occupancy by the NFPA
codes. If a multiple occupancy is considered mixed, the construction type, fire
protection, and means of egress, as well as other requirements, must follow the
most restrictive occupancy requirements. (In this way, it is similar to nonseparated
mixed occupancies in the IBC.) Figure 3.7 Multiple occupancies in the NFPA
codes: Mixed and separated. On the other hand, if the occupancies are separated by
rated walls but do not share exiting, then the NFPA considers the area a separated
multiple occupancy. Like the separated mixed occupancy in the IBC, each space
must only meet the code requirements for its occupancy classification. An example
of a separated multiple occupancy can be seen in Plan B of Figure 3.7. Here the
multiple occupancy classifications are separated from each other by a rated wall. In
addition, each has its own separate means of egress, so they do not share a
common corridor. All of these factors make it a separated multiple occupancy.
Note If they meet all the code requirements, incidental accessory use and accessory
occupancies will not make a building a mixed‐use occupancy. The NFPA codes
designate how a mixed or separated multiple occupancy should be handled. More
specific information on multiple occupancies may also be found within each
occupancy chapter. These requirements supersede the general requirements for
mixed or separated occupancy classifications. These individual occupancy chapters
must be reviewed to know when they apply. In addition, a code official may need
to be consulted to determine which requirements will apply to the different areas
versus the whole building. This is especially important if working in a jurisdiction
that requires both the IBC and the LSC. ACCESSIBILITY REQUIREMENTS
Under certain conditions, almost all occupancy classifications can be considered
public accommodations and/or commercial facilities and can be regulated by the
ADA Standards under the ADA. In addition to the general accessibility
requirements described throughout this book, the ADA Standards include specific
requirements for certain building types within various occupancies. The building
codes and the ICC A117.1 accessibility standard also include some similar
requirements, although these are not as extensive as those of the ADA Standards.
Note Both the 1991 ADA Standards and the 2010 ADA Standards include
regulations specific to certain occupancies. Refer to these requirements for details.
The following is a list of building types found in the ADA Standards and the
special accessibility requirements required for each. (The type of occupancy
classification is indicated as well.) This list is based on the 2010 ADA Standards.
In addition, there are specific storage requirements for any occupancy that requires
accessible storage as well as additional requirements specifically for dwelling units
(Residential). When working within these occupancies, the code research should
include reviewing the current ADA Standards as well as comparing them to the
ICC A117.1 standard, the accessibility chapter of the IBC, and other codes
enforced by the local jurisdiction to see if there are contradictory or stricter
requirements. Other federal accessibility regulations may also apply (e.g., FHAG
and ABA Standards), as explained in Chapter 1, and additional regulations for
certain occupancies may be added in the future. When necessary, consult the local
code official or the ADA Access Board for clarification. Assembly Areas
Percentage of accessible wheelchair locations Location and dispersion of
wheelchair spaces and companion seats Access to performance areas Types of
floor surfaces Assistive listening systems requirements Types and placement of
listening systems Businesses and Mercantile Size of checkout counters and work
surfaces Clearance and height of self‐service shelves/display units Size of teller
windows and information counters Width and quantity of checkout aisles Note
Many requirements of the 2010 ADA Standards are similar to those in the ICC
A117.1 and the accessibility chapter of the IBC. Clearance at security elements
Number, size, and types of dressing/fitting rooms Type and clearance of automatic
teller machines Medical and Long‐Term Care Facilities (Institutional and Health
Care) Size of covered entrances for unloading patients Percentage of accessible
toilets Percentage and dispersion of accessible patient bedrooms Dispersion of
accessible patient bedrooms Size of maneuvering spaces in patient rooms
Clearance area at patient beds Width of accessible doors and aisles Restaurants and
Cafeterias (Business or Assembly) Percentage of accessible fixed tables Access to
sunken and raised platforms Width of food service lines Height of counters and
self‐service shelves Access to controls of vending machines Width of access aisles
Transient Lodgings (Residential) Percentage of accessible sleeping rooms
Dispersion of accessible elements in types of rooms Specific requirements within
accessible rooms Number and dispersion of rooms for hearing‐impaired Dispersion
of accessible rooms suitable for disabled with multiple disabilities (mobility,
hearing, visual, etc.) Access to rooms and public and common areas Width of door
openings Size of maneuvering spaces Percentage of accessible amenities (ice
machines, washers and dryers, etc.) Clearance, height, and hardware of storage
units Housing at Places of Education (similar to Transient Lodging and
Residential) Percentage of accessible units Dispersion of accessible elements
among accessible rooms Specific requirements within accessible rooms Access to
rooms and public and common areas Width of door openings Accessible
circulation within units Access to kitchen units Judicial, Legislative, and
Regulatory Facilities (Business and Assembly) Access to secured entrances
(including an accessible security system) Access to courtroom elements (judge's
bench, jury assembly, and deliberation areas, etc.) Access to holding cells (and
amenities) Dispersion of accessible cells Accessible security systems Percentage of
assistive listening systems Detention and Correctional Facilities (Institutional)
Percentage of holding and housing cells or rooms (and amenities) Dispersion of
accessible cells Access to cells and visiting areas Spaces for Children (Educational
and certain Institutional) Access to drinking fountains Access to toilet facilities
(including water closets, toilet stalls, lavatories) Access to dining and work
