Review on Energy Resilience

profileharsh55
2019_Jannesar_Optimal-probabilistic-planning-of-passive-harmoni_International-Journal.pdf

Contents lists available at ScienceDirect

Electrical Power and Energy Systems

journal homepage: www.elsevier.com/locate/ijepes

Optimal probabilistic planning of passive harmonic filters in distribution networks with high penetration of photovoltaic generation Mohammad Rasol Jannesara, Alireza Sedighia,⁎, Mehdi Savaghebib, Amjad Anvari-Moghaddamc, Josep M. Guerreroc a Department of Electrical Engineering, Yazd University, Yazd, Iran b Electrical Engineering Section, Mads Clausen Institute, University of Southern Denmark, Odense, Denmark c Department of Energy Technology, Aalborg University, Aalborg, Denmark

A R T I C L E I N F O

Keywords: Harmonic mitigation High photovoltaic penetration Passive harmonic filter Probabilistic planning

A B S T R A C T

In recent years, distribution networks have been increasingly affected by the random nature of harmonic sources introduced by nonlinear load and renewable energy sources (RES) such as photovoltaic (PV) systems. This paper presents an approach based on Genetic Algorithm (GA) and Monte-Carlo Simulation (MCS) for the optimal planning of single-tuned passive harmonic filters (PHFs) in a distribution network. The resistance and inductance of the lines within the network are modeled by frequency dependent characteristics. The probabilistic characteristics of the load and PV system currents are also considered for optimal planning of PHFs. In our optimization model, the objective function minimizes the total PHF installation cost and the energy losses, by considering the total harmonic distortion (THD) of bus voltages and maximum capacity of PHF as constraints. The proposed method is validated by a simu- lation study using an unbalanced three-phase real distribution system. An advantage of this method over most of the conventional approaches is that both harmonic current magnitude and phase angle of real PV systems are taken into account. Numerical results show the applicability and effectiveness of the proposed method.

1. Introduction

Harmonic problems arising from the power electronic-based devices and nonlinear loads are increasing in distribution networks. On the other hand, penetration of renewable energy sources (RES), especially photo- voltaic (PV) systems [1] with power electronic converters is continuously increasing [2]. Due to increasing harmonic currents of nonlinear loads and PV systems, total harmonic distortion of voltage (THDv) is in- creasing. In addition, energy losses [3] and the risk of resonance phe- nomenon [4] may elevate by installing PV systems. Harmonic currents produced by nonlinear loads and PV systems are unpredictable mainly due to different consumers’ energy consumption patterns and inter- mittent shading (due to changing weather conditions caused by clouds, storms, rain, etc.), respectively [5]. Therefore, probabilistic methods should be applied for harmonic analyses [6]. Optimal filter planning is one of the solutions to mitigate harmonic problems [7]. Passive harmonic filters (PHFs) are divided into series, shunt, and series-shunt types. Series and shunt filters mitigate harmonic current in specific order(s) by pro- viding high and low impedance paths, respectively [8]. In addition, ac- tive harmonic filters produce proper harmonic currents to decrease THDv

[9]. The PHFs are still widely used in power systems due to simplicity and low cost [10]. Single-tuned is the most popular, efficient, and eco- nomical type of shunt PHFs [11]. Although in many works, angles of harmonic orders are neglected in harmonic analyses, it is important to consider both magnitude and angle of harmonic currents injected in case of high nonlinear loads and PV systems penetration. By considering the angles of harmonic currents, some harmonic components may cancel out each other. Therefore, the optimal capacity of PHF may be decreased. The IEEE Standard 519-2014 provides a guideline for the limitation and mitigation of harmonics.

Many studies on optimal PHF planning have been conducted in the literature that can be divided to deterministic and probabilistic methods. For instance, authors of [12–14] applied deterministic methods to si- multaneously minimize the investment cost, total harmonic distortion of current (THDI) and THDv of the system buses through a multi-objective filter planning optimization model. However, system losses are neglected in this process. In [15], several objective functions are considered as performance indices in the filter-planning problem but optimal place- ment and sizing are not performed simultaneously. In [16], minimization of power losses and investment cost of PHFs are considered as the

https://doi.org/10.1016/j.ijepes.2019.03.025 Received 17 July 2018; Received in revised form 8 February 2019; Accepted 11 March 2019

⁎ Corresponding author at: Department of Electrical Engineering, Yazd University, University Blvd, Safayieh, Yazd, Iran. E-mail addresses: [email protected] (M.R. Jannesar), [email protected] (A. Sedighi), [email protected] (M. Savaghebi),

[email protected] (A. Anvari-Moghaddam), [email protected] (J.M. Guerrero).

Electrical Power and Energy Systems 110 (2019) 332–348

Available online 19 March 2019 0142-0615/ © 2019 Elsevier Ltd. All rights reserved.

T

objectives of the optimal planning problem. Voltage limits, number/size of installed PHFs, location of PHFs installation and THDv of all buses are taken into account as constraints. In [17], optimal planning of distributed generation (DG) is added to the objective function of [16] and is si- multaneously solved with planning of PHF. Authors of [18] propose the optimal sizing of single-tuned filters to maximize power factor (PF) and transmission efficiency while minimizing energy loss; however, PHF cost is not taken into account. In another study, a multi-objective planning of PHFs and capacitors is performed to decrease PHF cost, energy losses as well as voltage distortion and deviation [19]. In [20,21], an optimal multi-objective design method (without optimal placement) is proposed for different types of PHFs based on the modified Bat algorithm and Pareto front to minimize power loss, THDv, and THDI. In a number of research works, the optimal design of PHF is proposed for increasing the loading of distribution/service transformers. For instance, in [22], comparative evaluation of PHFs is proposed to minimize harmonic loss factor (FHL), THDv, THDI, and displacement power factor (DPF). In [23], an optimal passive filter design approach is provided to maximize the power factor considering frequency-dependent line losses, under the harmonically contaminated voltages and currents. Optimal filter para- meters are also calculated in [24] using different optimization algorithms to maximize the suggested power factor function.

