review the thesis
Proceedings of the Institution of Civil Engineers Structures and Buildings 163 June 2010 Issue SB3 Pages 151–164 doi: 10.1680/stbu.2010.163.3.151
Paper 800013 Received 24/01/2008 Accepted: 07/09/2009
Keywords: failures/stress analysis/ structural frameworks
Robert Mark Lawson SCI Professor of Construction Systems, University of Surrey, Guildford, UK
Jane Richards Technical Director, WSP Cantor Seinuk, London, UK
Modular design for high-rise buildings
R. M. Lawson BSc (Eng), PhD, CEng, MICE, MIStructE, MASCE, ACGI and J. Richards BSc, CEng, MICE
Modular construction is widely used for residential
buildings of four to eight storeys and there is pressure
to extend this relatively new form of construction to 12
storeys or more. This paper reviews recent modular
technologies, and also presents load tests and the
analysis of light steel modular walls in compression. A
design method for high-rise modular applications is
presented taking account of second-order effects and
installation tolerances. For the modular walls tested, it
was found that the plasterboard and external sheathing
boards effectively prevent minor axis buckling of the
C sections, so that failure occurred either by major axis
buckling or local crushing of the section. In all cases, the
results of the tests on 75 mm and 100 mm deep 3
1.6 mm thick C sections exceeded the design resistance
to BS 5950-5 by 10 to 40%. However, an eccentricity of
20 mm in load application reduced the failure load by 18
to 36% owing to local crushing of the C section. Tension
tests on typical connections between the modules and
corridors gave a failure load of 40 kN, which is adequate
to transfer wind forces to a braced core and also to
provide tying action in the event of loss of support to
one corner of a module. Corner posts provide enhanced
compression resistance but their buckling resistance is
dependent on the sway stiffness of the wall panel. It is
also shown that the notional horizontal force approach
for steel structures presented in BS 5950-1 should be
increased for modular construction.
1. INTRODUCTION
Modular construction comprises prefabricated room-sized
volumetric units that are normally fully fitted out in
manufacture and are installed on site as load-bearing ‘building
blocks’. Their primary advantages are
(a) economy of scale in manufacturing of multiple repeated
units
(b) speed of installation on site
(c) improved quality and accuracy in manufacture.
Potentially, modular buildings can also be dismantled and
reused, thereby effectively maintaining their asset value. The
current range of applications of modular construction is in
cellular-type buildings, such as hotels, student residences,
Ministry of Defence (MoD) accommodation and social housing,
where the module size is compatible with manufacturing and
transportation requirements. The current application of
modular construction of all types is reviewed in a recent Steel
Construction Institute Publication 348 (Lawson, 2007). A paper
in The Structural Engineer (Lawson et al., 2005) describes the
mixed use of modules, panels and steel frames to create more
adaptable building forms.
There are two generic forms of modular construction, which
affect their range of application: load-bearing modules in
which loads are transferred through the side walls of the
modules – see Figure 1; and corner-supported modules in
which loads are transferred by way of edge beams to corner
posts – see Figure 2.
In the first case, the compression resistance of the walls
(comprising light steel C sections generally at 300 to 600 mm
spacing) is crucial. Current heights of modular buildings for
this type of construction are typically limited to four to eight
storeys, depending on the particular modular system and the
size and spacing of the C sections used.
In the second case, the compression resistance of the corner
posts is the controlling factor and for this reason, square hollow
sections (SHS) are often used owing to their high buckling
resistance. Building heights are limited only by the size of the
SHS that may be used for a given module size (150 3 150 3
12.5 SHS is the maximum sensible size of these posts).
Figure 1. Partially open-sided module with load-bearing walls (courtesy PCKO Architects)
Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards 151
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
Resistance to horizontal forces, such as wind loads and
robustness to accidental actions, becomes increasingly
important with the scale and height of the building. The
strategies employed to ensure adequate stability of modular
assemblies, as a function of the building height, are
(a) diaphragm action of boards or bracing within the walls of
the modules – suitable for four to six-storey buildings
(b) separate braced structure using hot-rolled steel members
located in the lifts and stair area or in the end gables –
suitable for six to ten storeys
(c) reinforced concrete or steel-plated core – suitable for taller
buildings.
Modules are tied at their corners so that structurally they act
together to transfer wind loads and to provide for alternative
load paths in the event of one module being severely damaged.
This is the scenario presented in Approved document A of the
Building Regulations (HMSO, 2006), which leads to minimum
tying force requirements. A recent paper (Lawson et al., 2008)
reviews the robustness requirements for modular construction
based on a ‘localisation of damage’ route. Modules or load-
bearing elements are removed individually to assess the ability
of the rest of the assembly to support the applied loads at the
accidental limit state.
For taller buildings, questions of compression resistance and
overall stability require a deeper understanding of the
behaviour of the light steel C sections in load-bearing walls
and of the robust performance of connections between the
modules. A further issue in the design of modular construction
is that of installation and manufacturing tolerances, which
cause eccentricities in the compression load path and also lead
to additional horizontal forces applied to the modules. This is
considered later in the paper in the context of design to BS
5950-1 (BSI, 2000), which is the standard for structural
steelwork in buildings.
2. HIGH-RISE BUILDING FORMS USING MODULAR
CONSTRUCTION
Modular construction is conventionally used for cellular
buildings up to eight storeys high where the walls are load-
bearing and resist shear forces owing to wind. However, there
is pressure to extend this technology to high-rise buildings by
using additional concrete cores or structural frames to provide
stability and robustness.
One technique is to cluster modules around a core without a
separate structure in which the modules are designed to resist
compression and the core provides overall stability. This
concept has been used on a major project called Paragon in
west London, shown in Figure 3, in which the modules were
constructed with load-bearing corner posts (a paper on this
project was presented in The Structural Engineer (Cartz and
Crosby, 2007).