surfaces Adjusted reach ranges Height of handrails at ramps and stairs Height of
mirrors Height of controls Transportation Facilities (Assembly or Business)
Boarding areas Signs Accessible routes Communication elements Recreational
Facilities (Assembly) Percentage of accessible sauna and steam rooms Number of
accessible means of entry to pool Number of accessible shooting facilities
DESIGN LOADS Occupant loads as described in this chapter are not to be
confused with two other types of design loads required by the codes: dead loads
and live loads. Dead loads include all permanent components of a building's
structure, such as the walls, floors, and roof. Live loads, in contrast, include any
loads that are not the actual weight of the structure itself. They include interior
elements such as people, furniture, equipment, appliances, and books. Other loads
that are sometimes considered live loads but are separate exterior elements include
wind loads, rain and flood loads, snow loads, and earthquake loads. These types of
load factors affect the design of the building's structure. Dead load and live load
calculations are typically done by engineers during the initial design and
construction of a building. Most of the calculations take into consideration that
some of the loads will change during the normal use of a building. For example, in
an office building it is common for interior walls to change and be relocated as
tenants move. The number of people will vary as well. Some interior projects may
require certain live loads to be researched when significant changes are proposed
in a project. The most common situations include (1) adding a wall, such as brick
or concrete, that is substantially heavier than a standard wall; (2) creating a filing
area or library that concentrates the weight at one point; (3) adding a heavy piece
of equipment; and (4) adding an assembly seating area in an existing space. In
most cases, a structural engineer is needed to determine if the existing structure
will hold the added load/weight. If not, the structural engineer will determine how
to add additional support, if possible. Social Service Establishments (Residential)
Access to beds Access to accessible toilet and roll‐in showers DETERMINING
OCCUPANT LOADS In addition to determining the occupancy classification at
the beginning of a project, the occupant load (OL) must also be determined. The
occupant load is used to determine how many people can safely use the space. It
sets the number of occupants for which adequate exiting must be provided from a
space or building. Proper exiting allows people to evacuate safely and quickly.
Usually, the occupant load is determined for each space or building either by using
a load factor given by the code or by establishing a desired number of occupants. If
multiple spaces will be exiting into a common area or converging into a common
path of travel, the codes require that the occupant load for the shared area be
determined by adding the number of occupants who will share a common path to
an exit. These methods can be used to determine the number of people that is
assumed will be using the corridors, stairs, and exits in the event of a fire.
Occupant loads are often based on a relationship between the size and use of the
space or building. In most cases, this means that a larger space allows more
occupants, and the need for more occupants requires a larger space. In some cases,
the number of occupants can be increased without increasing the size of the space.
However, the building codes, such as the International Building Code and the Life
Safety Code, do set limits on the allowable concentration of occupants within a
building. In addition, the occupant load may be needed to determine the occupancy
classification. An example is a restaurant with an occupancy under 50 (Business)
and a restaurant with an occupant load over 50 (Assembly). It is important to
determine the occupant load early in the design process: Not only will it provide
guidance in the correct selection of a building's occupancy classification, but it
affects other codes as well. For example, the occupant load is needed to size the
means of egress components, such as number of exits and the width of corridors
and aisles. (See Chapter 5.) The number of required plumbing fixtures and certain
mechanical calculations also depend on the occupant load. (See Chapter 8.) The
remainder of this chapter explains occupant loads. Occupant Load by Load Factor
Because most means of egress requirements are based on the occupant load, the
code must establish a minimum level of safety. To do this, each code assigns a
predetermined amount of area or square feet (or square meters) required for each
occupant based on the occupancy classification and the specific use of the space.
This predetermined figure is called the load factor. Using the load factor to
determine the occupant load typically generates the lowest number or minimum
number of occupants for which the space must be designed. Note Occupant loads
are typically determined using the load factors given by the codes. Using the Table
Each code discusses occupant load requirements, including load factors and exiting
requirements, within the means of egress chapter. The NFPA codes, including the
LSC, have additional occupant load factors and requirements in each separate
occupancy chapter as well. Figure 3.8 is the load factor table from the IBC, titled
“Table 1004.1.2, Maximum Floor Area Allowances per Occupant.” The NFPA
codes have similar load factor tables. The load factors for a specific use may be
different between the codes. For example, the load factor for a commercial kitchen
in the IBC is 200 sf (18.58 sm); in the LSC, it is 100 sf (9.3 sm). A code may also
have specific load factors for unique uses that may not be included in the other
code. For example, the NFPA codes have a load factor for “concentrated Business
use” (for uses similar to call centers where small cubicles create a higher
occupancy rate than a typical Business use) and Ambulatory health care (which is a
health care use but different than a hospital and a typical doctor's office). The IBC
does not specify a load factor for these uses. Figure 3.8 International Building
Code Table 1004.1.2, Maximum Floor Area Allowances per Occupant (2015
International Building Code, copyright© 2012. Washington, DC: International
Code Council. Reproduced with permission. All rights reserved. www.iccsafe.org).
