Acoustics and Architecture
BSApps
Mechanical Worksheet
Rev B
Summary
| Workshop | Question | Pg No | Notes |
| M1 | 1 to 5 Answers | 4-8 9 | U values and Heat loss |
| M2 | 6 to 11 Answers | 10-16 17 | Heat gains |
| M3 | 12 to 13 Answers | 18-21 22 | Radiator Selection |
| M4 | 14 to 16 Answers | 23-25 26 | Flow rates |
| M5 | 17 to 18 | 27-41 | System Pressure Drop |
| 42 | Concluding thoughts |
At this point I will be providing answers only.
Full working out will be provided later in the year.
Formula
Equation 1
Where:
QM = Mechanical load required to maintain a steady internal temperature (note that if this is positive then heating is required, negative means cooling)
Qc = Conduction Heat Loss
QI = Infiltration Heat Loss
QV = Ventilation Heat Loss
QOCC = Occupancy
QL = Lighting
QE = Equipment
QS = Solar
For heat loss only the equation can be substituted with:
Air:
x =1.2kg/m3
Water:
= 4.19 kg/m3
H
Workshop M1
Q 1-5
U value and heat gains
M1 : Q1-5
Typical U-Block Wall Build Up
A typical detail is shown opposite, which can be simplified to the following table:
M1 : Q1-5
Typical U-Block Wall Build Up
Calculate the U value for this element
Assuming all insulation (mineral wool and kooltherm) is replaced with straw.
What is the U value with the same thickness?
Straw λ = 0.06W/m.K
When replacing the insulation with straw. How thick does the wall need to be to achieve the same thermal performance?
M1 : Q1-5
Calculate the overall heat loss (in Watts) using the information below
Also make note of the fabric coefficient [] and Infiltration coefficient (NV/3).
External air temperature = -3°C
Internal temperature = 20°C
Room Dimensions:
Length = 20.9m
Width = 9.7m
Height = 5.5m
Glazed area = 35.7m2
Infiltration rate = 0.2 ACH
No internal gains, assume unoccupied.
The space has a floor below and above it which are at the same temperature.
Assume the wall to the south is the same length as the wall to the North (I.e. 9.7m)
U values
Glazing: 1.6 W/m2K
Wall : 0.25 W/m2K
Calculations:
M1 : Q1-5
What would be the result if there was a roof above the office?
External air temperature = -3°C
Internal temperature = 20°C
Room Dimensions:
Length = 20.9m
Width = 9.7m
U value of roof equivalent to minimum Building Regulations Part L:
Make a note of the following figures for later:
Revised coefficient of Fabric Heat Loss, Cf = ΣUA
Answers
Q1
- Rtotal = 7.52 m2.K/W
- U value = 0.133 W/m2.K
Q2
- Rtotal = 4.08 m2.K/W
- U value = 0.25 W/m2.K
Q3
- Insulation thickness = 416mm
- Overall Buildup of wall = 595mm
Q4
- = 102.7 W/K
- NV/3 = 74.3 W/K
- Heat loss = 4,070 W
Q5
- Heat Loss = 5,236 W
- = 153.4 W/K
Notes
Always provide units!
You may have slightly different answers, which if within 2-3% is likely to be from rounding rather than your calculations….but do double check.
If you are struggling with the answer, then come and ask me
Workshop M2
Q6 – 11
Heat Gains
M2 : Q6-11
Calculate the occupancy, lighting and equipment heat gain within the meeting room:
Use the tables in the following page
Make a suitable assumption about the heat output of people (W/person) (table 6.3)
Work out the occupant density of each space and calculate the number of people (table 6.2)
Work out the total heat gains from occupancy (based on above numbers) and lighting/equipment based on table 6.2
At what external temperature does the occupancy alone within the space balance the thermal losses?
Keeping an operative temperature of 20oC
Ignore all other internal gains
What occupancy heat gain would you use if this was an activity studio?
(take a look back at the previous tables)
Complete the solar gain exercise on the following pages
M2 : Q6-11
N
M2 : Q6-11
Determine the peak solar gain for the space during July and August when external ambient temperatures are likely to be hotter from the tables* included on the following page using the solar gain equation included in the lecture notes.