The building form may be elongated laterally provided that
wind loads can be transferred to the core. This can be achieved
by using in-plane trusses placed within the corridors, or by
consideration of the structural interaction between the modules
and their attachment to the core. Various alternative high-rise
building forms in which modules are clustered around a core
are presented in Figure 4.
An adaptation of this technology is to design a ‘podium’ or
platform structure on which the modules are placed. In this
way, more open space can be provided for retail or commercial
use or below-ground car parking. Support beams should align
with the walls of the modules and columns are typically
arranged on a 6 to 8 m grid (7.2 m is optimum for car parking),
as shown in Figure 5.
For the modular system covered by the tests reported in this
Figure 2. Open-sided module with corner and intermediate posts supported by a structural frame (courtesy Yorkon and Joule Engineers)
Figure 3. Modular building stabilised by a concrete core (courtesy Caledonian Building Systems)
152 Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
paper, three building projects have been completed to date
based on the enhanced modular technology. Bond Street,
Bristol is a 12-storey student residence and commercial
building in which six to ten storeys of modules sit on a two-
storey steel-framed podium (see Figure 6). The 400 bedroom
modules are 2.7 m external width, but approximately
100 modules are combined in pairs to form ‘premium’ studios
consisting of two rooms. The kitchen modules are 3.6 m
external width. Stability is provided by four braced steel cores,
into which some modules are placed (Figure 7).
A second building, Pitwines in Poole, is an eight-storey student
residence comprising approximately 300 modules. Both
buildings use lightweight cladding attached to the walls of the
modules and comprise terracotta tiles or insulated render
cladding. The nature of the student residential sector is that the
construction period is often less than 12 months, and the
installation of modules is generally carried out in the January
to March period for a September completion. A further project
using this technology has been completed in east London and
another is under way in north London. This last project is
shown under construction in Figure 8.
Another modular manufacturer has developed a system using
1B2P
2B4P
2B4P
2B4P
1B2P
2B4P
9 9
0 0
9 9
0 0
330033006000 6000 12001200
1 2
0 0
2B4P 2B4P
1B2P 1B2P
3B6P
1B2P 1B2P
9 9
0 0
24001200 120060006000
6 6
0 0
6 6
0 0
(a)
(b)
Figure 4. Typical high-rise building forms using modules and concrete cores (courtesy HTA Architects) (2B4P means a two-bedroom, four-person apartment for example): (a) option 1A; (b) option 2B
2·8 m Modules
Core for stairs/lifts
300 mm
3–3·6 m
300 mm
4·5 m
Spa n of
12– 18 m
6 m
Figure 5. Modules supported by cellular beams acting as a podium
Figure 6. Twelve-storey modular student residence at Bond Street, Bristol (courtesy Unite Modular Solutions)
Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards 153
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
SHS corner posts and a concrete floor with perimeter parallel
flange channel (PFC) steel sections. This has been used in eight
to eleven residential buildings, such as the one shown in Figure
9, and construction of taller buildings is in progress. In this
form of heavier modular construction, the effect of
construction tolerances on the forces acting on the corner posts
is much more important –see section 6.4.
3. DESIGN OF
MODULAR WALLS TO
BS 5950-5
Light steel walls and floors in
modular construction are
currently designed to
BS 5950-5 (BSI, 1998), but
interpretation of this standard
is required to take account of
the practical aspects of the
constructional system. In
modular systems with load-
bearing walls, the light steel
C sections in the walls are
subject to potentially
complex loading and
restraint conditions. In most cases, these conditions are as
outlined below.
(a) Axial load is transferred by way of direct wall–wall
bearing, taking into account eccentricities in manufacture
and installation of the modules, which causes additional
build-up of moments and accentuates the local bearing
stresses at the base of the wall.
(b) Loading from the floors and ceilings is taken as applied at
the face of the wall (at an eccentricity of half the wall
width), which causes additional local moments.
(c) Restraint is provided at the floor and ceiling positions so
that the effective height of the wall may be taken as its
clear internal height.
(d) Two layers of plasterboard or similar boards are attached to
the internal face of the wall by screws at not more than
300 mm spacing and provide up to 90 min fire resistance.
(e) Cement particle board (CPB) or oriented strand board (OSB)
are often attached to the exterior of the wall for weather-
tightness of the module and to provide some diaphragm
action. In production, boards may be fixed air-driven pins
enhanced by glued joints.
( f ) In taller modular buildings, second-order (P�˜) effects may occur owing to sway and other eccentricities that are
often neglected in the design of low-rise buildings
The effects of axial loading and eccentricity can be taken into
account in the design of compression members to BS 5950-5
(BSI, 1998), but the stabilising effect of the boards on local and
overall buckling is largely unquantified. It is reasonable to
assume that boards fixed on both sides provide restraint in the
minor axis direction of the C section, but the stiffening effect
of the boards in the major axis (out-of-plane) direction is not
known, nor is the stabilising effect of boards attached only on
one side. This is the subject of the test programme described
below.
4. COMPRESSION TESTS ON MODULAR WALLS
The following tests were carried out to verify the structural
action of the load-bearing walls in a typical modular system.
Two series of tests were carried out: one series on 75 mm
deep 3 45 mm wide 3 1.6 mm thick C sections at the Building
Research Establishment (BRE) and one series on 100 mm
deep 3 42 mm wide 3 1.6 mm thick C sections at the
University of Surrey.
Core 2
Core 4
Core 3
Core 1
Corridor Corridor
Corr idor
Separating wall
Premier room modules
Separating wall
Standard modules
Figure 7. Plan of modular building at Bond Street, Bristol showing the core positions
Figure 8. Eleven-storey modular student residence in north London under construction (courtesy Unite Modular Solutions)
Figure 9. Modular residential building, Wolverhampton (courtesy Vision Modular Structures)
154 Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
The tests were intended to establish the compression resistance
of the C sections, nominally placed at 300 mm spacing, taking
account of the restraining and stiffening effects of various
types of board. The sensitivity to eccentricities up to 20 mm
was also investigated, as this exceeds the maximum that may
be envisaged with good control on installation of modules in
practice.