However, in many cases, harmonic currents caused by nonlinear loads and PVs have a probabilistic nature. For example, in [25], a linear approximation method and a chance-constrained programming model are presented for optimal planning of single-tuned PHFs in an industrial network. The objective is to minimize the total filter installation cost, while harmonic current limits and filter component constraints are satisfied with predetermined confidence levels. However, energy losses and optimal sitting of PHFs are not considered in the objective function. The authors of [26] present a new method considering the probabilistic characteristics of harmonic current sources for planning of single-tuned PHFs in a power system. The objective is to minimize the voltage dis- tortion throughout the system while determining the optimal filter lo- cations and sizes. However, PHF cost and energy losses are not taken into account in that work. In [27], the disadvantages of [25] and [26] are covered without considering the energy losses.

In [28], a simplified heuristic approach is proposed for PHF plan- ning to improve power quality indices and minimize the total costs of filter and losses. In the same work, both deterministic and uncertain frameworks are taken into account.

In [29], a new method for studying PHFs planning using Simulta- neous Perturbation Stochastic Approximation (SPSA) is presented and the optimal number, placement, and sizing of PHFs are calculated. However, only PHF cost is included in the objective function and re- duction of energy losses is not taken into account. The objective func- tion and constraints of [30] are very similar to those of [29], but, in [30] three load levels are considered for load modeling and an Adaptive Dynamic Clone Selection Algorithm (ADCSA) is applied for optimiza- tion. However, reduction of energy losses is not considered in [30].

In [10], multiple scenarios including different load levels and har- monic currents are studied for PHF planning. However, similar to [30], energy losses are not modeled in the objective function. Authors of [31] present an approach of combining Feasible-Direction Method and a Genetic Algorithm (FDM + GA) to investigate the planning of PHFs. However, the optimal placement of PHF is not determined in planning approach. In [32], optimal multi-objective planning of PHFs using Hybrid Differential Evolution (HDE) method is investigated. Objective function is defined under three loading levels, but, optimal placement and sizing of PHFs is not computed. Likewise, in [33], a methodology is presented for probabilistic harmonic resonance assessment considering power system uncertainties. This approach uses both Monte-Carlo Si- mulation (MCS) and harmonic resonance mode analysis techniques.

Authors of [34] presented a method for planning PHFs, based on combining Sequential Neural-network Approximation and Orthogonal Arrays (SNAOA). In the objective function, the impacts of THDv and THDI are considered, but, energy losses and PHF cost are not taken into account. In [35], PHF cost is modeled to tackle the shortcoming of [34], but, still energy losses are not included in the optimization.

A scheme for mitigating harmonic problems in distribution systems is presented in [36] by deploying multiple low-cost distributed plug-in active filters and using MCS-based probabilistic harmonic power flow method.

In [37], optimal designing of single-tuned PHFs corresponding to the minimum power losses is addressed. However, optimal PHFs pla- cement and cost are not considered. Authors of [38] formulate the planning problem of PHFs as a probabilistic multi-objective optimiza- tion problem by using a heuristic approach. In [38], the objective function consists of PHF installation cost, probabilistic THDv, and fun- damental voltage index. However, the candidate buses for PHF in- stallation are limited and energy losses are not included in the opti- mization. Optimal probabilistic planning of PHFs is presented in [39] by considering THDv limits and filter capacity as constraints. In the same work, PHFs investment cost and imaginary parts of the harmonic currents are considered, but, energy losses are not taken into account. Authors of [40] present an optimal planning approach for PHFs using the HDE method and considering variations of system impedance, harmonic current sources, and filter tuning frequency. However, in- vestment cost of filter and energy losses are not considered. In [41], the application of PHF at the hybrid renewable microgrid has addressed to reduce THDv and PHF cost taken into account uncertainties of RES.

In the present paper, optimal probabilistic PHF placement and sizing are performed simultaneously by considering nonlinear loads and high PV penetration to minimize THDv, PHFs cost, and energy losses. THDv of buses and maximum capacity of filter are considered as con- straints. In addition, unlike most of the reviewed literature, both magnitude and phase angle of harmonic currents are included in our stochastic studies for PHF planning. To do so, PV harmonic currents are measured by a power analyzer for one week for a single-phase PV system in a real distribution network. Then, by using distribution fitting techniques, the Probabilistic Distribution Function (PDF) of PV mag- nitudes and phase angles are calculated for harmonic orders 1st to 25th. Probabilistic harmonic power flow is also performed by MCS. Inverse- transform method is considered for random variable generation. Additionally, the PDF of load is assumed as a normal PDF. Finally, the resistance and inductance of lines within the examined distribution network are modeled by frequency dependent characteristics.

The rest of this paper is structured as follows: in Section 2, the modeling of filter and distribution network is introduced. Also,

Fig. 1. Single-tuned filter.

Table 1 Values of a and b for cables and transformer.

Equipment Resistance Inductance

Cables a = 0.1; b = 0.9 a = 1; b = −0.65 Transformer a = 0.2; b = 1.5 a = 1; b = −0.03

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

333

probabilistic harmonic load flow and calculation method for PDF of PV current magnitude and phase angle are discussed. Cost function and the methods for optimization are explained in Section 3. In Section 4, computer simulations and numerical results are presented and ana- lyzed. Finally, Section 5 concludes the paper with a brief summary.

2. System modeling

2.1. Filter modeling

PHFs are divided into three groups including series, shunt, and series- shunt. The most common type of PHF is the single-tuned (notch) filter. In

the present paper, this filter type is used to mitigate harmonic effects of nonlinear loads and PV systems due to its low cost and high efficiency. The notch filter presents a low impedance in a specific harmonic current and connects in shunt with the power system (Fig. 1). In addition to harmonic mitigation, notch filters can provide power factor correction.