Façade glazing areas:
Glazed area to façade A = 10.2m2
Glazed area to façade B = 18.6m2
Glazed area to façade C = 6.9m2
Façade glazing properties:
Effective G-value = 0.4
*We are using data for London as it is the closest location for these data sets which are only available for London/ Manchester/Edinburgh
A
B
C
M2 : Q6-11
At any point on a building:
Where:
Ag = Area of glazing
= Incident Solar Radiation
geff = Glazing G value
(proportion of heat transmitted)
These terms can be derived from literature and where multiple rooms exist then the load needs to be calculated for a specific time of day
M2 : Q6-11
Solar gains incident on the are building are provided by the following chart from CIBSE Guide A
M2 : Q6-11
10.2m2
A
6.9m2
C
18.6m2
B
10.2m2
A
6.9m2
C
18.6m2
B
Use the formula to work out the solar gains at each time of day then find the maximum
Answers
Q6 - 75 W/person
Q7 - 17 people
Q8 - Qocc = 1,267 W
- QE = 3,041 W
- QL = 2,027 W
Q9 Can you get to this formula:
Q10 This answer is subjective. What do you think?
Q11 QS
QS = 4,506 W (what month and time of day is this?)
Workshop M3
Q12 – 13
Radiator Selection
M3 : Q12-13
Based on the result from Question 5 select a suitable radiator for the space based on keeping the room to a minimum of 12°C overnight.
Make the following assumptions:
Heating circulation water temperatures – Flow = 75°C Return = 65°C
Internal temperature = 12°C
External temperature = -5 °C
Assume that you are going to use 4 equally sized radiators
Hint: Correct the radiator outputs using the table opposite
(ΔT = Mean Water Temperature – Room Temperature)
Radiator table on the next page
M3 : Q12-13
M3 : Q12-13
Calculate the steady state heat loss during the day and reselect a suitable radiator for the space from the information provided.
Make the following assumptions:
External air temperature = 0°C
Internal temperature = 20°C
Assume space is occupied with the heat gains you worked out within question 8.
The office has a daytime occupancy of 17, requiring 10 l/s/person
Assume that the space is ventilated with the minimum required
We will assume it’s a cold overcast day, so ignore any solar gains.
Steady State Heat losses are calculated using the following
When selecting the radiator use the following:
Heating circulation water temperatures – Flow = 75°C Return = 65°C
Internal temperature = 20°C
Assume that you are going to use 4 equally sized radiators
Assume space is occupied internal gains exist (assume the loads calculated previously in Question 8)
Hint: Correct the radiator outputs using the table opposite
(ΔT = Mean Water Temperature – Room Temperature)
21
Answers
Q12 - 969 W per radiator.
Selection of radiator is variable depending on the height and choice of radiator
For example P+ type with dimensions 600mmx600mm (don’t forget to inc the k factor)
What other options are there?
Q13 - 597 W per radiator.
For example K1 radiator from the radiator selection table which is 600mm high by 700mm wide
What other options are there?
What do these two results tell you?
Workshop M4
Q14-18
Water Flow Rates and Pressure Drop
M4 : Q14-16
AHU used to provide heating
Instead of naturally ventilating the space it is assumed that a small air handling unit will be used instead. This is shown below right and has a fan and a heating coil. What is the heat load in the heating coil?
Assume again that the external temperature = 0°C
Internal temperature is = 20°C
Occupancy as calculated earlier (17 people)
Air Flow Rate = Minimum Ventilation Rate
Hint: Use the following equation to establish the heat load required by the air
For air
=1.2kg/m3
=1.02kJ/kg.K
Heater
Fan
Filter
M4 : Q14-16
If the air handling unit was also to be used to maintain room temperature in the space.
Consider the following:
Part a)
What would be the required air supply temperature,
Maintain the same volume of air as calculated in Q14
Calculate the heat load balance using the heat gains from earlier
Formula:
&
Part b)
What is the new heat load in the heating coil?
Calculate the heating water flow rates required for the following:
Part a)
Radiators used at night. Calculate the flow per radiator and the combined flow of all 4 radiators in the room.
Use the load calculated from Q12
Part b)
The air handling unit coil used to heat the space during the day
Use the load calculated from Q15.
Answers
Q14a -
Q14b -
Q15 - 2,393W
Note: see any similarities with Q13 answer?
Q16a -
Q16b -
Q17 and 18 answers will be provided after the workshop.
M4 : Q17-18 : Pressure Drop
These questions are provided along with an excel spreadsheet on blackboard.