The panels were loaded using a spreader beam and lateral
restraints in the form of PFC sections, and the test arrangement
is illustrated in Figure 10. The eccentricity in load application
was introduced by a 6 mm thick steel plate inserted at the base
of the wall.
The main variables were the type of boards that are attached
on one or both sides and the eccentricity in axial load.
Additional tests were included on taller walls to examine the
influence of slenderness. The boards were fixed using 2 mm
diameter air-driven nails at 200 mm centres, as used in
production of the wall panels. The boards were attached 2 mm
short of the web of the top and bottom track so that the boards
were not loaded directly.
OSB was attached externally and, in some tests, CPB was
included to assess the difference in restraint provided by the
two types of board. Two layers of 15 mm fire-resistant
plasterboard were used internally, as required for 90 min fire
resistance. In two of the tests,
this plasterboard was omitted.
The walls were first loaded up
to around 100 kN to represent
serviceability loading before
loading incrementally to
failure. Deflections were
recorded at the top of the wall
(vertically and horizontally)
and at mid-height
(horizontally). The test failure
loads are presented in Table 1.
The failure load generally
occurred at a relatively small
vertical displacement of less
than 5 mm.
A further series of tests was
carried out on 2300 mm
high 3 600 mm wide wall
panels, comprising three
100 mm deep C sections
with a mid-height noggin
built into the wall panel to
provide lateral restraint in
the minor axis.
Side B
Roller
Spreader 150 75 18
PFC � �
150 75 18 PFC
� �
2450 mm
11 mm OSB 2 15 mm plasterboard�
75 1·6 C�
Lateral restraint
Jack
Side A
Plate
150 75 18 PFC� �
1200 mm
150 75 18 PFC� �
(6 mm thick) Plate
Figure 10. Test arrangement for BRE wall compression tests
Wall test details Wall height: m Eccentricity of loading: mm
Failure load per C section: kN
Design resistance to BS 5950-5: kN
Model factor
75 3 45 3 1.6C: OSB boards on one side only
2.45 0 64 48 1.33
75 3 45 3 1.6C: Plasterboard on one side,
2.45 0 97 76 (inc. effect of boards) 1.27
OSB on the other 2.77 0 90 56 (inc. effect of boards) 1.61 2.45 10 79 56 (inc. effect of boards) 1.41
2.45 20 62 47 (crushing) 1.31
75 3 45 3 1.6C: Plasterboard on one side, CPB
2.45 0 96 76 (inc. effect of boards) 1.26
on the other 2.45 20 52 47 (crushing) 1.10 100 3 42 3 1.6C: Plasterboard on one side only
2.30 0 57 51 1.13
100 3 42 3 1.6C: CPB on one side only
2.30 0 70 61 1.14
Model factor ¼ Failure load/design resistance
Table 1. Failure loads of C section wall studs and comparison with BS 5950-5
Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards 155
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
Two additional bending tests were carried out on wall panels
using 75 3 1.6 C sections subject to a line load at mid-span.
The purpose was to calculate the effective stiffness of the wall
panels in order to calculate the modified slenderness of the
C section for the compression resistance to major axis buckling.
The cases considered were
(a) OSB board on one side and two layers of plasterboard on
the other (OSB in compression)
(b) OSB board on one side with no plasterboard on the other
(OSB in compression).
The measured values of Ieff taking into account the stiffening
effects of composite action with the boards were
432 3 103 mm4 and 270 3 103 mm4 per C section respectively.
The calculated second moment of area of the bare C section
was 265 3 103 mm4. It follows that the effective inertia is
increased by 62% for boards fixed on both sides but by only
2% for OSB board on one side.
5. ANALYSIS OF WALL TESTS TO BS 5950-5
The light steel walls were analysed in accordance with
BS 5950-5 using measured section dimensions and steel
strengths. Composite action occurred owing to the additional
stiffness of the boards attached to both sides, which increase
the buckling resistance of the wall. The section properties of
the C sections were calculated for the case where the edge lips
are considered to be fully effective.
The strip steel was S350 grade supplied to BS EN 10327 (BSI,
2004b) and measured strengths were in the range 380–405
N/mm2. Calculated compression resistances to BS 5950-5 are
presented in Table 1. The model factor is the ratio of the test
failure load to the compression resistance to BS 5950-5, based
on measured material strengths and geometry.
The attachment of boards to both sides of the wall effectively
prevents minor axis buckling, even for the narrow wall panels
tested and so failure may occur in one of three modes
(a) crushing of the cross-section locally in compression, as in
Figure 11
(b) buckling of the wall in the major axis direction, as in
Figure 12
(c) delamination of the boards from the wall studs, leading to
loss of composite action.
The stiffening effect of the boards leads to a reduction in
slenderness and increase in buckling resistance. Using the
measured 62% increase in bending stiffness of the wall panel,
the effective slenderness of the bare C section is reduced by
22% owing to attachment of the OSB and plasterboards. For a
2.45 m wall panel, the slenderness in the major axis direction
was 79, and so the effective slenderness becomes
0.78 3 79 ¼ 62. This leads to a buckling strength of pc ¼ 263 N/mm2 according to Table 10 of BS 5950-5 when using a Q factor (effective area/gross area) of 0.88.
The calculated compression resistance was 67 kN, which is
approximately 70% of the test result of 97 kN. This suggests
that the buckling curve for cold-formed sections used in
BS 5950-5 is conservative. In addition, local buckling of the
Figure 11. Local crushing of C section in compression tests
Figure 12. Wall failure by overall buckling in pure compression
156 Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
flanges of C section may be reduced by the attachment of the
boards, which increases the effectiveness of the cross-section.