Note In some cases, it may be possible to design a space for an occupant load less
than that calculated by the load factor. However, it usually requires additional
design documentation and approval by a code official. To use Table 1004.1.2 in
Figure 3.8, you must first determine the specific function of the space. See the first
column titled “Function of Space.” This column lists the different uses for spaces
within a building. Although some uses are similar to occupancy types, you must
choose the specific use of the space. For example, although Assembly is noted as a
general use, there are three main types, including “Assembly with fixed seats” and
“Assembly without fixed seats.” In addition, under the latter, there is the option of
“Concentrated (chairs only—not fixed),” “Standing space,” or “Unconcentrated
(tables and chairs).” Again, the specific use of the space must be considered not the
occupancy type. For example, bowling alleys are considered an Assembly
occupancy. But in this chart, bowling centers is a separate category of use and has
a unique floor area factor. The occupant load factors are listed in the next column
in square feet per person. (A metric conversion is shown at the bottom of the
table.) These areas are given for each of the specific uses regardless of occupancy
classification. For example, if you were designing the classrooms for a college, you
would still use the “Educational, Classroom area” occupant load factor to
determine the occupant load of the space even though the space would be assigned
to a Business occupancy. The load factor indicates the amount of space or area it is
assumed each person present will require. Although the square foot figures may
seem high for one person, they allow for furniture and equipment and, in some
cases, corridors, closets, and other miscellaneous areas. The area for each load
factor refers to the floor area within the exterior walls of a building. The load
factors are designated as gross or net area. The gross area refers to the building as a
whole and includes all miscellaneous spaces within the exterior walls. The net area
refers to actual occupied spaces and does not include ancillary spaces such as
corridors, restrooms, utility closets, or other unoccupied areas. The area of fixed
items, such as interior walls, columns, and built‐in counters and shelving (areas
that are not habitable), are also deducted from the overall area. When net figures
are required, it is assumed that the occupants who are using an ancillary area would
have left the occupied space to do so and, therefore, would already be taken into
account. For example, a person in the corridor of a school would most likely be a
student or teacher already accounted for in a classroom. However, you must
consider the actual use of a space, even a corridor. The Formula The formula that
is used with the load factor tables is Note The load factor does not mean that each
person is required to receive a particular amount of square feet (square meters)
when space planning a project. The figure is used only to determine an occupant
load. The placement of furniture, equipment, and walls will affect the size of the
final space. To determine the occupant load for a building or space, take the area of
the interior space and divide it by the load factor for the appropriate building type
and/or use. If the space or building has more than one type of use, the same is done
for each area according to its use and added together. This provides the number of
occupants that is allowed in the space. If the total results in a fraction over a half of
an occupant, round up to the nearest whole number. Depending on the project,
calculations for separate areas and separate occupancies may also need to be made
and added together. The final occupant load indicates the number of occupants for
which the space must be designed. Note The NFPA codes give load factors in
square feet and in metric dimensions. The IBC provides a metric conversion at the
bottom of the load factor table. Example 1 To further understand the difference
between gross and net area and how to use the load factor table, refer to the floor
plan for a library in Figure 3.9. “Library” is listed separately in the IBC table in
Figure 3.8. This building type is further divided into two separate functions:
reading rooms and stack area. A study room, corridor, and utility closet are also
noted on the plan. These will have to be addressed as well. The occupant load for
each separate function must be determined separately. Figure 3.9 Occupancy load
example: Single occupancy (Library) (1 square foot = 0.0929 square meter). Note
Gross area includes all areas within the exterior walls. Net area consists of all areas
within the exterior walls minus ancillary spaces such as corridors, restrooms, utility
closets, and other unoccupied areas. The load factor for the stack area of the library
is indicated in the table in Figure 3.8 as 100 gross square feet (9.3 sm). So, the area
measurement should include the entire stack area with aisles, reference area,
checkout counter, and so forth. The occupant load factor for the reading rooms is
indicated to be 50 net square feet (4.6 sm), meaning that the area should not
include ancillary spaces. Although there is not a specific function listed in the table
in Figure 3.8, a study room use is similar to a small conference room. A small
conference room may be determined by using the Assembly‐Unconcentrated
(tables and chairs). The load factor for this use is 15 net square feet (1.39 sm). Both
the reading room and the study room areas call for net load factors. Therefore, the
corridor or the utility closet adjacent to the reading rooms on the floor plan should
not be included when determining the area of the reading room or study room.