The questions include a worked through example for part of the work. Follow this through before trying to undertake the questions.
The next slide shows the overall schematic for the system.
27
This drawing is an extract from the heating layouts for the SU
It shows the heating pipework connecting a number of underfloor heating systems on the first floor.
M4 : Q17-18 : Layout
28
In this worked example we investigate the pipework connecting manifolds to the riser.
(in effect assume the riser is the plantroom)
The first step in developing a schematic is to label key nodes
These nodes are either junctions or system end points as shown
M4 : Q17-18 : Layout
29
M4 : Q17-18 : Schematic
The schematic should then set out the pipework connections clearly using the same node referencing as the layout.
The reason we select nodes as junctions is that between junctions the pipework size should always be consistent based on the flow rate in that section
30
M4 : Q17-18 : Index Run
The index run is the pipework run with the greatest overall pressure drop
This is the pressure that the pump driving the system needs to generate
31
M4 : Q17-18 : Index Run
Index Run Possibilities:
Option 1 = ΔP1-2 + ΔP2-3 + ΔP3-4
Option 2 = ΔP1-2 + ΔP2-3 + ΔP3-8
Option 1 = ΔP1-2 + ΔP2-5 + ΔP5-7
Option 1 = ΔP1-2 + ΔP2-5 + ΔP5-6
For a thorough analysis of pressure drop in a system it is necessary to calculate pressure drops in the section between each set of nodes.
All possible combinations are then examined to find the highest possible pressure drop.
For this exercise we are assuming all the UFH manifolds have the same flow and pressure drop through them …..……… so for this case the furthest one will be the highest pressure drop.
32
So manifold at node 4 has the highest pressure drop
M4 : Q17-18 : Index Run
33
M4 : Q17-18 : Index Run
Maximum demand on the manifold is 20kW
We now need to work out the mass flow rate
= ?
34
M4 : Q17-18 : Pipe Pressure Loss
Maximum demand on the manifold is 20kW
= 4.18
= 20oC
= 0.24 l/s
Note:
If you use 4.18 and a kW load you will immediately get l/s
Use tables or spreadsheet provided by CIBSE to size pipework.
Select pipe size based on following constraints:
Pipework should be as small as possible to reduce cost
Limit velocities 0.5-1.5m/s (in the most part to limit noise)
Limit pressure drop to below 300Pa/m
M4 : Q17-18 : Pipe Sizing
Taking the flow rate of 0.24kg/s.
Referring to the CIBSE table opposite it can be seen that to stay below a pressure drop of 300Pa/m we need to use a pipe size of 20mm diameter.
This results in 0.69m/s flow velocity of and 280Pa/m pressure drop.
Note it’s possible to be achieve higher accuracy through interpolation but rarely required.
0.24
280
0.69
20
These numbers can now be added to the call out label as shown.
M4 : Q17-18 : Bend Pressure Drop
Pressure loss factor derivation:
Velocity in this section = 0.69m/s
Pipe size = 20mm
Assume bend
Therefore ζ = 0.92
We can then calculate the pressure drop:
219Pa
Note there are three bends in this section so overall an allowance of 3x219Pa is required (657Pa)
M4 : Q17-18 : Bend Pressure Drop
Note the flow arrangement
For flow pipe we have Diverging flow:
For flow pipe we have:
Diverging flow
Pipe size = 32mm
Converged velocity = 0.83m/s
Converged flow = 0.48kg/s
Branch flow = 0.24kg/s
Flow ratio = 0.24/0.48 = 0.5
Therefore ζ = 0.63
M4 : Q17-18 : Branch Pressure Drop
The pressure drop due to a branch is derived from the following equation:
217Pa
Complete the schematic (note letters denote the reference to the crosshairs)
c
a
b
e
d
f
g
Work out the pressure loss through the system from the riser
Fill in the red blocks in the table opposite
Note: tables etc are available on blackboard
Concluding Thoughts
In your future designs be careful not to over design heating systems, consider careful what loads you use, how you apply diversity and what factors of safety you add.
Modern insulation standards mean that the heat losses are low and we need often to think how to prevent overheating and free cooling
In hydronic systems think carefully about system temperatures and the balance of how your heat emitters work and maximising efficiency in your heat source
Ensure that systems are variable flow and operate efficiently at part load