The eccentricity of load application using a plate below the
wall accentuates local crushing, as well as overall buckling.
The crushing resistance of the C section without consideration
of buckling is calculated from Aeff py. The reduced crushing
resistance owing to eccentric loading may be taken into
account by considering a reduced compression area, Aeff .
Because the buckling resistance is approximately 70% of the
crushing resistance, it follows that buckling will occur first
unless the crushing resistance is reduced by over 30%.
A 10 mm eccentricity caused a 19% reduction in load capacity
and a 20 mm eccentricity caused a 36% reduction in capacity.
However, in the tests, a 10 mm eccentricity did not reduce the
failure load below the theoretical buckling capacity.
The second series of tests on walls used 100 3 1.6C sections
with boards on one side only. These tests showed that minor
axis buckling is prevented by fixing to plasterboard for 1.6 mm
thick steel, but the increase in compression resistance relative
to BS 5950-5 was less than for the 75 mm deep sections. This is
attributable to the lower transverse bending stiffness of the
web of the deeper C section, which means that the unsupported
flange is only partially restrained.
6. STRUCTURAL ACTION OF GROUPS OF
MODULES
The structural behaviour of an assembly of modules is complex
because of the influence of the tolerances that are implicit in
the installation procedure, the multiple interconnections
between the modules and the way in which forces are
transferred to the stabilising elements such as vertical bracing
or core walls. The key factors to be taken into account in the
design of high-rise modular buildings are
(a) the influence of initial eccentricities and construction
tolerances on the additional forces and moments in the
walls of the modules
(b) application of the design standard for steelwork, BS 5950-1
to modular technology, using the notional horizontal load
approach
(c) second-order effects due to sway stability of the group of
modules, especially in the design of the corner columns
(d) mechanism of force transfer of horizontal loads to the
stabilising system, for example concrete cores
(e) robustness to accidental actions (also known as structural
integrity) for modular systems.
These aspects are now discussed in turn.
6.1. Influence of constructional tolerances
The National Structural Steelwork Specification for Building
Construction (NSSS) (BCSA, 2007) presents the permitted
tolerances of steel frames, in which the maximum out-of-
verticality of a single column is �H < height/600, but < 5 mm per storey. Furthermore, for steel-framed buildings of more
than ten storeys high, the maximum out of verticality over the
total building height is limited to 50 mm in the NSSS.
BS EN 1090-2 (BSI, 2008) concerns the execution of structures
and in it, the essential tolerances define the maximum
deviations that are permitted so as not to impair the overall
performance of a structure or member. BS EN 1090-2 Table
D.1.12, referring to multi-storey frames, differs from the NSSS
in that the cumulative error over n floors each of height h is
given by h ffiffiffi n
p =300. It follows that the permitted cumulative
deviation over n storeys is 10 ffiffiffi n
p mm (for h ¼ 3 m) to BS EN
1090-2.
These permitted deviations for steel frames may not, however,
reflect the practicalities involved in modular construction
because of the difficulties in precisely positioning one module
on another and in making suitable connections. For a single
module placed on another module, it is proposed that the
maximum out of alignment during installation may be taken as
12 mm in orthogonal plan directions relative to the top of the
module below. This alignment requires careful control on site,
especially in windy conditions.
For a vertical stack of modules, the cumulative positional error,
e, owing to installation can be partially corrected over the
building height. Using the same logic as in BS EN 1090-2, the
cumulative positional tolerance (in millimetres) may be taken
statistically as e < 12 ffiffiffi n
p , where n is the number of modules in
a vertical group. Typically, for n ¼ 10, the total cumulative positional tolerance that is permitted becomes approximately
40 mm, but this neglects the geometric tolerances in the
module manufacture.
An alternative simplified procedure that is easier to control on
site is to limit the cumulative positional tolerance to 5 mm per
module in orthogonal directions with a maximum of 50 mm
(for n ¼ 10), which is similar to the NSSS. However, it is considered that the maximum positional error of one module
on another may be taken as 12 mm (except at ground level
where a maximum of 5 mm should be achievable). This means
that at the first floor, the cumulative tolerance of 10 mm will
control, even if the first-floor module is 12 mm out of position
relative to the base module and the base module is positioned
at < �2 mm from datum.
Added to this positional error is the possibility of a systematic
manufacturing error in the geometry of the modules. For a
single module, the maximum permitted tolerance in geometry
may be taken as illustrated in Figure 13. However, over a large
number of modules, the average error in manufacture may be
taken as half of the permitted tolerance for a single module.
Therefore, the out of verticality of the corner posts may be
taken as h/1000, where h is the module height (typically 3 m).
To take account of manufacturing tolerances, the cumulative
out of verticality over the building height may be taken as
nh/1000, or approximately 3n mm. The total permitted out-
of-verticality �H over the building height, consisting of a stack of n modules vertically, is therefore a combination of
positional and geometric tolerances, approximately as
follows
�H < e þ nh=1000 ¼ 5n þ 3n ¼ 8n mm1
Using this simplified formula, it follows that �H ¼ 80 mm for
Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards 157
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
n ¼ 10 storeys, which is equivalent to approximately h/350 per floor. This is 60% higher than the tolerance permitted for
structural steelwork and reflects the different installation and
connection methods between structural frames and a group of
modules.
It is recommended that the absolute out of verticality in
modular construction is limited to a maximum of 80 mm
relative to a ground datum, which will control for buildings of
ten or more storeys. This is achievable with good control on
installation. Adjustments in module position should be made
gradually rather than at a few positions, which would
otherwise add to local eccentricities. These adjustments can be
made by varying the cavity spacing between the modules. In
detailing, the cavity width should be at least equal to half of
the expected maximum tolerance, or as a simple rule, taken as
a minimum of 40 mm.