In notch filters, harmonic tuning order (nres) can be calculated as

=n f fres res

1 (1)

where fres and f1 are resonance and nominal frequencies, respectively. The three-phase rated capacitive power (Qcap) of capacitance and

reactive power (Qind) of inductance can be calculated according to the

Fig. 2. Best PDF fittings of harmonic current magnitude and angle for 3rd, 5th, and 7th orders.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

334

following equations [42] (see Appendix section for more information). In addition, three-phase RMS values for reactive powers of capacitance (Qrmscap) and inductance (Qrmsind) are calculated according to the fol- lowing equations

= = × ×

= = × × = =

= =

Q Q Q V I

Q Q n Q V I

·(1 ), 3 ( ) ( )

·( 1), 3 ( ) ( )

cap tot n rmscap i i cap i i

ind tot res rmsind i i ind i i

1 1

2 1

2

2 1

2 1

2 res2

(2)

where Qtot is the three-phase rated reactive power of a single-tuned filter. Vi cap and Vi ind represent ith order harmonic of voltage across ca- pacitor and inductor, respectively. Ii is ith order of filter current.

PHF power loss can be calculated by the following equations

= = = ×

= × ×X U Q

R X Q

I Q U

P R I 3

3ind ind

act ind

f

tot act act

1 2

1 1

1 2

(3)

where Xind is the inductive reactance for one phase, U1 is nominal line- line voltage, Ract is resistance of PHF, Qf is quality factor, I1 is nominal current magnitude, and Pact is power loss of PHF.

2.2. Distribution line modeling

Due to the skin effect, the internal conductor inductance decreases because of less internal flux linkages and the resistance increases be- cause the effective cross-sectional area decreases [43]. Frequency polynomial characteristic can be defined as (4) for modeling frequency- dependent behavior of power lines.

= + × ×f a a f f

fy ( ) (1 ) y ( )h h

b

1 1

(4)

where fy ( )h and fy ( )1 represent resistance or inductance for h th and first

order harmonics, respectively. a and b are parameters specifying the degree of frequency dependence. This model is used for cables and transformers, while, low voltage (LV) overhead lines are modeled by a tower type of DIgSILENT that considers frequency dependence of lines automatically. To do this, the parameters such as DC-resistance, geo- metrical mean radius (GMR), outer diameter, and distance between overhead and ground lines are set in DIgSILENT. Values of a and b are obtained from DIgSILENT Library and shown in Table 1. These values are selected according to voltage level of cables and transformer.

2.3. Probabilistic distribution functions of load and PV harmonic

THDI of PV system increases when the power production decreases or THDv of PV bus increases [44]. Due to the random nature of the irra- diance, PV harmonics are probabilistic and thus, can be modeled by PDF [45–48]. To represent the harmonic behavior of grid-connected PVs, harmonic current magnitudes and angles of a PV farm are measured in- itially by a power analyzer within one week in an unbalanced three-phase real distribution system. Then, the best probabilistic distribution function is recognized for different harmonic orders using distribution fitting fea- ture in MATLAB. Based on this, it is possible to display the fitted dis- tribution over plots of PDF, cumulative distribution function (CDF), probability plots, and survivor functions. Also, two or more traditional PDFs and non-parametric functions can be fitted by comparing the results, and select the most valid model. In Fig. 2, some best PDF fittings of har- monic current magnitude and angle of the studied PV are shown.

After specifying the most valid PDF for harmonic current magnitude and phase angle in any order (e.g. normal and non-parametric PDF for 5th order harmonic current magnitude and angle, respectively), the inverse CDF is calculated. As explained in the MCS, there are various general methods for generating one-dimensional random variables from a prescribed distribution. In the present paper, the inverse-transform method is considered for random variable generation to increase the convergence rate of MCS. The random variable can be calculated as

=X F U( )1 (5)

where U is the uniform distribution, F−1 is inverse CDF, and X is random variable. Fig. 3 shows the concept of this method [49].

Considering the central limit theorem, the annual average for re- sidential load distribution can be represented by a normal distribution function even if the individual daily loads are not normally distributed. Such assumption has also been made in numerous research works where a normal distribution function is applied for residential loads in distribution systems (e.g. [48,50]). Standard deviation is assumed not very large (equal to 20%) to decrease the variation of load; and thus guarantee the worst case of THDv. Fig. 4 shows the mean value for load harmonic current magnitude and phase angle calculated according to [51].

Fig. 3. Inverse-transform method.

Fig. 4. Load harmonic current.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

335

Fig. 5. Flowchart of the solution methodology.

Fig. 6. The gene’s representation.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

336

2.4. Probabilistic harmonic load flow by MCS

Since PV generation and load are mostly uncertain, probabilistic studies should be carried out. In order to handle the probabilistic load

flow problem, some approaches have been studied in the literature. The proposed procedures could be divided into MCS-based, analytical, and approximate methods [52].

MCS is an iterative method to solve the probabilistic problem. In

Fig. 7. Case study system.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

337

this approach, first of all, sufficient numbers of samples should be generated. There are various general methods for generating one-di- mensional random variables from a prescribed distribution including inverse-transform, Alias, composition, acceptance-rejection, etc. [49]. As already mentioned, the inverse-transform method is considered in the present work for random variable generation.

Unbalanced harmonic load flow is performed in DIgSILENT. In this regard, harmonics of loads and PVs are modeled as current source in- cluding magnitude and angle for orders 1–25. For the nodes that con- tain both load and PV, the total harmonic current can be calculated using Kirchhoff's Current Law in each order. In the harmonic load flow calculation, a steady-state network analysis is carried out at each fre- quency at which harmonic sources are defined.

THDv of buses can be calculated by harmonic load flow and the generated samples of harmonic current sources. Calculating THDv is continued until maximum sample number of MCS is reached. As a re- sult, the PDF of variables such as THDv and energy losses are provided.