These areas are essentially left out of the load factor calculation because they are
not considered to contribute additional occupants to the library. Using the
dimensions of the floor plan and the occupant load formula to determine the area
for each space, Figure 3.9 shows how to determine the occupant load for the entire
library. Rounding up, the total occupant load is 40 people. Example 2 Sometimes,
load factors can be used in a slightly different way. If the area required for a
particular occupancy or use needs to be determined, the load factors may help
establish the space requirements. This may be helpful in the programming stage of
a project. For example, if planning a new office space for a client with 125
employees, the table can be used to look up the occupant load factor under
Business areas (100 gross square feet, or 9.3 sm). Multiply this factor by the
number of people intended to occupy the space (125) to determine the minimum
size of the space needed. In this case, at least 12,500 square feet (1161.3 sm) will
be required, according to the codes. This can be done for a smaller use such as a
break room or conference room as well. Although this will provide a good estimate
and the minimum required by code, typically other program requirements must be
added to that area to determine the final size of a space or building. Modifying the
Occupant Load In some cases, it might be desirable to have more people occupy a
space than are determined by the load factor. However, if an increased occupant
load of a space is allowed, additional exiting for the increased number of occupants
must typically be provided. This may require providing additional diagrams
showing aisles, exit widths, seating configurations, and/or locations of fixed
equipment to the code official for approval. Note New occupant load factors
added in recent editions of the IBC include day care centers and exhibit gallery and
museums. For example, a client is developing a restaurant and he has a space that
is 5000 square feet (464.5 sm) for use as the dining area (Assembly). Referring to
the load factor table in Figure 3.8, the load factor is 15 gross square feet (1.4 sm)
for an “Assembly without fixed seats, Unconcentrated (tables and chairs).” By
dividing 5000 square feet (464.5 sm) by 15 gross square feet (1.4 sm), the result is
an occupant load of 333 occupants. However, if the client wanted to be able to seat
400, then 400 would be considered the desired occupant load—the modified
number. The means of egress (i.e., exits, aisles, corridors, and number of doors)
would then be designed for an occupant load of 400. That would also be the
maximum number allowed within the space at any one time. Making sure that the
space can be designed to handle the increased exiting requirements and other
accessible clearances is also necessary. When designing for an increased occupant
load, it is advisable or may be required to review it with the code official early in
the design process. There may be instances when a reduced number is desirable so
that a space is designed for a number of occupants less than the calculated load.
For example, a workshop may not typically be occupied by the number of
occupants determined by the load factor because of the size and amount of
equipment used in the room. Generally, designing for a lower number is not
allowed. Similar to designing for an increased occupant load, designing for a
reduced number would require approval by the code official. Justifying the use and
the reduced number would be required as well. In addition, to allow the lower
occupant load, the code official can require special conditions and limitations for
use of the space. Remember, designing the space for the lower occupant load can
affect the future use of the space because of the lower means of egress capacity.
Occupant Load for Primary and Secondary Spaces When one or more smaller
spaces exits into a larger or primary space before reaching the final exit, the codes
usually require that the occupant load of the primary space include the occupant
loads of the secondary spaces that exit through it. Two examples are shown in
Figure 3.10. The business offices are secondary spaces within the Business
occupancy. Occupants must walk through the open office area in order to exit the
space. However, the training room would also be considered a secondary space,
since it too must empty through the open office area. In this case, the occupant load
for the large training room in Figure 3.10 should be calculated separately using an
Assembly (A) factor, not the load factor of the main Business (B) occupancy.
When these separate calculations are added together, they provide an occupant
load that more accurately addresses the use of the space. Figure 3.10 Occupant
load example: Primary and secondary spaces. Note If the allowable occupant load
of a space needs to be increased, a maximum load factor of 7 square feet (0.65 sm)
could be used. This is the maximum density allowed by the code. An accessory
space can sometimes be considered a secondary space as well. For example, the
occupant load for the design center (B) in Figure 3.4B should be added to the
occupant load of the Mercantile (M) portion of the furniture store, since the
occupants of the design center must walk through the store to exit the building.
Each would be calculated separately according to the load factor for its use. This
total would be used to determine the exiting from the primary space. Occupant
Load for a Building Floor Whenever there is more than one use or occupancy
classification on the same building floor, additional calculations are typically
required. If a building floor is occupied by a single tenant but has a variety of
functional spaces such as offices, cafeteria, and locker rooms, the occupant load of
each area must be calculated. These will be added together to determine the total
occupant load of the floor. Likewise, if the floor has multiple tenants that may be
different occupancies such as Business, Mercantile, and Assembly, the occupant
load must be calculated for the separate tenants using the load factors for the
different functions with the individual tenants. The exiting requirements for each
tenant space must be designed for their occupant load. Further, if these
occupancies or tenants share common spaces such as exiting corridors or
restrooms, the occupant load of each tenant is then added together to determine the
total occupant load for the floor. This will be used to establish the requirements for
the common areas (including public toilet facilities) and the exiting requirements
for the entire floor. (This is described more in Chapter 5.) This process is similar
whether calculating the occupant load under the IBC (mixed occupancies) or the
NFPA 101 (mixed‐multiple occupancies.) A simple example is shown in Figure
3.11. In this example, there is a mixture of Mercantile (M) and Business (B) spaces
on the first floor and multiple Business (B) spaces on the second floor. Figure 3.11
Occupant load example: Mixed/multiple occupancy building (1 square foot =
0.0929 square meter). One way to figure the occupant load for the first floor is to
calculate the occupant load separately for each tenant space and required common
areas and then add them together. Another way (as shown in Figure 3.11) is to
combine the areas for all the occupancy classifications and uses that are the same
(i.e., all the Business occupancies) and then use the load factor for that use. The
same would then be done for the Mercantile occupancies. In this case, because a
gross load factor is required, the public areas (i.e., lobby, restrooms, main corridor)
will also have to be included in the calculations. Typically, this would be
proportionally divided among the different occupancy types, as shown in Figure