6.2. Application of notional horizontal forces in modular
construction
A way of assessing the sway stability of a group of modules is
by using the notional horizontal force approach given in clause
2.4.2.3 of BS 5950-1. For steel frames, this horizontal force
corresponds to 0.5% of the factored vertical load acting per
floor, and is used in the absence of wind loading. It represents
the minimum horizontal force that is used to assess the sway
stability of a frame. A further limit for the combination of
wind and vertical load is that the wind load should not be less
than 1% of the factored dead load acting horizontally. This
may control where the self-weight exceeds the imposed loading
on a floor.
BS EN 1993-1-1 Eurocode 3 clause 5.3.2 (BSI, 2004a) permits
an out-of-verticality of L/200 for a single column, but this is
reduced by a factor of 2/3 when considering the average over a
number of storeys (i.e. �H < L/300). The permitted out of verticality of a whole structure is obtained by multiplying this
value for a single column by a factor of f[0:5 [1 þ (1=m)]g0 :5
for m columns in a group horizontally. The result tends to
�H < L/420, which is higher than in the NSSS, but further requirement in the approach of Eurocode 3 is that this out of
verticality is considered in combination with wind loading
rather than as an alternative load case, as in BS 5950-1.
The combined eccentricity on a vertical assembly of modules
takes into account the effects of eccentricities of one module
placed on another, and the reducing compression forces on the
walls acting at the increased eccentricity with height. This effect
is illustrated in Figure 14. The walls of the module are unable to
resist high moments owing to these effects and so the equivalent
horizontal forces required for equilibrium are transferred as
shear forces in the ceiling, floors and end walls of the modules.
The total additional moment acting on the base module is
therefore given by an effective eccentricity ˜eff multiplied by the compression force in the base module, as follows
� h/500
h Bow /1000� hOut of verticality
/500� h
Datum position
Idealised dimensions Actual dimensions of module
Width tolerance
/500� h
Length tolerance /500� h
Figure 13. Permitted maximum geometric errors in manufacture of modules
P � � � � � �
1 2
1000 e h
�P
P
P
P P
P
∆3
∆2
∆1
h
P( 1)/n n�
P( 2)/n n�
P P
e1 M P� e
e3
e2
V
V 1:1000 1:1000
(a) (b)
Figure 14. Combined eccentricities acting on the ground-floor modules: (a) shear in end walls due to eccentric loading for a four-sided module; (b) transfer of eccentric loading to stabilising system for corner-supported modules
158 Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
Madd ¼ Pwall˜eff
¼ Pwall (n � 1)
n þ 2
(n � 2) n
þ 3 (n � 3)
n . . . þ
1
n
� �
3 (e þ h=1000)
2
where Pwall is the compression force at the base of the ground-
floor module ¼ nWu, n is the number of modules in a vertical assembly, e is the average positional eccentricity per module, h
is the module height (in mm), and Wu is the factored load
acting on each module.
As a good approximation, it is found that the following
formula holds for the effective eccentricity of the vertical stack
of modules as a function of n:
˜eff ¼ n � 1 6
� � 8n3
The effective base eccentricities are presented in Table 2 for
n ¼ 6 to 12 storeys and for a module height, h ¼ 3 m. This eccentricity may be converted to a notional horizontal force
applied at each floor level, which is expressed as a percentage
of the vertical load acting at each floor level, and is defined as
the force which causes the same equivalent moment in the base
module as the effective eccentricity in Equation 2. This
moment is given by
kWun 2 h=2 ¼ Pwall˜eff ¼ nWu˜eff4
where k is the proportion of the factored load acting on each
floor, and so
k ¼ 8(n � 1) 3h
� � or
n � 1 3n
� � 80
h
� � for n . 105
From Table 2, and using the tolerances defined above, it is
calculated that the notional horizontal force varies from 0.5% to
0.9%, when expressed as a percentage of the vertical load
applied to the module. It should be noted that k ¼ 0.5%, when the maximum tolerance is 50 mm, which agrees with BS 5950-1.
For modular construction, it is therefore recommended that the
notional horizontal force is taken as a minimum of 1% of the
factored vertical load acting on each module, which reflects the
higher tolerances that are permitted in modular construction. It
is used as the minimum horizontal load in assessing overall
sway stability of the structure, and it is proposed that it is used
in combination with wind forces.
As an example, for a module of 25 m2 floor area subject to
factored loading of 7 kN/m2, the notional horizontal force
acting in orthogonal directions is approximately 2 kN. For a
vertical stack of ten modules, the base shear is therefore 20 kN.
This shear force may be shared between the two walls of the
module in the direction under consideration. The notional force
may be compared with a wind load of up to 10 times this
magnitude acting as a shear on the longitudinal side façade of
the building, and so is still relatively small. The notional
horizontal force may, however, control when there are less
than 10 modules in a horizontal group.
If the modules are unable to resist the horizontal force required
for overall stability, the forces must be combined for a number
of modules on plan at each level and transferred to the
stabilising system. This may be the case for partially open-
sided modules.
6.3. Forces at module interconnections
The structural interactions within a group of modules are
complex. Horizontal forces may be transferred by tension and
compression forces in the ties at the corners of the modules by
utilising the diaphragm action of the base and ceiling of the
modules. Shear forces may be transferred through the
continuous corridor members rather than the corner
connections because of the potential articulation through the
bolts and connecting plates between the modules. These actions
are illustrated in Figure 15.
Where the corridor floor is used to transfer shear forces, the
connection of the modules to the corridor may be made by a
detail of the form of Figure 16. The extended plate is screw
fixed on site to the corridor members and is bolted to the re-
entrant corners between the modules so that it also acts as a tie
plate. This detail is not used to provide vertical support to the
corridor floor, which is supported on continuous angles
attached to corridor wall of the modules.
The forces in the tie connection in Figure 16 may be calculated
on the basis of the wind forces acting on the module. The
highest force occurs for an external pressure coefficient of
+0.85 and a negative internal pressure of �0.3. The wind force on one module is divided between two module-to-corridor
connections. For a wind pressure of 1.2 kN/m2, the force in this
connection is approximately 8 kN at working loads.