3. Objective function and solving method

The objective function that should be maximized is defined as (6) based on net present value:

× + +=

maximize B ir dr

C: 1 1L

N

LOSS L

PHF 1 (6)

where BLOSS is benefit of loss reduction, CPHF is PHF investment cost, ir and dr are inflation and discount rates, and N is the number of opera- tion years. Since the benefit of loss reduction is realized during the planning and operation horizon, its value is multiplied by ++( )irdr

L1 1 to

calculate the present value. Benefit of loss reduction is defined as:

= B =

M LOSS LOSS × Pr × 24 × 3601 ( ) ( )LOSS

S

M

old S new S m 1 (7)

where S and M are generated samples and the maximum sample number of MCS, respectively. LOSS( )old S and LOSS( )new S are losses for generated sample S before and after PHF planning, respectively. Therefore, the expected value of loss reduction is calculated in (7). Also,

Prm is the average daily energy price. The hourly benefit is multiplied by 24 to calculate daily benefit and daily benefit is multiplied by 360 to calculate annual benefit.

PHF investment cost [53] can be defined as

= × + + × + ×C C P C C Q C Q( ) ( ) ( )PHF act act fix cap cap rmscap ind rmsind (8)

where Cact is the PHF resistance cost and Cfix cap is fixed cost of capacitor installation. Also, Ccap and Cind are the PHF capacitor and inductor costs, respectively.

Constraints consist of THDv, RMS voltage limit, and PHF component limit. THDv constraint can be defined as:

> C i NP {THD THD } ;v i v b, ,max (9)

where THDv,max is the maximum allowed THDv at any node i within the studied network with Nb nodes and P{.} denotes the probability of event {.}. Also, C is the confidence or limit level of the allowable probability that is assumed to be 95% in this paper [54]. According to [8] and IEEE Standard 1159-2009, the utilization voltage is permitted to be in the range of −10 to +10 percent of the nominal voltage. As the PHF component constraint, maximum rated reactive power of PHF is limited to 127 kVAr.

Fig. 5 shows the flowchart of the solution methodology. Firstly, modeling of cables, transformers, and overhead lines is performed to consider frequency dependence of distribution line. Also, PDF and in- verse CDF of PVs are calculated by distribution fitting techniques in- troduced in Section 2.3. In the next step, maximum iterations for GA and number of generated samples for MCS are assumed equal to 30 and 100 respectively. Also, the initial generation of GA is created. The format of the gene is shown in Fig. 6. The population size of GA is 200. The range of PHF number, tuning order, rated reactive power, and PHF placement are between 1–7, 2–15, 1–127 (kVAr), and 0–31, respec- tively.

The number of PHFs is optimized by GA. According to Fig. 6, when the number of PHFs is for instance equal to 4 in a generation of GA, the number of genes is equal to 67 (3 genes for PHF number, (4 × 4) genes for tuning order, (4 × 7) genes for rated reactive power, and (4 × 5) genes for PHF placement). In other words, for each PHF, a string con- taining 16 genes (4 genes for tuning order, 7 genes for rated reactive power, and 5 genes for PHF placement) is added to the number of genes. In general, the PHF number is the number of PHFs that are placed in different places by different rated reactive powers and tuning orders (1 PHF in each place).

In the third step, samples of harmonic current magnitude and angle for PVs are determined by inverse-transform method introduced in Section 2.3. To calculate samples of nonlinear loads, a stochastic number is generated according to a normal distribution function. In the next step, unbalanced harmonic load flow is performed by considering

Table 2 PV nodes for each penetration.

Penetration (%) PV nodes

20 T379 and T371 50 T379, T371, T525, T660, and T531 80 T379, T371, T525, T660, T531, T529, T533, and T538

Fig. 8. Box plot of THDv for some buses (rated power is considered as base value).

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

338

load and PV harmonics. Then energy losses, THDv, and thus, value of cost function are evaluated. In the fifth step, the stop criterion for scenario making by MCS is checked.

In the sixth step, if the THDv constraint is not violated, the expected value of the objective function is calculated for the current generation. Then, the stop criterion for the outer loop (which counts the number of GA iterations) is checked. If the maximum number of iterations is reached, the best solution that has the maximum loss reduction and minimum PHF cost is recognized and printed.

4. Numerical result

As demonstrated in Fig. 7, the case study system is a 383-buses real LV distribution system located in Yazd province, Iran.

This system is connected to a 20 kV system by a 20 kV/0.4 kV transformer while feeding 299 nonlinear residential loads. This network is feeding two main feeders that can be divided into upstream (above) and downstream (below) the transformer. In the sub system below the transformer, two single-phase PV systems labeled as PV1 and PV2, each

with the capacity of 5 kW, are located at the end of the feeder connected between phase A and neutral. By considering PV1 and PV2, total active and reactive loads of the feeder below transformer are 141 kW and 64 kVAr, respectively. When no PVs are connected to the network, the maximum active and reactive powers of phase A, B and C are almost equal to 50 kW and 21 kVAr, respectively. Therefore, penetration of PVs located in the real network is equal to 20%. In simulations, the pene- tration of PVs is initially increased to 50% by adding 5 kW PVs to buses T525, T660, and T531. Then, the penetration of PVs reaches 80% (which is regarded here as a high penetration rate) by adding 5 kW PVs to buses T529, T533, and T538. PV nodes for each penetration are summarized in Table 2.

Firstly, the impact of considering harmonic current phase angle on THDv and losses is evaluated. Fig. 8 displays box plots of THDv for different buses without PVs. The top and bottom of each box are the 25th and 75th percentiles of the results, respectively. Also, the line in the middle of each box is the median. As can be seen in Fig. 8, con- sidering phase angle as the real network condition decreases the THDv compared to the situation without phase angle. When harmonic

Table 3 Relation between phase angle and losses (rated power is considered as base value).

Case (without PV) Harmonic losses (kW) Total power losses (kW) Harmonic losses (kW) Total power losses (kW)

Lines Transformer

Without considering phase angles 1.06028 14.8295 3.08661 12.6882 Considering phase angles 0.05445 13.8238 0.09056 9.6922

Fig. 9. Active and reactive powers for secondary side of transformer.

Table 4 Relation between power losses, load, and length of line.