3.11. (See the note at the bottom of the figure.) Once the occupant load for each
occupancy/use or each tenant is determined, add them together with the common
areas to get the total occupant load for the whole floor. The total occupant load on
the first floor is 205. The same process is used for the second floor, as shown in
Figure 3.11. However, in this case there is only one occupancy/use type. The total
occupant load for the second floor is 124. The occupant load for each floor
(including common areas) will be used for code requirements such as exiting,
which affect the entire floor and the stairs. (See Chapter 5.) It will also be used to
determine the number of plumbing fixtures in the common toilet facilities on each
floor. (See Chapter 8.) Areas with Multiple Uses Some buildings or building areas
are used for different purposes at different times. For example, a church fellowship
hall might be used for a large assembly one night and as a cafeteria the next. The
following weekend, it might be used as a gymnasium or exercise room. In other
words, any area of a building that has more than one function is considered to have
multiple uses. The occupant load is determined by the use that indicates the largest
concentration of people. Several calculations may be required to determine which
occupancy will provide the largest number. Occupant Load for Fixed Seats Fixed
seating arrangements are common in some building types, especially in Assembly
occupancies. The seats are considered fixed if they are not easily moved and/or if
they are used on a relatively permanent basis. Instead of using the standard formula
for calculating the occupant load when separate fixed seats are present, the actual
seats are counted. For example, the occupant load in a movie theater, as shown in
Plan A of Figure 3.12, would be determined by the number of seats used in the
space (including spaces specifically created for wheelchair users). Figure 3.12
Occupant load example: Occupancies with fixed seats. Note When reading code
tables, it is important to read all the footnotes at the bottom of the tables for
additional information and possible exceptions. Counting seats with arms is self‐
explanatory. However, fixed seating may also consist of continuous seating such as
benches, bleachers, and pews. Each of the codes provides a variable (either in the
occupant load table or the text) to be used for continuous seating. They typically
allow 18 linear inches (457 mm) of seating for each occupant. If, for example, a
church has 28 pews and each pew is 12 feet long, as shown in Plan B of Figure
3.12, the 18‐inch (457 mm) variable would be used. A 12‐foot pew equals 144
inches (3658 mm). Divide the 144 (3658 mm) by the 18‐inch (457 mm) variable to
get 8 people per pew. Because there is a total of 28 pews, this church has an
occupant load of 224 people (28 pews × 8 people/pew). Note The continuous
seating variable will not always evenly divide into the length of the seating.
Usually, if the remaining fraction is one‐half or greater, round
Kennon, Katherine E.; Harmon, Sharon K.. The Codes Guidebook for Interiors
(pp. 181-209). Wiley. Kindle Edition.
Booth seating is another type of continuous fixed seating. Booth seating usually
has a separate variable provided by the codes. The typical increment is 24 inches
(609.6 mm). For example, Plan C in Figure 3.12 shows several types of booth
seating. Each should be calculated separately. Measure the length of the bench
along the front edge (especially at corners) and divide by 24 inches (609.6 mm).
Add all the calculations together to determine the occupant load for the bench
areas. This would be added to the occupant loads of the other seating areas within
the space to determine the total occupant load of the restaurant. All areas of a
building or space have to be included in the occupant count. If the space has
different types of seating and different types of activities occurring, each area
would be assigned by its specific use. For example, a nightclub might have fixed
seating in one area, tables and chairs in another, and a dance floor in another. In
this case, calculate the occupant load for all the different areas separately and add
them together to get the final count. Occupant Load for Unusual Uses There may
also be occasions when the building type or the use of a space is not typical. The
occupant load factors given in the code table may not be appropriate for a unique
use, or a specific occupancy use may not be listed on the table. On other occasions,
a space may not clearly fit into one of the use categories. When this occurs, it is
important to meet with a code official for guidance. Typically, only the code
official can approve a different or unique load factor. This decision should be made
at the beginning of a project, because occupancy classifications and many of the
codes that will apply depend on the determined occupant load. Note Open areas
adjacent to spaces with fixed seats may require additional occupant load
calculations. The open area may be considered standing space and increase the
occupant load. USING THE OCCUPANT LOAD The occupant loads determined
at the beginning of a project will be used again later in the code research to
determine several aspects of the design. Occupant loads will be used to determine
the capacity of the means of egress, such as the number of exits and the width of
the exits. They will also be used to determine the number of plumbing fixtures and
to size a mechanical system. (This is discussed in Chapters 4 and 7.) The space
should be designed to be adequate for the occupant load and the occupant load
should be appropriate for the intended use. Also be aware that changes in the
occupant load may affect the occupancy classification and many of the applicable
code requirements. It should be clear that these have an interactive relationship that
can potentially affect several aspects of the design. Note Every assembly room or
Assembly occupancy usually requires the approved occupant load to be
permanently posted near the main exit from the space. A typical sign might read:
“Occupancy by more than 100 persons is dangerous and unlawful.” In all cases,
adequate means of egress must be provided for the number of people who will be
occupying a space or building. Once the occupant load is set and the means of
egress have been designed, the number of people allowed within a space cannot
exceed that number. For Assembly uses, the approved occupant load is required to
be posted for each space. In other spaces, a code official may require the approved
occupant load to be posted where a modified occupant load has been used to
design the space. Exceeding the posted allowable occupant load is unsafe and
unlawful. RESEARCH AND DOCUMENTATION It is important to accurately
determine and document both the occupancy classification(s) and the occupant
load(s) at the beginning of a project, since most code requirements will depend on
them. For some projects, the occupancy classification may be straightforward or
already determined. For some, you must consider the risk factors and unique
conditions that exist within the space or building. Compare them to the definitions
of each occupancy classification and/or subclassifications. From what you know
about the activities within the space and these risk factors, you should be able to
determine the correct occupancy classification. If hazards are present, consider
them as well. (Each of the code publications lists the types of hazards to look for
and whether they are explosive, fire, physical, or health hazards.) It may not
always be necessary to get approval from your code official at this point in a
project, but each situation is different. (See the section “Preliminary Review” in
Chapter 11.) You do not want proceed with research or design if it is not clear.