The shear attachment to the core is made both through the
corridor and also at the module adjacent to the core. This
Number of modules
Approx. building height: m
Cumulative out-of-verticality at top of building: mm
Effective eccentricity on base module – Simplified formula in
Equation 3: mm
Notional horizontal force Equation 5: %
n ¼ 6 16 48 5/6 3 48 ¼ 40 0.5 n ¼ 8 22 64 7/6 3 64 ¼ 75 0.7 n ¼ 10 27 80 9/6 3 80 ¼ 120 0.9 n ¼ 12 33 80 11/6 3 80 ¼ 147 0.9
Table 2. Summary of effective eccentricities and notional horizontal forces in modular construction as a function of building height
Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards 159
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
connection force at the core is designed for the aggregate of
the module–corridor connection forces, which for a group of
three to four modules is 24 to 32 kN (factored loading ) or 18
to 24 kN as a working load.
6.4. Stability of corner posts in modular construction
Corner posts add to the compressive resistance of a wall and, if
they are included in the module, it is normal practice to
assume that all the applied vertical loads acting on the module
are resisted by the corner posts. These posts are usually in the
form of steel angle sections for low-rise applications, or SHSs
for taller buildings. The posts are effectively restrained from
buckling by the in-plane stiffness of the walls of the modules
to which they are connected, but this assumption may not be
valid for partially open-sided modules or for highly perforated
walls.
Consider the stability of the corner posts of a module when
restrained only by the in-plane stiffness of the walls of the
module, as illustrated in Figure 17. The posts are discontinuous
at the module–module connections and do not contribute to
the sway stiffness of the structure, but are restrained against
buckling in their height between the connection points.
The initial out of verticality of the corner post increases under
an axial load, P, in each post, which may be approximated by
strut buckling theory, according to
� ¼ �o
1 � 2P=Pcritð Þ 6
where P is the axial compression acting on one post; �o is the initial out of verticality and eccentricity of the corner post; Pcrit is the critical buckling resistance for sway stability of the
module.
From this simple shear failure mechanism, the work done in
Module
(a)
θ Tie
L
B
Tie in corridor
(b)
Forces in ties
Module
Figure 15. Force transfer between modules: (a) force transfer at corridor – bending action; (b) force transfer at corridor – pure shear
80
7030 gap
Bolt hole
Upper module
Lower module
(a)
(b)
Figure 16. Connection detail between the corridor cassette and modules: (a) sketch detail; (b) actual detail
160 Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
shear and compression may be equated, in order to determine
the critical buckling load, Pcrit, as follows
k˜2
2 ¼
2Pcritð Þ˜2 2h
or Pcrit ¼ 0:5kh7
where k is the shear stiffness of the wall panel.
As P approaches Pcrit, so the shear deflection of the wall panel
increases rapidly. Therefore, it is necessary to keep P well
below Pcrit to avoid instability effects. The eccentricity of load
causes both bending in the post and shear in the wall panel.
The shear stiffness of the wall can be estimated from shear
diaphragm tests and corresponds to the horizontal load at a
serviceability deflection of h/500, where h is the module height
in millimetres. This is achieved for a shear force of typically
(a) 10 kN for a 2.4 m wide wall panel with a window, or
approximately 4 kN/m width
(b) 20 kN for a 2.4 m wide unperforated panel, or
approximately 8 kN/m width.
In the case of a module with h ¼ 3 m and width of b ¼ 3.6 m, it follows that the typical shear stiffness of an end wall panel
with a window becomes
k ¼ 4 3 3:6 3 500
3:0 ¼ 2400 kN=m
Inserting this value of k in Equation 7 leads to a critical
buckling load owing to shear in the end wall of a module of
Pcrit ¼ 0:5 3 2400 3 3 ¼ 3600 kN
To check the stability of the corner post, it is recommended
that the eccentricity in load application is taken as the
maximum positional eccentricity of 12 mm when one module
is placed on another plus the maximum out of verticality in
manufacture of a single module (or h/500, as shown in Figure
13). For a 3 m high module, �o ¼ 12 + 6 ¼ 18 mm. These eccentricities are illustrated in Figure 18.
In addition, a local moment is transferred from the floor or
edge beam, which may act in the same sense as the positional
eccentricity. For a floor–wall junction, this shear load may be
assumed to act at the face of the wall studs (or a minimum of
50 mm). For a corner post, the shear load acts at the centre of
the bolt group, and a minimum eccentricity of 75 mm from the
centre of the post may be used. This local moment acts only on
individual modules and is not cumulative.
The additional moment acting on a corner post is calculated
from M ¼ P�, where � is given by Equation 6. For a wall, the effective eccentricity also includes the bow in the wall between
the corners (or h/1000, as shown in Figure 14).
For a corner post, the effective eccentricity is therefore given
by �o ¼ 18 + 75/n mm. For a load-bearing wall, the effective eccentricity is given by �o ¼ 21 + 50/n mm. For n ¼ 10, the effective eccentricities become approximately 25 mm in both
cases.
The stability of a corner post is then checked as
P=Pc þ M=Mc < 1:08
where P is the load acting at the top of the base module and Pc is the compression resistance of the post.
When the post is restrained against buckling in its height by
attachment to the adjacent walls, then the bending resistance
may be taken as Mc ¼ Mel, where Mel is the elastic bending resistance of the post. Elastic properties should be used in order
to take account of uncertainties in this simple linear interaction
method in Equation 8.