Case Harmonic losses (kW) Total power losses (kW) Harmonic losses (kW) Total power losses (kW)

Lines Transformer

Present network 0.10186 11.8598 0.13473 8.1867 Multiply load by 1.2 0.15326 18.6686 0.20999 12.6605 Multiply length of line by 4 0.64779 70.1259 0.17399 11.5386 Multiply length of line by 4 and load by 1.2 1.08170 127.1628 0.31273 20.1047

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

339

currents are modeled by both phase angle and magnitude, some har- monic currents may cancel out each other and thus, magnitude of harmonic current flowing throughout the network and consequently, THDv is decreased. Due to the harmonic current magnitude reduction, total and harmonic losses for line and transformer are decreased as well (see Table 3). This shows the importance of considering phase angles in modeling harmonic currents. However, phase angles are ignored in

many studies. In Fig. 9, the active and reactive powers for each harmonic order are

shown for the secondary side of transformer (for 80% PV penetration). It should be noted that fundamental frequency active and reactive powers are equal to 19.6 kW and 28 kVAr, respectively.

Note that the current harmonic magnitudes of load and PV for or- ders 2–25 are relatively low and in addition, since phase angles of

Fig. 10. THDv of some buses (fundamental component is considered as base value).

Table 5 Economic parameters.

Prm ($/kWh) N (year) ir (%) dr (%) Cact ($/kW) Cfix cap ($) Ccap ($/kVAr) Cind ($/kVAr)

0.06364 20 1.5 9 100 100 15 300

Table 6 PHFs planning.

Rated reactive power (kVAr) Qrms cap (kVAr) Qrmsind (kVAr) PHF cost ($) Harmonic tuning order Location Average RMS voltage (pu)

Phase A Phase B Phase C

14 36.5 0.36 763.5 7 T371 T371 0.97 0.92 0.93

77 80.6 7.07 3484.3 5 T632 T632 0.97 0.96 0.95

39 14 0.82 562.8 15 T541 T541 0.95 0.96 0.94

15 14 0.22 379.1 13 T519 T519 0.94 0.95 0.93

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

340

harmonic currents are also considered, some harmonic currents cancel each other and thus, as can be seen in Fig. 9, the harmonic active and reactive powers are very low compared with the fundamental frequency powers. Therefore, with respect to these powers, the losses associated with harmonic orders are also very low.

It is noteworthy that network topology and characteristics such as loading conditions and length of distribution lines could affect the harmonic losses. For example, if the system loading is increased or length of lines are considered relatively longer in the test system, it can be clearly observed that the loss values increase. In this regard, please, see Table 4 in which 80% PV penetration is assumed.

Fig. 10 shows the THDv of some buses without and with different PV

penetration rates. Simulation results indicate that THDv of buses increase as we get

farther from the service transformer due to the nonlinear loads and harmonic currents injection by PVs. More importantly, by connecting more PVs to the network, THDvs increase and go beyond the permis- sible ranges, but, the growth rate of THDvs is mitigated. Therefore, with increasing penetration of PVs, the network faces harmonic problems, which have to be addressed suitably. Here, optimal planning of PHFs is used as an effective solution to mitigate the mentioned issues. To this end, single-tuned PHFs with the quality factor (Qf ) of 30 [35] are as- sumed to be optimally placed within the network. In Table 5, the economic parameters used for simulations, including the value of Prm,

(a) Before planning

(b) After planning Fig. 11. Harmonic distortion for T379.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

341

number of operation years, and inflation and discount rates [55] are reported. Also, Cact [41], Cfix cap, Ccap, and Cind are shown in this table [53].

Based on the optimization results for 80% PV penetration, the op- timal capacity (Qtot), Qrmscap, Qrmsind, PHF cost, the harmonic tuning order, location of the three-phase star-connected PHFs, and Average

(a) Upstream feeder

(b) Downstream feeder

Fig. 12. Voltage profile of feeders for phases A, B, and C in full (100%) load.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

342

RMS voltage of PHF location are determined as shown in Table 6. In Fig. 11, individual harmonic voltage distortions (HDv) and voltage waveform of T379 before and after planning are shown.

As it can be seen in Fig. 11(a), the odd orders have high values of HDV before planning. By solving the proposed optimization problem, the fifth, seventh, thirteenth, and fifteenth harmonics are selected as the optimal

(a) Upstream feeder

(b) Downstream feeder

Fig. 13. Voltage profile of feeders for phases A, B, and C in 20% loading.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

343

harmonic tuning order of the planned PHF. In addition, since the 5th order has the maximum value of HDV before planning, the highest cost and rated reactive power of PHFs (77 kVAr) is tuned for this order.

As it can be understood in Fig. 11(b), the 5th, 7th, 13th, and 15th orders HDV are decreased due to PHFs planning resulting to a better voltage quality.

To consider the worst case of harmonic, it is assumed that all loads are equal to their maximum power (full load). Adding PHFs to the network increase the voltage magnitude especially for the nearby buses. However, as can be seen in Table 6, due to heavy loading in this case study, the RMS voltages of PHF candidate buses do not exceed the al- lowable range after placing planned PHFs. As can be seen in Fig. 12 (voltage profile of upstream and downstream feeders for phases A, B, and C), by full loading (100%) and PHF planning, the RMS voltages of

all buses are limited between 0.91 and 0.99. Therefore, RMS voltage constraint is satisfied.

Adding PHF to the case with low loading may increase voltage mag- nitude over allowable range. For very low loading condition, 20% loading is considered as worst case. For this situation, as can be seen in Fig. 13, the RMS voltages of all buses are limited to ±10% of nominal voltage.

In the present case, since all PV units are connected between phase A and neutral, RMS voltage of phase A is bigger than other phases for downstream feeder.

Table 7 shows the average power losses for different phases of lines and transformer in various cases.

According to Table 7, by increasing PVs penetration to 80%, har- monic losses (of lines) and total power losses (of lines and transformer) increase and decrease, respectively. Optimal PHF planning decreases total losses of lines and transformer. It should be noted that in DIgSI- LENT, only line losses can be divided into per-phase values.

According to Table 6, since THDv values are higher for buses that are farther from the service transformer and especially the ones with PVs, T371 is proposed by the optimization algorithm as the candidate bus for PHF with rated reactive power equal to 14 kVAr. In addition, other PHFs are distributed in the network to decrease the losses.