Note Not only can a building have more than one occupancy, but each occupancy
can have more than one use for the purpose of determining the occupant load.
Therefore, one building or a large tenant space could require a number of
calculations. Keep in mind that you may have more than one type of occupancy
within the space or building, incidental uses, accessory uses, mixed occupancies
(separated or nonseparated), or multiple uses (mixed or separated) as discussed in
this chapter. You need to document this as well as it may affect other aspects of the
project like location of rated walls (discussed in later chapters). It may be helpful
to create a diagram of the different uses and occupancies in the space or building.
Also, determine if the space will be considered new or existing according to the
codes. This will be important if you are using the LSC. (You may also be required
to use the International Existing Building Code.) In the construction documents,
the occupancy classification and occupant load should be stated. Usually this is
included on the coversheet as a diagram or list. You can use the Occupancy
Classification section of the digital Code Checklists provided with this book. This
will help you determine and document the occupancy classification(s) and
occupant load(s) aspects of your project.
Kennon, Katherine E.; Harmon, Sharon K.. The Codes Guidebook for Interiors
(pp. 209-212). Wiley. Kindle Edition.
CHAPTER 5
MEANS OF EGRESS A means of egress is most commonly described as a
continuous and unobstructed path of travel from any point in a building to a public
way. A means of egress comprises both vertical and horizontal elements, including
doorways, corridors, passageways, stairs, ramps, and intervening rooms. The
design of these components is crucial to the safety of the building occupants in
normal use of a building and especially during emergencies. There are two main
strategies for the means of egress: evacuation and “defend in place.” Evacuation
means that the occupants will be provided with a direct path out of the building. In
a defend in place strategy, occupants will go to a specific area, either on the same
floor or on another floor, to wait for assistance and/or be provided with an
alternative method to exit the building. Every means of egress has various
components. This chapter explains how these components work together. The first
half of the chapter concentrates on explaining the components of the means of
egress. The rest of the chapter discusses how to determine the required quantities,
sizes, and locations of the parts of the means of egress. Accessibility requirements
are also discussed throughout the chapter. Although the codes usually separate
means of egress codes and accessibility requirements, they should be considered
together. In most cases, the means of egress will be required to be accessible or
special conditions must be provided. This chapter has combined the discussion of
these topics wherever possible. (The figures typically show the strictest
requirements as well.) Remember that not every type of means of egress mentioned
in this chapter will be used in every interior project. In addition, many existing
buildings will already have the correct number of exits. If working with just one
occupant or tenant in the building, only the exiting within and from that tenant
space may need to be considered. It may generally be safe to assume that the
number and size of the exits and exit stairways have been correctly designed for
the building. However, some projects may require reevaluating the existing exit
requirements and making alterations, especially if the number of occupants has
been significantly increased. This may require more extensive calculations. Either
way, every interior project must meet specific means of egress requirements. Note
There are two basic strategies for means of egress: evacuation of occupants and
“defend in place.” This chapter discusses the wide variety of codes, standards, and
federal regulations that pertain to the means of egress. Some of the requirements
are based on occupant loads, as discussed in Chapter 2. Specific fire ratings are
also required for each means of egress. Chapter 5 explains the fire‐rating
requirements for building materials and assemblies. Chapter 9 explains the
different types of finishes allowed in each area of a means of egress.
COMPARING THE CODES Although the various codes define the parts of the
means of egress in similar ways, the specific requirements can vary. For instance,
all the codes agree that the means of egress include exit accesses, exits, and exit
discharges. However, the required width of exits, allowable length of corridors,
and hourly fire resistance rating of the components and similar requirements may
differ between codes. The building codes and the Life Safety Code (LSC) set most
of the requirements for the various parts of the means of egress. Each of these code
publications has a chapter dedicated to means of egress. In the NFPA codes,
specific requirements are also included in the individual occupancy chapters. In the
LSC, these requirements may also be different for new or existing buildings or
spaces. If a jurisdiction enforces a building code as well as the LSC, these
requirements will have to be compared so that the most restrictive ones are used.
Note The 9/11 Commission Act of 2007 is a federal legislation that calls for the
development of voluntary, private‐sector standards for emergency preparedness.