For an unsupported post (not restrained by the walls), the
compression resistance is given by Pc ¼ pcA, where pc is calculated from the minor axis slenderness of the post and Mc
B
P P
H
2P
∆ K
φ
Figure 17. Sway stability of the wall of a module for corner posts in compression
Pmax ( 1)n �
nPmax ( 1)n �
n
Wall of module
Floor
Floor
φ 0·002�
� /500h
Ceiling
Mfloor
Pmax Pmax b
w
h
Mfloor � 0·25 wbd
d
e
Figure 18. Illustration of eccentricity of forces applied to the walls or corner posts of a module
Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards 161
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
is the bending resistance for lateral torsional buckling. The
interaction equation is also modified to take into account
bending in two directions, as in BS 5950-1.
As an example for a 7.2 m long 3 3.6 m wide module, with a
factored floor load of 7 kN/m2, the compression force acting at
the top corner of the ground-floor module in a 12-storey
building is approximately
P ¼ 7 3 7:2 3 3:6 3 (12 � 1)=4 ¼ 499 kN
Check the compression resistance of the corner posts using
100 3 100 3 10 SHS (in S355 steel), which are stabilised by
the walls of the modules: crushing resistance, Py ¼ 1239 kN, and bending resistance, Mel ¼ 32.8 kN m.
The out-of-plane displacement and its associated moment, M,
are obtained from Equation 6
�o ¼ 18 þ 75=n ¼ 25 mm
� ¼ 25
1 � 2 3 499=3600ð Þ ¼ 34 mm
M ¼ 499 3 0:034 ¼ 17:0 kN m
Using the linear combination of axial force and moment for
member stability
P=Pc þ M=Mel ¼ 499=1239 þ 17:0=32:8
¼ 0:40 þ 0:52 ¼ 0:92 , 1:0
It follows that the effect of eccentricity in installation and out
of verticality in manufacture is to reduce the compressive
resistance of a corner post by about 60%. It is also
recommended that for simple design, the effective eccentricity
of load acting on the corner post is taken as not less than
35 mm, which allows for a 40% magnification in sway from
the initial eccentricity of 25 mm.
6.5. Robustness to accidental damage
The ability of an assembly of modules to resist applied loads in
the event of serious damage to a module at a lower level is
dependent on the development of tie forces at the corners of
the modules. The loading at this so-called accidental limit state
is taken as the self-weight plus one third of the imposed load
all multiplied by a partial factor of safety of 1.05 to BS 5950-1.
To satisfy ‘robustness’ in the event of accidental damage to one
of the modules, the tie forces between the adjacent modules
may be established on the basis of a cantilever model, as
presented in a recent paper (Lawson et al., 2008). Assuming
that the worst case corresponds to loss of support to one side of
a corner module and that each module above is able to develop
tying forces equally, the tension force in the ties is given as
follows
T ¼ Wab
4h
� � 9
where Wa is the load acting on the module at the accidental
limit state, and b and h are the dimensions of narrow end of
the module.
Figure 19 shows the results of a finite-element analysis of a
module when one corner support is removed, which is a more
likely case than complete removal of one side wall. The applied
load is taken as 10 kN/m per wall for a heavyweight module
using the partial factors noted above. Torsional stiffness of the
module is developed by diaphragm action of the walls and
floor/ceiling. From this analysis, the maximum horizontal tying
force is equal to 26% of the total load applied to the module
(rather than 48% in the cantilever formula) and the maximum
vertical load is approximately 40% of the total load. It is
concluded that the minimum values of the horizontal tying
force, T, may be taken as 30 kN for lightweight modules (self-
weight , 3.5 kN/m2) or 50 kN for heavyweight modules (self-
weight , 6 kN/m2).
6.6. Module connection tests
As part of the development programme for the modular
supplier, tests on complete modules were carried out at the BRE
to assess the tensile resistance of the tie detail between the
corridor cassette and the corner of the module. The tie
connection is made at the re-entrant corner of the module.
The module was held in place at two corners and a tensile force
was applied at the top opposite corner causing pull-out of the
connecting bolt to the 4 mm thick corner angle manufactured
as part of the module. Forces within the module are transferred
by way of in-plane diaphragm action of the ceiling and walls.
A rigid corner gusset plate was attached across the junction
between the bottom track and the end wall stud, and the
tension force reached of 40 kN at failure corresponding to a
displacement of 10 mm. The gusset detail at a load level of
25 kN is shown in Figure 20. The load–deflection graph for
this test is shown in Figure 21.
27 kN
5 kN
1 kN
56 kN
27 kN
5 kN
1 kN
38 kN
38 kN 50 kN
38 kN
3·6 m
2·7 m
10 kN/m
10 kN/m
Deflected shape
7·2 m
32 mm vertically
Figure 19. Illustration of tie forces when support to one corner of a module is removed
162 Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
The test using a stiffening plate at the corner of the module
showed that this arrangement offers the best solution for the
module-to-corridor connection. The characteristic resistance of
this connection is taken as 20% less than the failure load of a
single test, or 0.8 3 40 ¼ 36 kN, which exceeds the calculated load of 24 kN for transfer of wind forces across three modules
to an adjacent core.
7. CONCLUSIONS
This paper presents the results of tests on light steel walls in
compression, which are used to demonstrate the extension of
modular construction up to 12 storeys high. The tests showed
that the stiffening effect of the fascia boards is very high and
that the compression resistance of the C sections is increased in
comparison to the bare steel section. These conclusions refer to
internal wall heights of 2.3 to 2.8 m using 75 mm to 100 mm
deep C sections.
(a) Minor axis buckling is effectively prevented by attachment
of various types of boards on one side only, provided the
steel thickness is not less than 1.6 mm.
(b) The test load capacities exceeded the design resistance to
BS 5950-5 by 10 to 40% due to the stiffening effects of the
attached boards.
(c) The effective bending stiffness of the bare steel sections is
increased by up to 62% due to the attachment of OSB and
CPB boards on both sides.
(d) The effect of 10 mm out-of-plane eccentricity in load
application reduces the failure load by 19%, and the effect
of 20 mm out-of-plane eccentricity accentuates local
crushing and reduces the failure load by 18 to 36%.