This improvement in THDv and losses is achieved at a net benefit of 17,248.4 $. In addition, increasing the allowable PV penetration, as a results of provided harmonic mitigation, can decrease environmental emission, increase the reliability, limit voltage drops experienced by end-consumers, and defer facility investment and construction of tra- ditional power plants. Also, in summer, PV production matches with cooling load and thus, increases network stability. Therefore, with considering these advantages, mitigating harmonic effects of high PV

Table 7 Average power losses in different cases.

Case Harmonic losses (kW)

Total power losses (kW)

Harmonic losses (kW)

Total power losses (kW)

Phase A losses (kW)

Phase B losses (kW)

Phase C losses (kW)

Lines Transformer Lines

Without PV and PHF 0.07953 13.8488 0.13142 9.7330 4.7779 4.4634 4.5280 With 20% PVs penetration 0.08756 13.4859 0.13620 9.5795 4.3898 4.5475 4.4610 With 50% PVs penetration 0.09710 12.7441 0.13399 8.9626 3.9804 4.4575 4.2092 With 80% PVs penetration 0.10186 11.8598 0.13473 8.1867 3.5511 4.2766 3.9303 With 80% PVs penetration and

PHF 0.17713 9.8163 0.03735 6.2663 2.5728 3.8989 3.1675

Fig. 14. THDv after optimal planning of PHF for 80% PV penetration.

Fig. 15. PDF of THDv for some buses.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

344

penetration is very beneficial. Fig. 14 shows the THDv values of buses by optimal planning of PHF

for 80% PV penetration. As can be seen, due to PHFs planning, the THDv of buses are limited under allowable range (5%).

Figs. 15 and 16 indicate PDF and CDF of THDv for some buses after PHF planning for this PV penetration.

As can be seen from Fig. 15, PDF of THDv for buses that are far from PVs is similar to normal distribution because loads are modeled by normal PDF and PVs are modeled according to measurements and a few of PVs harmonic orders (i.e. only harmonic current magnitude of 5th order) are modeled by normal PDF (see Fig. 2). Also, for the buses which are near PV system, due to the different PDF of loads and PVs, the PDF cannot be easily fitted by well-known distribution function. According to Fig. 16, THDvs of buses T379, T531, and T494 are equal to 3.132%, 1.937%, and 1.521%, respectively, obtained by 95% cumulative

probability. According to economic objective function (6), THDv of buses is maintained below 5% considering a 100% cumulative probability.

The rated reactive power, tuning order, and placement of three- phase star-connected PHFs are calculated to limit THDv of phase A within the allowable range. By such PHFs, THDv of phases B and C caused by nonlinear loads decrease, too.

Since the place of PV depends on consumers’ requests and it is as- sumed that distribution network accepts the requests as much as pos- sible, in this paper, a quasi-worst-case scenario (80%) is considered for optimal PHF planning. 80% penetration is a hypothetical case to guarantee if the penetrations of phases A, B and C are increased to 80% in the future, unacceptable harmonic conditions will not occur in such a network. PHF planning introduced in this paper is a general approach and can be applied for other practical cases, too (e.g., when single- phase PVs are almost evenly connected to all phases or three-phase PVs

Fig. 16. CDF of THDv for some buses.

Fig. 17. System frequency response of T371, T632, T541, and T519.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

345

are added to distribution network). In Fig. 17, the system frequency responses at T371, T632, T541, and

T519 are shown. As it can be seen and also mentioned in [8], single- tuned PHF creates a parallel resonance point at a frequency below the tuned frequency. This resonant frequency must be safely away from main harmonics produced by the loads and PVs.

The convergence analysis of GA is performed, and the results are shown in Fig. 18. It can be seen that the used iteration number is en- ough because GA is converged within a number of iterations less than 30.

5. Conclusion

This paper presented probabilistic optimization of PHFs considering real PV harmonic current and network data to mitigate harmonic im- pacts of PV and nonlinear loads. Due to the random nature of load and PV production, MCS was performed for probabilistic harmonic power flow. To increase the convergence rate of MCS while being computa- tionally-efficient, the inverse-transform method was also applied for random variable generation. To increase the accuracy of results, the proposed method in this work considered both magnitude and phase

angle of harmonic currents, frequency-dependent behavior of the net- work lines, and harmonic losses of the network. Also, the applicability and effectiveness of the proposed approach was tested and evaluated in a real distribution network using realistic information captured from the examined system.

Simulation results indicated that considering current phase angle in harmonic analysis (which denotes the real network condition), could result in lower THDv values compared to situation where phase angle is neglected. It was also observed that THDv of buses increases with dis- tance from the service transformer and PDFs of THDv for buses that are far from PV systems are very similar to a normal distribution. Furthermore, it is understood that by connecting more PVs to the net- work, THDvs are increased. Results also indicated that by increasing the PV penetration to 80%, harmonic losses and total power losses increase and decrease, respectively. Numerical results demonstrated also that by optimal PHF planning, THDvs of all buses could be kept within the al- lowable limits and total losses could be decreased.

It should be mentioned that since the modeling approach in this paper is based on measurement, harmonic interactions between non- linear loads and PV systems have not been taken into account; thus, it is worthy to address this issue in future studies.

Appendix A

By defining Qind and Qcap as following

= =Q U X

U L

U f L2ind ind ind ind

1 2

1 2

1 2

1

Fig. 18. Optimization process of GA.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

346

= =Q U X

U C U f C( ) (2 )cap cap

cap cap 1 2

1 2

1 2

1

In resonance: = =X X f L( ) ( ) 2ind res cap res res ind f C 1

2 res cap = =n f L X2 res ind n f C ind

X n1

1 2 res cap

cap

res1 2

= = = = = ( )

Q U

X X U

X U

X Q

Q Q n(1 ) 1

(1 1 )tot cap ind cap

X n

cap n

cap

n

cap tot res

1 2

1 2

1 2

1 1 2cap

res res res 2 2 2

= = = = =Q U

X X U

n X X U

X n Q

n Q Q n

( 1) ( 1) ( 1)tot

cap ind res ind ind ind res

ind

res ind tot res

1 2

1 2

2 1 2

2 2 2

Appendix B. Supplementary material

Supplementary data to this article can be found online at https://doi.org/10.1016/j.ijepes.2019.03.025.