Some of these standards are included in the LSC appendixes to provide additional
emergency evacuation requirements. The fire codes include requirements that
affect the means of egress as well. In the International Fire Code (IFC), for
example, the chapter titled “Means of Egress” includes several sections that repeat
the information found in the means of egress chapter in the IBC. However, the IFC
also includes maintenance requirements so that the means of egress remain usable
after the building or space is occupied. These include limitations on the use of
decorations, mirrors, and other objects that may obstruct the egress path. In
addition, the IFC includes special requirements for existing buildings that may
allow exceptions to the requirements for new buildings. (See Appendix B.) In the
“Emergency Planning and Preparedness” chapter of the IFC, the code requires that
occupants be made aware of evacuation procedures. This typically includes
announcing the location of exits at assembly events and practicing fire drills in
schools. The fire code also often requires egress patterns to be posted in certain
locations. In addition, staff be instructed and review procedures for evacuation for
certain occupancies. Although these requirements may not directly affect the
design of a space, in some cases development of these diagrams is part of the
project. The ICC Performance Code (ICCPC) also has a chapter dedicated to
means of egress. Additional information is included in the chapter titled
“Pedestrian Circulation.” That chapter includes accessibility criteria as well. Each
NFPA code includes a performance chapter with specific criteria. Although the
ICCPC chapter does not set specific requirements for means of egress, it does
require that a building and its design allow occupants sufficient time to evacuate,
relocate, or have a “defend in place” location. Obviously, this could be achieved in
several ways. The chapter also sets several objectives for safety during an
emergency that affects the means of egress. Although all the same elements of a
means of egress discussed by the prescriptive codes—such as area of refuge, travel
distance, and unobstructed path—can be part of a performance design, those
specific terms are usually not used by performance codes. Instead, the phrases are
more generic, like “safe place,” “appropriate to the travel distance,” and “adequate
lighting.” Therefore, it may not matter if a particular area is a corridor or a
passageway according to the definition of the prescriptive code. Instead, what
matters is how it works within the path to safety. In addition, performance codes
require the designer to consider the characteristics of the occupants, the features of
the design, and the hazards that may exist to identify the specific challenges of
egressing a particular space or building. For example, consider if the occupants can
move to an exit independently, if they can exit at a normal rate or a slower rate, or
should not exit a building for safety or security reasons. Understanding the special
conditions that exist within a building and using performance criteria may allow a
unique and appropriate system of evacuation to be developed. Prescriptive codes
may then be used to define other specific elements of the means of egress, such as
the location of exit signs and emergency lighting. (Rarely are performance codes
used for design of the entire means of egress.) As always, when using performance
criteria, establish the appropriate criteria of the design and then provide supporting
evaluations and information to the code official for approval. Note Many
accessibility requirements are similar in the ICC A117.1 standard and the 2010
ADA Standards; however, both should be checked to make sure the most stringent
requirements are used. Because the means of egress in most cases is required to be
accessible, these requirements must also be reviewed in conjunction with the
appropriate federal or local accessibility regulations or standards. (See Chapter 2.)
In addition to the ADA standards, the ICC A117.1 accessibility standard may
apply because it is referenced by the IBC and/or it may be used as a stand‐alone
standard by a local jurisdiction. As discussed throughout this chapter, accessibility
requirements will affect the size of many of the means of egress components, as
well as the shapes and mounting heights of the various elements that occupants
must use as part of the means of egress. Some of these differences that occur
between documents are explained in this chapter. Others may be found as more
research is done for a specific project. Remember, if there is a conflict in the
requirements, the strictest requirements must be met—in other words, satisfy the
need for both accessibility and safety. In addition, review the means of egress
requirements for the specific occupancy classification(s) of a project. Although
most of the regulations are consistent, some occupancies allow exceptions or have
additional requirements. Some of the exceptions are given in the means of egress
chapters, and others are grouped by occupancy classification in different sections
of the codes. Assembly occupancies especially must be reviewed, as the use of
fixed seats can create unusual egress paths. (See the section “Aisles and Aisle
Accessways” later in this chapter.) Note The Access Board, ICC, and NFPA have
created comparison documents of the accessibility requirements found in each of
their respective publications. These documents can be found on their websites.
MEANS OF EGRESS COMPONENTS Means of egress is a broad term that
encompasses almost every part of a building interior as well as some exterior
elements. Each of the codes divides a means of egress into three main categories:
exit access, exit, and exit discharge. In all cases, a public way is the final
destination of a means of egress. In some cases, an area of refuge will also be a
part of the means of egress, as explained later. The means of egress components
are defined as follows: Note An exterior space can be either an exterior exit
discharge or a public way. To be a public way, the space must be at least 10 feet
(3048 mm) wide and 10 feet (3048 mm) high and be considered a public space.
Exit access: The portion of a means of egress that leads from any occupied area to
the entrance of an exit. It includes any room or space occupied by a person and any
doorway, aisle, corridor, stair, or ramp traveled on the way to the exit. Exit: The
portion of a means of egress between the exit access and the exit discharge or
public way. It is often required to be physically separated from other interior
spaces. It can be as basic as an exterior exit door or it can include enclosed
stairwells and ramps. In some special cases, it can include certain corridors or
passageways. The enclosure for exits are often distinguished from the exit accesses
because they are required to be fire‐resistant rated. (See Chapter 6.) Area of refuge:
A space or area where persons who are unable to use a stairway (or elevator) can
remain temporarily to await instructions or assistance during an emergency
evacuation. Exit discharge: The portion of a means of egress between the
termination of an exit and the public way. It can be inside a building, such as the
main lobby; or outside a building, such as an egress court, courtyard, patio, small
alley, or other pathway to the public way. Public way: The area outside a building
that is legally considered public. Examples include a street, an alley, or a sidewalk.