The tests on the module-to-module connections showed that a
tying force of 40 kN can be resisted. For robustness to
accidental actions, the minimum tying force between modules
should be taken as 30 kN for lightweight modules (self-weight
, 3.5 kN/m2) and 50 kN for heavyweight modules.
The effect of installation and geometric inaccuracies must be
taken into account in the design of modular buildings. It is
proposed that the maximum positional error is 12 mm for one
module placed on another. When combined with
manufacturing tolerances, it is proposed that the maximum out
of verticality should not exceed 8 mm per module in a vertical
group (or an absolute maximum of 80 mm) relative to ground
datum. Using these tolerances, the notional horizontal force
used to evaluate stability of a group of modules should be
taken as a minimum of 1% of the applied vertical load on the
modules, which acts in combination with wind loading but at
reduced load factors.
For modules designed with corner posts, it is shown that an
additional effect owing to the shear flexibility of the end walls
has to be taken into account when calculating the moments
acting on the posts due to sway effects. The minimum
eccentricity for design of the corner posts should not be less
than 35 mm taking account of second-order effects, and the
minimum eccentricity for design of load-bearing side walls
should not be less than 25 mm.
ACKNOWLEDGEMENTS
The structural testing at the Building Research Establishment
was funded by Unite Modular Systems Ltd as part of their
development strategy. The contribution of Dave Brooke and the
team in the Heavy Structures Lab at BRE is gratefully
acknowledged. Additional wall tests at the University of Surrey
were funded by Metek UK Ltd.
REFERENCES
BCSA (British Constructional Steelwork Association) (2007)
National Structural Steelwork Specification for Building
Construction, 5th edn. BCSA, London.
BSI (British Standards Institution) (1998) Structural Use of
Steelwork in Building. Code of Practice for Design of Cold
Formed Thin Gauge Sections. BSI, London, BS 5950: Part 5.
BSI (2000) Structural Use of Steelwork in Building. Code of
Figure 20. Tensile test on module with stiffening plate
�10·00
0·00
10·00
20·00
30·00
40·00
50·00
�5 0 5 10 15 20 25 30 Deflection mm
L o a d : kN
Figure 21. Load–displacement results for module test with stiffening plate. Unite module corner test 7
Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards 163
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
Practice for Design of Simple and Continuous Construction:
Hot Rolled Sections. BSI, London, BS 5950 Part 1.
BSI (2004a) Eurocode 3: Steel Structures – General Rules and
Rules for Buildings. BSI, London, BS EN 1993-1-1.
BSI (2004b) Specification For Continuously Hot-dip Zinc Coated
Structural Steel and Strip – Technical Delivery Conditions.
BSI, London.
BSI (2008) Execution of Steel Structures and Aluminium
Structures. Part 2 Technical Requirements for Execution of
Steel Structures. BSI, London, BS EN 1090-2.
Cartz JP and Crosby M (2007) Building high-rise modular
homes. The Structural Engineer 85(l9): 20–21.
HMSO (2006) England and Wales Approved Document A.
HMSO, London
Lawson RM (2007) Building design using modules. The Steel
Construction Institute, London, Publication 348.
Lawson RM, Ogden RG, Pedreschi R, Popo-Ola S and Grubb J
(2005) Developments in pre-fabricated systems in light steel
and modular construction. The Structural Engineer 83(6):
28–35.
Lawson RM, Byfield M, Popo-Ola S and Grubb J (2008)
Robustness of light steel frames and modular construction.
Proceedings of the Institution of Civil Engineers, Buildings
and Structures 161(1): 3–16.
What do you think? To discuss this paper, please email up to 500 words to the editor at [email protected]. Your contribution will be forwarded to the author(s) for a reply and, if considered appropriate by the editorial panel, will be published as discussion in a future issue of the journal.
Proceedings journals rely entirely on contributions sent in by civil engineering professionals, academics and students. Papers should be 2000–5000 words long (briefing papers should be 1000–2000 words long), with adequate illustrations and references. You can submit your paper online via www.icevirtuallibrary.com/content/journals, where you will also find detailed author guidelines.
164 Structures and Buildings 163 Issue SB3 Modular design for high-rise buildings Lawson • Richards
Downloaded by [] on [14/12/18]. Copyright © ICE Publishing, all rights reserved.
- 1. INTRODUCTION
- Figure 1
- 2. HIGH-RISE BUILDING FORMS USING MODULAR CONSTRUCTION
- Figure 2
- Figure 3
- Figure 4
- Figure 5
- Figure 6
- 3. DESIGN OF MODULAR WALLS TO BS 5950-5
- 4. COMPRESSION TESTS ON MODULAR WALLS
- Figure 7
- Figure 8
- Figure 9
- Figure 10
- Table 1
- 5. ANALYSIS OF WALL TESTS TO BS 5950-5
- Figure 11
- Figure 12
- 6. STRUCTURAL ACTION OF GROUPS OF MODULES
- 6.1. Influence of constructional tolerances
- Equation 1
- 6.2. Application of notional horizontal forces in modular construction
- Figure 13
- Figure 14
- Equation 2
- Equation 3
- Equation 4
- Equation 5
- 6.3. Forces at module interconnections
- Table 2
- 6.4. Stability of corner posts in modular construction
- Equation 6
- Figure 15
- Figure 16
- Equation 7
- Equation 8
- Figure 17
- Figure 18
- 6.5. Robustness to accidental damage
- Equation 9
- 6.6. Module connection tests
- Figure 19
- 7. CONCLUSIONS
- ACKNOWLEDGEMENTS
- Figure 20
- Figure 21
- REFERENCES
- BCSA 2007
- BSI 1998
- BSI 2000
- BSI 2004a
- BSI 2004b
- BSI 2008
- Cartz and Crosby 2007
- HMSO 2006
- Lawson 2007
- Lawson et al. 2005
- Lawson et al. 2008