References

[1] Padmanathan K, Govindarajan U, Ramachandaramurthy VK, Selvi SOT, Jeevarathinam B. Integrating solar photovoltaic energy conversion systems into industrial and commercial electrical energy utilization—A survey. J Ind Inf Integr 2018;10:39–54.

[2] Kalair A, Abas N, Kalair AR, Saleem Z, Khan N. Review of harmonic analysis, modeling and mitigation techniques. Renewable Sustain Energy Rev 2017;78:1152–87.

[3] Nduka OS, Pal BC. Quantitative evaluation of actual loss reduction benefits of a renewable heavy DG distribution network. IEEE Trans Sustain Energy 2018;9(3):1384–96.

[4] Hu H, Shi Q, He Z, He J, Gao S. Potential harmonic resonance impacts of PV inverter filters on distribution systems. IEEE Trans Sustain Energy 2015;6(1):151–61.

[5] Wang Sh, Liu X, Wang K, Wu L, Zhang Y. Tracing harmonic contributions of mul- tiple distributed generations in distribution systems with uncertainty. Int J Elect Power Energy Syst 2018;95:585–91.

[6] Kaddah SS, Abo-Al-Ez KhM, Megahed TF, Osman MG. Probabilistic power quality indices for electric grids with increased penetration level of wind power generation. Int J Elect Power Energy Syst 2016;77:50–8.

[7] Sakar S, Balci ME, Aleem ShHEA, Zobaa AF. Increasing PV hosting capacity in distorted distribution systems using passive harmonic filtering. Elect Power Syst Res 2017;148:74–86.

[8] Dugan RC, McGranaghan MF, Santoso S, Beaty HW. Applied harmonics. Electrical power systems quality. 2nd ed.McGraw-Hill Education; 2004. p. 225–94 chapter 6.

[9] Akagi H. New trends in active filters for power conditioning. IEEE Trans Ind Appl 1996;32(6):1312–22.

[10] Hong YY, Chiu ChSh, Huang ShW. Multi-scenario passive filter planning in factory distribution system by using Markov model and probabilistic Sugeno fuzzy rea- soning. Appl Soft Comput 2016;41:352–61.

[11] Sakar S, Balci ME, Aleem ShHEA, Zobaa AF. Integration of large- scale PV plants in non-sinusoidal environments: considerations on hosting capacity and harmonic distortion limits Review article. Renewable Sustain Energy Rev 2018;82:176–86.

[12] Chen YL. Optimal multi-objective single-tuned harmonic filter planning. IEEE Trans Power Del 2005;20(2):1191–7.

[13] Chang YP, Low Ch. Optimization of a passive harmonic filter based on the neural- genetic algorithm with fuzzy logic for a steel manufacturing plant. Expert Syst Appl 2008;34(3):2059–70.

[14] Chang YP. Integration of SQP and PSO for optimal planning of harmonic filters. Expert Syst Appl 2010;37(3):2522–30.

[15] Chang GW, Chu SY, Wang HL. A new method of passive harmonic filter planning for controlling voltage distortion in a power system. IEEE Trans Power Del 2006;21(1):305–12.

[16] Mohammadi M. Bacterial foraging optimization and adaptive version for econom- ically optimum sitting, sizing and harmonic tuning orders setting of LC harmonic passive power filters in radial distribution systems with linear and nonlinear loads. Appl Soft Comput 2015;29:345–56.

[17] Mohammadi M, Rozbahani AM, Montazeri M. Multi criteria simultaneous planning of passive filters and distributed generation simultaneously in distribution system considering nonlinear loads with adaptive bacterial foraging optimization ap- proach. Int J Elect Power Energy Syst 2016;79:253–62.

[18] Abdul Kahar Nor HB, Zobaa Ahmed F. Application of mixed integer distributed ant colony optimization to the design of undamped single-tuned passive filters based harmonics mitigation. Swarm Evol Comput 2019;44:187–99.

[19] Leite JC, Abril IP, Azevedo MSS. Capacitor and passive filter placement in dis- tribution systems by nondominated sorting genetic algorithm-II. Elect Power Syst Res 2017;143:482–9.

[20] Yang N, Le M. Optimal design of passive power filters based on multi-objective bat algorithm and pareto front. Appl Soft Comput 2015;35:257–66.

[21] Yang N, Le M. Multi-objective bat algorithm with time-varying inertia weights for optimal design of passive power filters set. IET Gener, Transmiss Distrib 2015;9(7):644–54.

[22] Karadeniz A, Balci ME. Comparative evaluation of common passive filter types

regarding maximization of transformer’s loading capability under non-sinusoidal conditions. Elect Power Syst Res 2018;185:324–34.

[23] Aleem ShHEA, Balci ME, Sakar S. Effective utilization of cables and transformers using passive filters for non-linear loads. Int J Elect Power Energy Syst 2015;71:344–50.

[24] Abolfathi K, Babaei M, Ahmarinejad A. Designing optimal passive filters for transformers under harmonic conditions. 4th Int. Conf. Power Energy Syst. Eng. (CPESE 2017), Berlin. 2017. p. 411–7.

[25] Chang GW, Wang HL, Chu SY. A probabilistic approach for optimal passive har- monic filter planning. IEEE Trans Power Del 2007;22(3):1790–8.

[26] Chang GW, Wang HL, Chu SY. Probabilistic approach for passive harmonic filter planning in a power system. 2006 Int. Conf. Power Syst. Technol., Chongqing. 2006. p. 1–5.

[27] Chang GW, Wang HL, Chuang GS, Chu SY. Passive harmonic filter planning in a power system with considering probabilistic constraints. IEEE Trans Power Del 2009;24(1):208–18.