The area must have a minimum clear width and height of not less than 10 feet
(3048 mm) to be considered a public way. The intent is to be a destination where
occupants would be safe from exposure to a fire in the building. It is important to
understand the relationship of these components and when each exists. The
simplest relationship is when the exit access leads directly to an exit that takes
occupants out of the building. This is shown conceptually in Figures 5.1A and
5.1B. In the first diagram, the exit is simply an exterior door. Figure 5.1 Means of
egress components. In the second diagram, the exit is an exit stair that opens at the
bottom to the exterior of the building. In some cases, an exit does not end at the
exterior of the building or public way but leads into an exit discharge. As shown in
Figure 5.1C, the exit discharge connects the exit to the public way. The exit
discharge can be either inside or outside the building. In either case, the code will
have specific requirements for its use. The typical means of egress assumes that
occupants can exit the building without any special help, including using stairs.
However, at least one “accessible means of egress” must be provided and if more
than one means of egress is provided from a space, at least two accessible options
must also be available. This type of egress path is usable by a greater range of
occupants, including those with mobility limitations who, for example, cannot use
the exit stair to exit the building. In an accessible means of egress, the common
components of a means of egress (i.e., exit access, exit, etc.) meet the same
requirements. It is often the way the occupant reaches the public way that makes it
accessible. For example, an area of refuge may be used. An area of refuge is not
considered the end point for the accessible means of egress, but instead is a place
where people with disabilities can wait for additional help to reach the public way.
As indicated in Figure 5.1D, an area of refuge can occur adjacent to but before
entering an exit stairway or within the exit stairway. In one scenario, emergency
personnel will assist or carry the occupant down the stairway to the public way. In
special cases, an area of refuge can be included in the elevator lobby. In this case,
emergency personnel will assist the occupant to use the specially equipped elevator
to egress the building to the public way. (See Figure 5.13.) In some cases, as
shown in Figure 5.1E, the exit access leads through a horizontal exit to an area of
refuge on the same floor. If necessary, emergency personnel will take disabled
occupants down a stairway or elevator from the area of refuge side of the building.
(See the sections “Areas of Refuge” and “Horizontal Exits” later in this chapter.)
Note An area of refuge is a component of an “accessible means of egress.” In some
cases, it may be considered part of an exit or exit discharge. In order to know the
requirements that apply to a particular space, it is necessary to know whether that
space is part of the exit access, exit, or exit discharge. For example, the finish
classifications required for an area that is an exit access will differ from those for
an area that is part of an exit. (See Chapter 9.) Some means of egress
Kennon, Katherine E.; Harmon, Sharon K.. The Codes Guidebook for Interiors
(pp. 249-258). Wiley. Kindle Edition.
components within a space may be easy to identify. For example, exit stairs are
always considered exits. For others, the path of the occupants may have to be
considered to correctly identify the component and its role within the means of
egress. For example, a corridor may be part of the exit access, exit or exit
discharge. This is demonstrated on the floor plan in Figure 5.2. Figure 5.2 Means
of egress in a typical building.
Kennon, Katherine E.; Harmon, Sharon K.. The Codes Guidebook for Interiors
(pp. 258-260). Wiley. Kindle Edition.
Recognizing that a space could be considered to be more than one part of the
means of egress, the path of the occupant to the exit or public way can help
determine each component in the means of egress. In the floor plan in Figure 5.2,
different shading patterns indicate whether the space is considered an exit access,
an exit, an exit discharge, or a public way. For example, if a person were standing
in the lobby of this diagram, the distance from the person to the exterior door
would be the exit access and the exterior door would be the exit. Once through the
exterior door, the person would be in an exterior exit discharge (egress court),
because, in this case, the sidewalk is the public way. However, for a person coming
down the stairway at the left of the plan and emptying into the lobby, the stairway
is the initial exit component, the lobby is then part of the exit discharge, and the
exterior door is the end of the interior exit discharge because it leads to the exterior
of the building. From that point, the egress court continues as an exterior exit
discharge until it reaches the sidewalk, as previously discussed. When a space can
be considered more than one part of the means of egress, it must meet the
requirements of the most restrictive component. Note If a building or space is only
required to have one exit, it typically must be an accessible means of egress.
Although the parts of an exit can be defined somewhat differently by the various
codes, they all assume that a means of egress will be continuous. This path
provides protection to the occupant from the point and floor of origin to the ground
level and public way. The requirements for the means of egress components ensure
that the level of protection is maintained until the occupant is in the public way.
What follows is a description of the types of means of egress and the various
components of each. Exit accesses are described first. These components are
elaborated in more detail, since similar components in the other means of egress
categories have many of the same requirements. For example, exit access stairs and
exit stairs are used for different purposes and require different fire protection, but
they both use the same tread and riser dimensions, landing widths, handrail
requirements, and so on. EXIT ACCESSES An exit access is the portion of a
means of egress that leads to an exit. It leads an occupant from anywhere in a room
or space to an exit (including the room itself).
Kennon, Katherine E.; Harmon, Sharon K.. The Codes Guidebook for Interiors
(pp. 260-261). Wiley. Kindle Edition.