[28] Carpinelli G, Ferruzzi G, Russo A. A heuristic multi-objective approach with trade off/risk analysis issues for passive harmonic filters planning I. Problem formulation and solution algorithm. 8th Mediter. Conf. on Power Gener., Transmiss., Distrib. and Energy Convers. (MEDPOWER 2012), Cagliari. 2012. p. 1–8.

[29] Hong YY, Chiu ChSh. Passive filter planning using simultaneous perturbation sto- chastic approximation. IEEE Trans Power Del 2010;25(2):939–46.

[30] Hong YY, Liao WJ. Optimal passive filter planning considering probabilistic para- meters using cumulant and adaptive dynamic clone selection algorithm. Int J Elect Power Energy Syst 2013;45(1):159–66.

[31] Chang YP, Tseng WK, Tsao TF. Application of combined feasible-direction method and genetic algorithm to optimal planning of harmonic filters considering un- certainty conditions. IEE Proc Gener, Transmiss Distrib 2005;152(5):729–36.

[32] Chang YP, Wu ChJ. Optimal multiobjective planning of large-scale passive har- monic filters using hybrid differential evolution method considering parameter and loading uncertainty. IEEE Trans Power Del 2005;20(1):408–16.

[33] Li Zhaoyang, Hu Haitao, Wang Yang, Tang Li, He Zhengyou, Gao Shibin. Probabilistic harmonic resonance assessment considering power system un- certainties. IEEE Trans Power Del 2018;33(6):2989–98.

[34] Chang YP, Low Ch, Wu ChJ. Optimal design of discrete-value passive harmonic filters using sequential neural-network approximation and orthogonal array. IEEE Trans Power Del Jul. 2007;22(3):1813–21.

[35] Chang YP, Low Ch, Hung ShY. Integrated feasible direction method and genetic algorithm for optimal planning of harmonic filters with uncertainty conditions. Expert Syst Appl 2009;36(2):3946–55.

[36] Bagheri P, Xu W, Ding T. A distributed filtering scheme to mitigate harmonics in residential distribution systems. IEEE Trans Power Del 2016;31(2):648–56.

[37] Ali HAM, Zobaa AF, El-Zahab EEA. Single-tuned passive harmonic filters design with uncertain source and load characteristics. Rec Pate Elect Eng 2012;5(1):72–80.

[38] Carpinelli G, Ferruzzi G, Russo A. Trade-off analysis to solve a probabilistic multi- objective problem for passive filtering system planning. Int J Emerg Elect Power Syst 2013;14(3):2194–5756.

[39] Zhao Y, Deng H, Li J, Xia D. Optimal planning of harmonic filters on distribution systems by chance constrained programming. Elect Power Syst Res 2004;68(2):149–56.

[40] Yang ChF, Lai GG, Su ChT. “Optimal planning of passive harmonic filters using hybrid differential evolution considering variation of system parameters. Int Trans Elect Energy Syst 2013;23(8):1317–34.

[41] Elkholy MM, El-Hameed MA, El-Fergany AA. Harmonic analysis of hybrid renew- able microgrids comprising optimal design of passive filters and uncertainties. Elect Power Syst Res 2018;163(Part A):491–501.

[42] Technical reference documentation: filter/shunt. Germany: Power Factory Co.; 2018.

[43] Wasilewski J, Wiechowski W, Bak CL. Harmonic domain modeling of a distribution system using the DIgSILENT PowerFactory software. 2005 Int. Conf. Futu. Power Syst., Amsterdam. 2005. p. 1–7.

[44] Nduka OS, Pal BC. Harmonic domain modeling of PV system for the assessment of grid integration impact. IEEE Trans Sustain Energy 2017;8(3):1154–65.

[45] Gomez-Gonzalez M, Ruiz-Rodriguez FJ, Jurado F. A binary SFLA for probabilistic

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

347

three-phase load flow in unbalanced distribution systems with technical constraints. Int J Elect Power Energy Syst 2013;48:48–57.

[46] Carpinelli G, Caramia P, Varilone P. Multi-linear Monte Carlo simulation method for probabilistic load flow of distribution systems with wind and photovoltaic generation systems. Renewable Energy 2015;76:283–95.

[47] Abdelsalam AA, El-Saadany EF. Probabilistic approach for optimal planning of distributed generators with controlling harmonic distortions. IET Gener, Transmiss Distrib 2013;7(10):1105–15.

[48] Conti S, Raiti S. Probabilistic load flow using Monte Carlo techniques for dis- tribution networks with photovoltaic generators. Sol. Energy 2007;81(12):1473–81.

[49] Rubinstein RY, Kroese DP. Random number, random variable, and stochastic pro- cess generation. Simulation and the Monte Carlo method. 2nd ed.Wiley; 2007. p. 49–80 chapter 2.

[50] Kabir MN, Mishra Y, Bansal RC. Probabilistic load flow for distribution systems with uncertain PV generation. Appl Energy 2016;163:343–51.

[51] IEEE draft guide for applying harmonic limits on power systems. IEEE P519.1/D12; 2015.

[52] Longatt FMG, Torres JLR. Probabilistic power flow module for powerfactory DIgSILENT. PowerFactory applications for power system analysis. Springer; 2014. p. 61–84 chapter 3.

[53] Kawann C, Emanuel AE. Passive shunt harmonic filters for low and medium voltage: a cost comparison study. IEEE Trans Power Syst 1996;11(4):1825–31.

[54] Compatibility levels for low frequency conducted disturbances and signalling in public low voltage power supply systems. IEC 61000-2-2; 1990.

[55] Leou RC. An economic analysis model for the energy storage system applied to a distribution substation. Int J Elect Power Energy Syst 2012;34(1):132–7.

M.R. Jannesar, et al. Electrical Power and Energy Systems 110 (2019) 332–348

348

  • Optimal probabilistic planning of passive harmonic filters in distribution networks with high penetration of photovoltaic generation
    • Introduction
    • System modeling
      • Filter modeling
      • Distribution line modeling
      • Probabilistic distribution functions of load and PV harmonic
      • Probabilistic harmonic load flow by MCS
    • Objective function and solving method
    • Numerical result
    • Conclusion
    • mk:H1_10
    • Supplementary material
    • References